MG34M422
MG34M422
MG34M422
Contents
1 Introduction 1-1
1.1 Introduction 1-1
1.1.1 Sequence of Operation 1-2
7 Troubleshooting 7-1
7.1 Status Messages 7-1
7.1.1 Warnings/Alarm Messages 7-1
9 Index 9-1
1 1
1 Introduction
1.1 Introduction
Unit controller
VFD
130BC396.13
Start/stop
Oil solenoid
The VLT® Compressor Drives utilize and combine Danfoss The frequency converter is 100% preset for speed open
design and manufacturing expertise. Our extensive loop configuration with 0-10 V reference corresponding to
application knowledge of refrigeration, air conditioning, 1800-5400 RPM for CDS 302 and 1500-6000 RPM for CDS
and motion controls ensures an optimized product design 303.
and package solution:
• Operational efficiency
1 1
The dedicated frequency converter functionality includes: • High Pressure Switch
The high-pressure switch must be connected to
• Start Up
input terminal 37 of the frequency converter in
Once the frequency converter has a start
command, the compressor runs up to 3000 RPM series with the other safety devices.
and remains at that speed for 10 s. Once this
initial time is complete, the frequency converter 1.1.1 Sequence of Operation
slowly ramps to the reference speed.
All compressor types have strong demands of speed limits
• Shut Down
to ensure the oil lubrication of the bearings. Therefore, fast
The stop command bypasses the normal ramp
acceleration from standstill to minimum speed with a
time and the frequency converter ramps the
special start ramp is important, when a start command is
compressor to stop fast.
given. This is also the reason why the Compressor Drive
• Short Cycle Prevention trips with an alarm [A49] Speed Limit, if the speed falls
The frequency converter has a minimum running below minimum speed e.g. when the current limit
time of 12 s, with an interval between starts of 5 controller reduces the speed due to a high load. This alarm
minutes (300 s). The short cycle delay values are is reset automatically after 30 s and the compressor
adjustable in parameter group 28-0* Short Cycle restarts.
Protection.
• Crankcase Heater
On VSH088 and VSH117, when the compressor is
stopped, the frequency converter provides a DC
current to the compressor motor. The DC current
keeps the oil warm and an external crankcase
heater is not needed.
VSH170 needs an external crankcase heater
(surface sump heater or belt type).
WARNING Compressors
The voltage of the frequency converter is dangerous Do not to throw away a used compressor, but dispose of it
whenever the converter is connected to mains. Incorrect and its oil at a specialized recycling company site.
fitting of the motor or frequency converter may damage
the equipment, or cause serious injury, or death. It is
NOTICE!
essential to comply with the instructions in this manual as Imposed limitations on the output frequency
well as local and national rules and safety regulations. (due to export control regulations):
From software versions 2.4x (CDS 302) and 1.0x (CDS 303),
CAUTION
The VLT® Compressor Drives DC link capacitors remain
These Operating Instructions can be used for all CDS 302
charged after power has been disconnected. To avoid an
Compressor Drives® with software version 2.4x. The software
electrical shock hazard, disconnect the frequency converter
version number can be read in 15-43 Software Version.
from the mains before carrying out maintenance. Wait at
least as follows before doing service on the frequency
converter: CDS 303 Operating Instructions Software version: 1.0x
CDS 302 and CDS 303: 11-22 kW 15 minutes
High voltage can be present on the DC link even when the
LEDs are turned off.
2.1.3 Disposal These Operating Instructions can be used for all CDS 303
Compressor Drives® with software version 1.0x. The software
version number can be read in 15-43 Software Version.
• The ground leakage current exceeds 3.5 mA 2.1.10 Avoid Unintended Start
2 2 • The [Off] key is not a safety switch. It does not
disconnect the frequency converter from mains While the frequency converter is connected to mains, the
motor can be started/stopped using:
2.1.6 General Warning
• digital commands
Touching the electrical parts may be fatal - even after the • references
equipment has been disconnected from mains. Also make • via the Local Control Panel (LCP)
sure that other voltage inputs have been disconnected,
Disconnect the frequency converter from mains whenever
such as load-sharing (linkage of DC intermediate circuit).
personal safety considerations make it necessary to avoid
Using VLT® Compressor Drives: Wait at least 15 minutes.
unintended start. To avoid unintended start, always press
Shorter time is allowed only if indicated on the nameplate
[OFF] before changing parameters. An electronic fault,
for the specific unit.
temporary overload, a fault in the mains supply, or lost
motor connection may cause a stopped motor to start. A
2.1.7 Leakage Current frequency converter with Safe Torque Off provides a
certain degree of protection against such unintended start,
CAUTION if the Safe Torque Off Terminal 37 is on low voltage level
or disconnected.
The ground leakage current from the frequency converter
exceeds 3.5 mA. Ensure good mechanical ground
connection (terminal 95) to the ground cable. Use at least 2.2 Safe Torque Off
10 mm2 cable cross section or 2 times rated ground wires
terminated separately. The frequency converter can perform the safety function
Safe Torque Off (STO, as defined by EN IEC 61800-5-21) and
Stop Category 0 (as defined in EN 60204-12).
2.1.8 Residual Current Device Before integration and use of Safe Torque Off in an instal-
lation, perform a thorough risk analysis to determine
CAUTION whether the Safe Torque Off functionality and safety levels
This product can cause a DC current in the protective are appropriate and sufficient. Safe Torque Off is designed
conductor. Where a ground fault interrupter (GFI) is used and approved suitable for the requirements of:
for extra protection, only use an GFI of Type B (time • Safety Category 3 in EN 954-1 (and EN ISO
delayed) on the supply side of this product. See also RCD 13849-1)
Application Note, MN90G. Protective grounding of the
frequency converter and the use of RCDs must always
• Performance Level "d" in EN ISO 13849-1:2008
follow local and national regulations. • SIL 2 Capability in IEC 61508 and EN 61800-5-2
• SILCL 2 in EN 62061
2.1.9 IT Mains 1) Refer to EN IEC 61800-5-2 for details of Safe torque off
(STO) function.
CAUTION 2) Refer to EN IEC 60204-1 for details of stop category 0
Data for EN IEC 62061, EN IEC 61508, EN IEC 61800-5-2 STO EN Safe Torque Off
61800-5-2
• SIL 2 Capability, SILCL 2
SS1 EN 61800 Safe Torque Off 1
• PFH (Probability of Dangerous failure per -5-2
Hour)=7e-10FIT=7e-19/h
• SFF (Safe Failure Fraction) >99% Table 2.1 Abbreviations Related to Functional Safety
Liability Conditions • When external forces influence the motor axis (for
2 2 Ensure that qualified personnel installs and operates the
Safe Torque Off function:
example, suspended loads), more measures are
required (for example, a safety holding brake) to
eliminate potential hazards
• Read and understand the safety regulations Safe Torque Off Installation and Set-Up
concerning health and safety/accident prevention
WARNING
• Understand the generic and safety guidelines
SAFE TORQUE OFF FUNCTION!
given in this description and the extended
description in the relevant Design Guide The Safe Torque Off function does NOT isolate mains
voltage to the frequency converter or auxiliary circuits.
• Have a good knowledge of the generic and safety Perform work on electrical parts of the frequency converter
standards applicable to the specific application or the motor only after isolating the mains voltage supply
User is defined as: and waiting the length of time specified in 2.1 Safety and
Warnings. Failure to isolate the mains voltage supply from
the unit and waiting the time specified could result in
• integrator
death or serious injury.
• operator
130BA874.10
A safety relay evaluates the E-Stop button signals and
triggers an STO function on the frequency converter in the
2 2
event of an activation of the E-Stop button (See Figure 2.4).
This safety function corresponds to a category 0 stop
12/13 37
(uncontrolled stop) in accordance with IEC 60204-1. If the
function is triggered during operation, the motor runs
down in an uncontrolled manner. The power to the motor
is safely removed, so that no further movement is possible.
It is not necessary to monitor plant at a standstill. If an
external force effect can occur, provide additional
measures to prevent any potential movement (for example
mechanical brakes).
NOTICE!
For all applications with Safe Torque Off it is important
that short circuit in the wiring to T37 can be excluded.
Exclude the short circuit as described in EN ISO 13849-2 D4
Figure 2.2 Jumper between Terminal 12/13 (24 V) and 37 by the use of protected wiring (shielded or segregated).
NOTICE!
When using the SS1 function, the brake ramp of the
frequency converter is not monitored with respect to
37 safety.
5 4
Example with Category 4/PL e application
Figure 2.3 Installation to Achieve a Stopping Category 0 (EN Where the safety control system design requires two
60204-1) with Cat. 3 /PL “d” (ISO 13849-1) or SIL 2 (EN 62061). channels for the STO function to achieve Category 4/PL e,
implement one channel via Safe Torque Off T37 (STO) and
the other by a contactor. Connect the contactor in either
1 Frequency converter the frequency converter input or output power circuits and
2 [Reset] key controlled by the Safety relay (see Figure 2.6). The
3 Safety relay (cat. 3, PL d or SIL2 contactor must be monitored through an auxiliary guided
4 Emergency stop button contact, and connected to the reset input of the Safety
5 Short-circuit protected cable (if not inside installation IP54 Relay.
cabinet) Paralleling of Safe Torque Off input the one Safety Relay
Safe Torque Off inputs T37 (STO) may be connected
Table 2.2 Legend to Figure 2.3
directly if it is required to control multiple frequency
converters from the same control line via one Safety Relay
Safe Torque Off Commissioning Test
(see Figure 2.7). Connecting inputs increases the probability
After installation and before first operation, perform a
of a fault in the unsafe direction. A fault in one frequency
commissioning test of the installation using Safe Torque
converter can result in all frequency converters becoming
Off. Moreover, perform the test after each modification of
enabled. The probability of a fault for T37 is so low, that
the installation.
130BC974.10
2 2 1 2
SIL2. K1
1
130BC972.10
12
2
12
3
37
K1
4
K1
37
4
Figure 2.4 STO Example
1
Table 2.5 Legend to Figure 2.6
130BC973.10
12
18
37
4
Figure 2.5 SS1 Example
1 Frequency converter
2 [Reset] key
3 Safety relay
4 Emergency stop
130BC975.10
removing the 24 V DC voltage supply to the
3
2 terminal 37.
2. After activation of Safe Torque Off (that is, after
12
the response time), the frequency converter
coasts (stops creating a rotational field in the
motor). The response time is typically less than 10
ms.
4 The frequency converter is guaranteed not to restart
creation of a rotational field by an internal fault (in
accordance with Cat. 3 of EN 954-1, PL d acc. EN ISO
20 13849-1 and SIL 2 acc. EN 62061). After activation of Safe
Torque Off, the display shows the text ”Safe Stop
37
activated”. The associated help text says, "Safe Stop has
been activated. This means that the Safe Torque Off has
5 been activated, or that normal operation has not been
1
resumed yet after Safe Torque Off activation”.
20 NOTICE!
The requirements of Cat. 3 (EN 954-1)/PL “d” (ISO 13849-1)
37
are only fulfilled while 24 V DC supply to terminal 37 is
kept removed or low by a safety device which itself fulfills
1
Cat. 3 (EN 954-1) PL “d” (ISO 13849-1). If external forces act
on the motor, it must not operate without additional
measures for fall protection. External forces can arise for
example, in the event of vertical axis (suspended loads)
20
where an unwanted movement, for example caused by
37 gravity, could cause a hazard. Fall protection measures can
be additional mechanical brakes.
Figure 2.7 Paralleling of Multiple Drives Example
By default the Safe Torque Off function is set to an
Unintended Restart Prevention behaviour. Therefore, to
1 Frequency converter resume operation after activation of Safe Torque Off,
2 24 V DC 1. reapply 24 V DC voltage to terminal 37 (text Safe
3 [Reset] key Torque Off activated is still displayed)
4 Safety relay
2. create a reset signal (via bus, Digital I/O, or
5 Emergency stop
[Reset] key.
Table 2.6 Legend to Figure 2.7
The Safe Torque Off function can be set to an Automatic
3 How to Install
3 3
3.1 Environment 3.2 Mechanical Installation
3.1.1 Ambient Temperature and Altitude 3.2.1 Accessory Bags
The normal ambient temperature supported by the CDS is Find the following parts included in the accessory bag:
-14000000 °F to +122 °F without derating. The CDS
operates normally down to -4 °F with only the LCP display
130BT330.10
function impaired but without performance reduction.
130BT346.10
Altitude [ft/m] Derating factor
3280/1000 1 61 68
39 42 50
53 54
6561/2000 0.90
01
03 02
04
06 05
WARNING
8202/2500 0.86 Risk of Electric
Discunnect
mains and
:
Shock - Dual
supply
loadsharing
before service
9842/3000 0.82
Figure 3.2 Enclosure B3, IP20/Chassis
11482/3500 0.78
01
03 02
06 05 04 61 68
39 42 50
53 54 5
Mechanical Installation 95
99
A C D
39 42 50 53 54 5
E
F
G H
I
J K
WARNING:
ISOA0021
130BT348.10
130BA419.10
RELAY 1
RELAY 2
01
03 02
06 05 04 61 68
39 42 50
53 54 5
WARNIN
Risk of G:
DisconnElectric Shock
ect mains - Dual supply
and loadsha
ring before
service
95
a
3 3 99
130BA219.10
130BA228.11
1
B1 B2 B3 B4 C1 C3
Height [inch/mm]
Backplate A 18.90/480 25.59/650 15.71/399 20.47/520 26.77/680 21.65/550
Distance between mounting holes a 17.87//454 24.57/624 14.96/380 19.49/495 25.51/648 20.51/521
Width [inch/mm]
Back plate B 9.53/242 9.53/242 6.50/165 9.06/230 12.13/308 12.13/308
Distance between mounting holes b 8.28/210 8.28/210 5.51/140 7.87/200 10.71/272 10.63/270
Depth [inch/mm]
Without option C 10.24/260 10.24/260 9.80/249 9.53/242 12.21/310 13.11/333
With option C 10.24/260 10.24/260 10.24/260 9.53/242 12.21/310 13.11/333
Screw holes [inch/mm]
c 0.47/12.0 0.47/12.0 0.32 0.49/12.0
d Ø 0.75/19.0 Ø 0.75/19.0 0.47/12.0 Ø 0.75/19.0
e Ø 0.35/9 Ø 0.35/9 0.34/8.8 0.33/8.5 Ø 0.35/9 0.33/8.5
f 0.35/9 0.35/9 0.31/7.9 0.59/15 0.38/9.8 0.67/17
Other Specifications
Max. weight [lbs/kg] 50.4/23 59.53/27 26.46/12 51.81/23.5 99.21/45 77.16/35
3 3 CAUTION
Cables general:
Always comply with national and local regulations on cable cross-sections.
• Remove cable entry from the frequency converter (avoiding foreign parts in the frequency converter when
removing knockouts)
• The knockout can now be removed with a strong mandrel and a hammer
130BA720.10
NOTICE!
Frequency converter sizes differ, but terminal numbers are
always the same. Incoming power is always 91, 92, 93 3 3
labeled L1, L2, L3.
NOTICE!
For correct cable dimensions see 8 General Specifications.
130BT332.10
NOTICE!
Frequency converter sizes differ but terminal numbers are
always the same. Incoming power is always 91, 92, 93
labeled L1, L2, L3.
130BA714.10
B2
L1 91
L2 92
L3 93
Figure 3.8 How to Connect to Mains and Grounding for B3
without RFI
L1 91
L2 92
L3 93
U 96
V 97 W
95 98 DC-88
DC+89
R-81
R+82
99
130BA389.10
NOTICE!
Always wire terminal 96 (U) to T1, 97 (V) to T2, and 98 (W)
3 3 to T3.
91 92 93
L1 L2 L3
130BC399.10
95
bag.
4. Insert terminals 96 (U), 97 (V), 98 (W) and motor
91 9
2 93 compressor cable to terminals labeled MOTOR.
5. Fasten screened cable to decoupling plate with
screws and washers from the accessory bag.
6. Connect U, V, W for motor compressor clockwise.
95
91 9
2 93
96
97 9
8
88 8 99
9
81 8
2
130BT333.10
Compressor Cables
Screening of cables
Avoid installation with twisted screen ends (pigtails). They 3 3
reduce the screening effect at higher frequencies.
Aluminum conductors
L3
L 2 93
Aluminium conductors are not recommended. Terminals
L1
91
92
accept aluminium conductors, but clean the conductor
surface and remove and seal the oxidation by neutral acid-
free Vaseline grease before the conductor is connected.
Furthermore, the terminal screw must be retightened after
two days due to the softness of the aluminium. It is crucial
to keep the connection a gas tight joint, otherwise the
Figure 3.15 How to Connect to Mains and Ground without aluminium surface oxidizes again.
Mains Disconnect
3.3.8 Compressor Motor Protection
3.3.6 Motor Compressors Cables The frequency converter fully provides electrical
compressor motor protection.
Correct dimensioning of motor compressor cable cross-
section and length is described in the application manual. • The frequency converter makes through an
electronic current measurement anti-overload and
• Use a screened/armored motor compressor cable lock-rotor compressor motor protection (see
to comply with EMC emission specifications description in the application manual).
• Keep the motor compressor cable as short as • The frequency converter is protected against
possible to reduce the noise level and leakage short circuits on compressor terminals T1, T2, T3
currents
• If a mains phase is missing, the frequency
• Connect the motor compressor cable screen to converter trips or issues a warning (depending on
both the decoupling plate of the frequency the load)
converters and to the metal cabinet of the motor
compressor
• If a compressor motor phase is missing, the
frequency converter trips
• Make the screen connections with the largest
• The frequency converter is protected against
possible surface area (cable clamp). Use the ground faults on compressor motor terminals T1,
supplied installation devices in the frequency T2, T3
converter for making the screen connections.
130BA012.12
130BT248.10
3 3
3
55
54
53
50
42
39
37
69 20
68
61 33
32
29
27 4
19
2 18
13
12
To remove the cable from the terminal: 2. Connect terminals 18, 27 and 37 to +24 V
(terminal 12/13)
1. Insert a screwdriver in the square hole. Default settings:
18 = start
2. Pull out the cable.
27 = coast inverse 3 3
130BT311.10
9 - 10 mm
(0.37 in)
Use terminal 37 as input for safe stop. In rare cases, control cables more than 100 m (330 ft) and analog signals result in
50/60 Hz ground loops due to noise from mains supply cables. If this situation occurs, break the screen or insert a 100 nF
3 3 capacitor between screen and chassis. Connect the digital and analog inputs and outputs separately to the frequency
converter common inputs (terminal 20, 55, 39) to avoid ground currents affecting the system.
Control cables must be shielded/armored. To connect the screen to the frequency converter decoupling plate for control
cables, use a clamp from the accessory bag.
130BT340.10
Eliminate low-frequency noise currents between two
frequency converters by connecting one end of the screen
to terminal 61. This terminal is connected to ground via an
internal RC link. To reduce the differential mode
interference between the conductors, use twisted-pair
3 3
cables.
a. Correct grounding
Control cables and cables for serial communication must
be fitted with cable clamps at both ends to ensure the
best possible electrical contact.
b. Wrong grounding
Do not use twisted cable ends (pigtails). They increase the
screen impedance at high frequencies.
3 3
The frequency converter has a high leakage current and must be grounded appropriately for safety reasons according to EN
50178. The ground leakage current from the frequency converter exceeds 3.5 mA. To ensure a good mechanical connection
3 3 from the ground cable to the ground connection (terminal 95), the cable cross-section must be at least 10 mm2 or 2 rated
ground wires terminated separately.
Controls using an external controller with 0-10 V signal. It is not necessary to change any parameters, as this is the default
value.
Controls using an external controller with 4-20 mA signal. Change switch 53 from U to I. It is not necessary to change any
parameters, as this is the default value.
130BC398.10
NOTICE!
To ensure compliance with IEC 60364 for CE or NEC 2009
for UL, use fuses and/or circuit breakers on the supply side
of the unit for protection of electrical components within
the frequency converter.
WARNING
Personnel and property must be protected against the
consequence of component break-down internally in the
frequency converter.
NOTICE!
The recommendations given do not provide UL branch
circuit protection.
3.4.3 CE Compliance
Fuses or circuit breakers are mandatory to comply with IEC 60364. Danfoss recommends using a selection of the following.
3 3 The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, 480 V, 500 V, or
600 V depending on the unit's voltage rating. With the proper fusing, the frequency converter short circuit current rating
(SCCR) is 100,000 Arms.
Enclosure Power [kW] Recommended Recommended Recommended circuit Max trip level [A]
Size fuse size Max. fuse breaker
Moeller
B1 5.5-7.5 gG-25 (5.5) gG-80 PKZM4-63 63
gG-32 (7.5)
B2 11 gG-50 gG-100 NZMB1-A100 100
B3 5.5 gG-25 gG-63 PKZM4-50 50
B4 7.5-15 gG-32 (7.5) gG-125 NZMB1-A100 100
gG-50 (11)
gG-63 (15)
C1 15-22 gG-63 (15) gG-160 (15-18.5) NZMB2-A200 160
gG-80 (18.5) aR-160 (22)
gG-100 (22)
C2 30-37 aR-160 (30) aR-200 (30) NZMB2-A250 250
aR-200 (37) aR-250 (37)
C3 18.5-22 gG-80 (18.5) gG-150 (18.5) NZMB2-A200 150
aR-125 (22) aR-160 (22)
C4 30-37 aR-160 (30) aR-200 (30) NZMB2-A250 250
aR-200 (37) aR-250 (37)
Enclosure Power [kW] Recommended Recommended Recommended circuit Max trip level [A]
Size fuse size Max. fuse breaker
Moeller
B1 11-15 gG-40 gG-80 PKZM4-63 63
B2 18.5-22 gG-50 (18.5) gG-100 NZMB1-A100 100
gG-63 (22)
B3 11-15 gG-40 gG-63 PKZM4-50 50
B4 18.5-30 gG-50 (18.5) gG-125 NZMB1-A100 100
gG-63 (22)
gG-80 (30)
C1 30-45 gG-80 (30) gG-160 NZMB2-A200 160
gG-100 (37)
gG-160 (45)
C2 55-75 aR-200 (55) aR-250 NZMB2-A250 250
aR-250 (75)
C3 37-45 gG-100 (37) gG-150 (37) NZMB2-A200 150
gG-160 (45) gG-160 (45)
C4 55-75 aR-200 (55) aR-250 NZMB2-A250 250
aR-250 (75)
Enclosure Power [kW] Recommended Recommended Recommended circuit Max trip level [A]
Size fuse size Max. fuse breaker
Moeller
B1 11-18 gG-25 (11) gG-80 PKZM4-63 63
gG-32 (15)
B2 22-30
gG-40 (18.5)
gG-50 (22) gG-100 NZMB1-A100 100
3 3
gG-63 (30)
B3 11-15 gG-25 (11) gG-63 PKZM4-50 50
gG-32 (15)
B4 18.5-30 gG-40 (18.5) gG-125 NZMB1-A100 100
gG-50 (22)
gG-63 (30)
C1 37-55 gG-63 (37) gG-160 (37-45) NZMB2-A200 160
gG-100 (45) aR-250 (55)
aR-160 (55)
C2 75 aR-200 (75) aR-250 NZMB2-A250 250
C3 37-45 gG-63 (37) gG-150 NZMB2-A200 150
gG-100 (45)
C4 55-75 aR-160 (55) aR-250 NZMB2-A250 250
aR-200 (75)
UL Compliance
Fuses or circuit breakers are mandatory to comply with NEC 2009. Danfoss recommends using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, 480 V, 500 V, or
600 V depending on the unit's voltage rating. With the proper fusing, the frequency converter’s Short Circuit Current Rating
(SCCR) is 100,000 Arms.
1) FWH-fuses from Bussmann may substitute FWX for 240 V frequency converters.
2) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V frequency converters.
1)170M fuses shown from Bussmann use the -/80 visual indicator. –TN/80 Type T, -/110 or TN/110 Type T indicator
fuses of the same size and amperage may be substituted.
3 3
130BC400.10
The BASIC Cascade/Pack Controller is used for up to 3 running on the frequency converter or running
compressors to control up to two on/off compressors on the mains
together with one variable speed compressor. The capacity
control is typically based on suction pressure feedback, but
• Pack Status, is a readout of the status for the
Pack Controller. The display shows that the Pack
it could also be e.g. a cold room temperature.
Controller is disabled, all compressors are off, and 3 3
emergency has stopped all compressors, all
Fixed Lead Compressor compressors are running, fixed speed
The BASIC Pack Controller allows the frequency converter compressors are being staged/destaged.
to control up to 3 compressors using the frequency
converter's two built-in relays. The variable compressor • If a no load need occurs, then destaging ensures
that all fixed speed compressors are stopped
(lead) is connected directly to the frequency converter,
individually followed by the variable speed
while 2 bilt-in relays control the other 2 compressors.
compressor.
NOTICE!
Only one fixed speed compressor can be controlled with 3.5.3 Pack Compressor Wiring Diagram
the built-in relays. To control two fixed compressors, an
extra relay is needed via the MCB 105 Relay Option. The wiring diagram shows an example with the built-in
BASIC Cascade Controller with one variable speed
Bandwidth Management compressor (lead) and two fixed speed compressors, a 4-20
In pack control systems, to avoid frequent switching of mA transmitter and System Safety Interlock.
fixed speed compressors, the desired system load is kept
within a bandwidth rather than at a constant level. The
130BD448.10
L1/L2/L3 L1/L2/L3 L1/L2/L3
Staging Bandwidth provides the required bandwidth for
operation. When a large and quick change in system load
RELAY from MCB 105
130BX505.11
Power
Relay from
MCB 105
card
SAFE STOP
3 3
37
4 Quick Set-up
CAUTION
When the connections are made, the compressor starts
automatically.
CAUTION
If an error trips the frequency converter, it automatically
tries to restart the compressor after 30 s (unless the error
is severe and causes a trip lock). See also 14-20 Reset Mode Figure 4.2 Speed Open Loop, Auto On Mode
and 14-21 Automatic Restart Time.
4. Done.
4.1.2 Open Loop with External Reference
1. Apply analog speed reference signal (0-10 V) on 4.1.3 PID Closed Loop with 4-20 mA
terminal 53 using the terminal 55 as common. Pressure Transmitter
See 3.3.14 Basic Examples of Control Connections.
1. Connect pressure transmitter to analog input on
2. Check if switch A53 is positioned to U (voltage)
terminal 54 according to 3.3.14 Basic Examples of
instead of I (current). The switch A53 is on the
Control Connections.
frequency converter and is visible when the LCP
is removed. 2. Make sure that the switch for analogue input 54
is set to “I” for current input.
3. Press [Quick Menu], go to “PID Closed Loop” and Feedback [unit]. The pressure [psi] is going to be
then to “Basic PID Settings) menu. shown in the upper right corner of the display
Now change parameters to
This is what the screen will look like, after configuring the
1-00 Configuration Mode: Select [3] Process
frequency converter for Closed loop application.
3-01 Reference/Feedback Unit: Select [71] Psi
3-02 Minimum Reference and 3-03 Maximum
Reference: Enter the lower and upper limits of the
4 4 setpoint range [psi].
3-15 Reference Resource 1: Select [0] No function
for fixed setpoint.
6-22 Terminal 54 Low Current + 6-23 Terminal 54
High Current: The values of these parameters
should match the output of the pressure
transmitter (4-20 mA for example is the factory
setting).
6-24 Terminal 54 Low Ref./Feedb. Value +
6-25 Terminal 54 High Ref./Feedb. Value: Set range
Figure 4.3 Closed Loop
of pressure transmitter (factory setting -14/+174
psi)
Return to 3-13 Reference Site: Select [2] Local to
run with a fixed setpoint adjustable via LCP. 5. Ready to Run: Press [Hand On] and set reference
Select [1] Remote if the setpoint is given by the in psi using the arrows on the display. Before
analog input (as defined in 3-15 Reference leaving the site, never forget the next step.
Resource 1). 6. Ready to Run: Press [Auto On].
4. Press [Quick Menu], go to My Personal Menu, go For more details on PID Closed Loop, see Figure 4.4.
to 0-22 Display Line 1.3 Small and select [1652]
To set up other dedicated compressor features press [Quick Menu] and go to Q4 or follow Figure 4.5.
4 4
4 4
5 How to Program
130BA018.13
5.1 How to Program on the Graphical LCP
5.1.1 Control Panel a
Status 1(0)
1234rpm 10,4A 43,5Hz
The following instructions are valid for the graphical LCP
(LCP 102):
The control panel is divided into four functional groups:
5 5
1 b
43,5Hz
1. Graphical display with Status lines. All data is
displayed in a graphical LCP display, which can
Run OK c
show up to five items of operating data while
displaying [Status].
Quick Main Alarm
2. Menu keys and indicator lights - changing 2 Status
Menu Menu Log
parameters and switching between display
functions.
3. Navigation keys and indicator lights (LEDs).
Ca
ck
n
Ba
ce
4. Operation keys and indicator lights (LEDs).
Info
3 On OK
Warn.
Alarm
Hand Auto
4 Off Reset
on on
a. Status line:
Status messages displaying icons and graphic.
b. Line 1-2:
Operator data lines displaying data defined or chosen by
the user. By pressing the [Status] key, up to one extra line
can be added.
c. Status line:
Status messages displaying text.
5.1.4 Indicator Lights [Quick Menu] allows quick access to different Quick Menus
such as:
If certain threshold values are exceeded, the alarm and/or Q1 - My Personal Menu
warning LED lights up. A status and alarm text appear on
Q2 - Quick Set-up
the control panel. The on LED is activated when the
frequency converter receives mains voltage. Q3 – PID Process Loop
Q4 - Compressor Functions
• Green LED/On: Control section is working.
Q5 - Changes Made
• Yellow LED/Warn.: Indicates a warning.
Q6 - Loggings
5 5 • Flashing Red LED/Alarm: Indicates an alarm
Q7 - Load Profile
130BP044.10
[Hand On] enables control of the frequency converter via 5.2.5 Data Storage in LCP
the LCP. [Hand on] also starts the motor compressor, and it
is now possible to enter the motor compressor speed data 1. Go to 0-50 LCP Copy in the Main Menu.
by means of the arrow keys. The key can be selected as [1]
2. Press [OK].
Enable or [0] Disable via 0-40 [Hand on] Key on LCP.
External stop signals activated by means of control signals 3. Select [1] All to LCP.
or a serial bus will override a “start“ command via the LCP. 4. Press [OK].
The following control signals will still be active when
[Hand on] is activated: All parameter settings are now stored in the LCP indicated
by the progress bar. When 100% is reached, press [OK].
[Auto On] enables the frequency converter is to be 5. Disconnect mains supply and wait until the
controlled via the control terminals and/or serial communi- display turns off.
cation. When a start signal is applied on the control 6. Reconnect the mains supply.
terminals and/or the bus, the frequency converter will
7. Drive initialized [A80] (Alarm 80) appears - the
start. The key can be selected as [1] Enable or [0] Disable
frequency converter is now reset.
via 0-42 [Auto on] Key on LCP.
14-22 Operation Mode initializes all except:
NOTICE!
An active HAND-OFF-AUTO signal via the digital inputs has • 8-30 Protocol
higher priority than the control keys [Hand on] and [Auto • 8-31 Address
on].
• 8-32 FC Port Baud Rate
[Reset] is used for resetting the frequency converter after • 8-33 Parity / Stop Bits
an alarm (trip). It can be selected as [1] Enable or [0] • 8-34 Estimated cycle time
Disable via 0-43 [Reset] Key on LCP.
• 8-35 Minimum Response Delay
The parameter shortcut can be carried out by holding • 8-36 Max Response Delay
down the [Main Menu] key for 3 seconds. The parameter • 8-37 Max Inter-Char Delay
shortcut allows direct access to any parameter.
• 14-50 RFI 1
• 4-** Limits/Warnings
1. Disconnect from mains and wait until the display • 5-** Digital In/Out
turns off. • 6-** Analog In/Out
2. Press [Status] - [Main Menu] - [OK] at the same • 7-** Controls
time while power up for LCP 102, Graphical
Display.
• 8-** Comm. and Options
NOTICE!
Stop the motor compressor before performing this
operation.
5 5
6 Parameter Descriptions
Table 6.1 lists the parameters that cannot be changed from the LCP. These parameters are defined by the compressor
choice made in 1-13 Compressor Selection.
130BP075.10
Figure 6.2 Set-up 1
OR
130BP076.10
Figure 6.3 Set-up 2
Figure 6.1 Edit Set-up After the link is complete, 0-13 Readout: Linked
Set-ups will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are
0-12 This Set-up Linked to now the same in Set-up 1 and Set-up 2. If there
are changes to a ‘not changeable during
Option: Function:
operation’ parameter, e.g. 1-30 Stator Resistance
To enable conflict-free changes from one set-up
(Rs), in Set-up 2, they will also be changed
to another during operation, link set-ups
automatically in Set-up 1. A switch between Set-
containing parameters which are not changeable
up 1 and Set-up 2 during operation is now
during operation. The link will ensure synchro-
possible.
nizing of the ‘not changeable during operation’
parameter values when moving from one set-up [0] Not linked
to another during operation. ‘Not changeable [1] Set-up 1
during operation’ parameters can be identified by [2] Set-up 2
the label FALSE in the parameter lists in [3] Set-up 3
6.16 Parameter Lists. [4] Set-up 4
0-12 This Set-up Linked to is used by Multi set-up
in 0-10 Active Set-up. Multi set-up is used to move
from one set-up to another during operation (i.e.
while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up
2 whilst the motor is running. Program in Set-up
1 first, then ensure that Set-up 1 and Set-up 2
are synchronized (or ‘linked’). synchronization can
be performed in two ways:
1. Change the edit set-up to [2] Set-up 2 in
0-11 Edit Set-up and set 0-12 This Set-up Linked to
to [1] Set-up 1. This will start the linking (synchro-
nizing) process.
6 6
2 {1,2}
[1612] Motor Voltage
3 {3}
[1613] Frequency
4 {4}
[1614] Motor current
Table 6.3 Example: Set-up 1 and Set-up 2 are [1615] Frequency [%]
linked [1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
0-14 Readout: Edit Set-ups / Channel
[1619] KTY sensor temperature
Range: Function: [1620] Motor Angle
0* [-2147483648 - View the setting of 0-11 Edit Set-up for [1622] Torque [%]
2147483647 ] each of the four different communication [1630] DC Link Voltage
channels. When the number is displayed in [1632] Brake Energy /s
hex, as it is in the LCP, each number [1633] Brake Energy /2 min
represents one channel.
[1634] Heatsink Temp.
Numbers 1-4 represent a set-up number;
[1635] Inverter Thermal
‘F’ means factory setting; and ‘A’ means
[1636] Inv. Nom. Current
active set-up. The channels are, from right
[1637] Inv. Max. Current
to left: LCP, FC-bus, USB, HPFB1-5.
[1638] SL Controller State
Example: The number AAAAAA21h means
[1639] Control Card Temp.
that the FC bus selected Set-up 2 in
0-11 Edit Set-up, the LCP selected Set-up 1 [1650] External Reference
and all others used the active set-up. [1651] Pulse Reference
[1652] Feedback[Unit]
[1653] Digi Pot Reference
6.2.2 0-2* LCP Display [1654] Feedback 1 [Unit]
[1655] Feedback 2 [Unit]
Define the display in the Graphical Logic Control Panel. [1660] Digital Input
0-20 Display Line 1.1 Small [1661] Terminal 53 Switch Setting
6 6
unit selected (see ). The actual calculated
[2580] Cascade Status
value can be read in 16-09 Custom Readout,
[2581] Compressor Status
and/or shown in the display be selecting
[2587] Inverse Interlock
[16-09] Custom Readout in 0-20 Display Line
[2827] Discharge Temperature 1.1 Small to 0-24 Display Line 3 Large.
[9913] Idle time
[0] None
[9914] Paramdb requests in queue
[1] %
[9917] tCon1 time
[5] PPM
[9918] tCon2 time
[10] min
[9919] Time Optimize Measure
[11] RPM
0-25 My Personal Menu [12] PULSE/s
Range: Function: [20] liter / sec.
Size [0 - Define up to 20 parameters to include in [21] liter / min
related* 9999 ] the Q1 Personal Menu, accessible via the [22] liter / hr.
[Quick Menu] key on the LCP. The [23] m³ / sec.
parameters will be displayed in the Q1 [24] m³/min
Personal Menu in the order they are [25] m³ / hr.
programmed into this array parameter. [30] kg / sec.
Delete parameters by setting the value [31] kg/min
to « 0000 ». [32] kg / hr.
[33] ton / min
0-21 Display Line 1.2 Small [34] ton / hr.
Option: Function: [40] m / sec.
Options are the same as in [41] m/min
0-20 Display Line 1.1 Small [45] m
[1614] * Motor Current [A] [60] °C
[70] mbar
0-22 Display Line 1.3 Small
[71] bar
Option: Function:
[72] Pa
Options are the same as in 0-20 Display
[73] kPa
Line 1.1 Small.
[74] m WG
[1610] * Power [kW]
[80] kW
0-23 Display Line 2 Large [120] GPM
[121] gal / sec.
Option: Function:
[122] gal/min
Options are the same as in 0-20 Display
[123] gal / hr.
Line 1.1 Small.
[124] CFM
[1613] * Frequency [Hz]
[125] ft³/s
[126] ft³/min
[127] ft³/h
0-30 Unit for User-defined Readout 0-40 [Hand on] Key on LCP
Option: Function: Option: Function:
[130] lbs / sec. [1] Enabled Prevents unauthorised start in Hand mode.
[131] lbs / min.
[2] Password
[132] lbs / hr.
[140] ft/s 0-41 [Off] Key on LCP
[141] ft/min Option: Function:
[145] ft Options are the same as in 0-40 [Hand on] Key on LCP.
[160] °F
[170] psi
0-42 [Auto on] Key on LCP
[171] lb/in² Option: Function:
[172] in. wtr. gage Options are the same as in 0-40 [Hand on] Key on LCP.
6 6 [173] ft WG
[180] HP
0-43 [Reset] Key on LCP
Option: Function:
0-31 Min Value of User-defined Readout Options are the same as in 0-40 [Hand on] Key on LCP.
Range: Function:
0 CustomRea- [ -999999.99 - This parameter sets the 6.2.4 0-5* Copy/Save
doutUnit* par. 0-32 min. value of the custom
CustomRea- defined readout (occurs at Copy parameter settings between set-ups and to/from the
doutUnit] zero speed). Only possible LCP.
to set different from 0 is
when selecting a linear unit 0-50 LCP Copy
in 0-30 Unit for User-defined Option: Function:
Readout. For Quadratic and [0] * No copy
Cubic units the minimum [1] All to LCP Copies all parameters in all set-ups from
value will be 0. the frequency converter memory to the
LCP memory.
0-32 Custom Readout Max Value [2] All from LCP Copies all parameters in all set-ups from
Range: Function: the LCP memory to the frequency
100 CustomRea- [ par. 0-31 - This parameter sets the max converter memory.
doutUnit* 999999.99 value to be shown when [3] Size indep. from Copies only the parameters that are
CustomRea- the speed of the motor has LCP independent of the motor size.
doutUnit] reached the set value for
0-51 Set-up Copy
4-13 Motor Speed High Limit
[RPM] or 4-14 Motor Speed Option: Function:
High Limit [Hz] (depends on [0] No copy
setting in 0-02 Motor Speed [1] Copy to set-up 1 Copies all parameters in the present edit
Unit). set-up (defined in par. 0-11 Edit Set-up) to
Set-up 1. Likewise, select the option
corresponding to the other set-up(s).
6.2.3 0-4* LCP Keypad [2] Copy to set-up 2
[3] Copy to set-up 3
Enable and disable individual keys on the LCP keypad.
[4] Copy to set-up 4
0-40 [Hand on] Key on LCP [9] Copy to all Copies the parameters in the present set-
Option: Function: up over to each of the set-ups 1 to 4.
6 6 Option: Function:
NOTICE!
This parameter cannot be adjusted while
the motor is running.
Select the application control principle to be
used when a Remote Reference (via analog
input) is active. A Remote Reference can only
be active when 3-13 Reference Site is set to [0]
or [1].
[0] * Speed Enables speed control (without feedback signal
open loop from motor) to the input signal over the
compressor speed range.
[3] Process Enables the use of process control in the
frequency converter. The process control
parameters are set in parameter groups 7-2*
Process PID Feedback and 7-3* Process PID
Control.
Parameters for reference handling, definition of limitations, 0.00%* [-100.00 Must remain 0 for Open Loop Control.
and configuration of the reaction of the frequency - 100.00 The preset reference is stated as a percentage
converter to changes. %] of the value RefMAX (3-03 Maximum Reference)
or as a percentage of the other external
3-00 Reference Range references. If a RefMIN 0 (3-02 Minimum
Option: Function: Reference) is programmed, the preset
Select the range of the reference signal and reference is calculated as a percentage of the
the feedback signal. Signal values can be full reference range, i.e. on the basis of the
positive only, or positive and negative. The difference between RefMAX and RefMIN.
minimum limit may have a negative value,
unless [1] Speed closed loop control is selected
Afterwards, the value is added to RefMIN.
When using preset references, select [16]
6 6
in 1-00 Configuration Mode. Preset ref. bit 0, [17] Preset ref. bit 1 or [18]
[0] * Min. - Max For positive values only Preset ref. bit 2 for the corresponding digital
[1] -Max - For both positive and negative values inputs in parameter group 5-1* Digital Inputs.
+Max
3-12 Catch up/slow-down value
3-01 Reference/Feedback Unit Range: Function:
Option: Function: 0 %* [0 - Enter a percentage (relative) value to be either
Select the unit to be used in Process PID Control 100 %] added to or deducted from the actual reference
references and feedbacks. for Catch up or Slow down respectively. If Catch
[0] None up is selected via one of the digital inputs
[71] * bar (5-10 Terminal 18 Digital Input to 5-15 Terminal 33
[60] °C Digital Input), the percentage (relative) value is
added to the total reference. If Slow down is
[160] °F
selected via one of the digital inputs
[170] psi
(5-10 Terminal 18 Digital Input to 5-15 Terminal 33
3-02 Minimum Reference Digital Input), the percentage (relative) value is
Option: Function: deducted from the total reference. Obtain
extended functionality with the DigiPot function.
Enter the minimum reference. The minimum reference
See parameter group 3-9* Digital Potentiometer.
is the lowest value obtainable by summing all
references. Minimum reference is active only when
3-13 Reference Site
3-00 Reference Range is set to [0] Min.- Max..
Option: Function:
The minimum reference unit matches:
Select which reference site to activate.
• The choice of configuration in 1-00 Configu-
[0] Linked to Use the local reference when in Hand mode;
ration Mode: for [1] Speed closed loop.
Hand / Auto or the remote reference when in Auto mode
• The unit selected in 3-01 Reference/Feedback
[1] Remote Use the remote reference in both Hand
Unit.
mode and Auto mode
[2] Local Use the local reference in both Hand mode
and Auto mode
3-03 Maximum Reference
Option: Function: 3-14 Preset Relative Reference
Enter the maximum reference. Range: Function:
0.00%* [-100.00 - Define a fixed value (in %) to be added to
100.00 %] the variable value (defined in 3-18 Relative
Scaling Reference Source). The sum of the
fixed and variable values is multiplied with
the actual reference. This product is then
added to the actual reference (X+X*Y/100)
to give the resultant actual reference.
NOTICE! NOTICE!
If [1] S-ramp Const Jerk is selected and the reference during If [1] S-ramp Const Jerk is selected and the reference during
ramping is changed the ramp time may be prolonged in ramping is changed the ramp time may be prolonged in
order to realize a jerk free movement which may result in order to realize a jerk free movement which may result in
a longer start or stop time. a longer start or stop time.
Additional adjustment of the S-ramp ratios or switching Additional adjustment of the S-ramp ratios or switching
initiators may be necessary. initiators may be necessary.
6 6
3-51 Ramp 2 Ramp-up Time 3-61 Ramp 3 Ramp-up Time
Range: Function: Range: Function:
Size [ 0.01 Enter the ramp-up time, i.e. the acceleration Size [ 0.01 - Enter the ramp-up time, i.e. the
related* - 3600 time from 0 RPM to the rated motor speed related* 3600 s] acceleration time from 0 RPM to the
s] ns. Choose a ramp-up time such that the rated motor speed ns. Choose a ramp-up
output current does not exceed the current time such that the output current does
limit in 4-18 Current Limit during ramping. not exceed the current limit in
The value 0.00 corresponds to 0.01 s in 4-18 Current Limit during ramping. The
speed mode. See ramp-down time in value 0.00 corresponds to 0.01 s in
3-52 Ramp 2 Ramp-down Time. speed mode. See ramp-down time in
tacc s x ns RPM 3-62 Ramp 3 Ramp-down Time.
Par . 3 − 51 =
ref RPM
3-62 Ramp 3 Ramp-down Time
3-52 Ramp 2 Ramp-down Time
Range: Function:
Range: Function:
Size [ 0.01 Enter the ramp-down time, i.e. the
Size [ 0.01 Enter the ramp-down time, i.e. the related* - 3600 deceleration time from the rated motor speed
related* - 3600 deceleration time from the rated motor speed s] ns to 0 RPM. Choose a ramp-down time such
s] ns to 0 RPM. Choose a ramp-down time such that no over-voltage arises in the inverter due
that no over-voltage arises in the inverter due to regenerative operation of the motor, and
to regenerative operation of the motor, and such that the generated current does not
such that the generated current does not exceed the current limit set in 4-18 Current
exceed the current limit set in 4-18 Current Limit. The value 0.00 corresponds to 0.01 s in
Limit. The value 0.00 corresponds to 0.01 s in speed mode. See ramp-up time in 3-61 Ramp
speed mode. See ramp-up time in 3-51 Ramp 3 Ramp-up Time.
2 Ramp-up Time.
tdec s x ns RPM
tdec s x ns RPM Par . 3 − 62 =
ref RPM
Par . 3 − 52 =
ref RPM
3-70 Ramp 4 Type
3-60 Ramp 3 Type
Option: Function:
Option: Function:
Select the ramp type, depending on
Select the ramp type, depending on requirements for acceleration and deceleration.
requirements for acceleration and deceleration. A linear ramp will give constant acceleration
A linear ramp will give constant acceleration during ramping. An S-ramp will give non-linear
during ramping. An S-ramp will give non-linear acceleration, compensating for jerk in the
acceleration, compensating for jerk in the application
application.
[0] Linear
[0] Linear
[1] S-ramp Accelerates with lowest possible jerk.
[1] S-ramp Accelerates with lowest possible jerk. Const Jerk
Const Jerk
NOTICE!
130BA070.10
RPM
RPM
4 Ramp-up Time.
tdec s x ns RPM
Par . 3 − 72 =
ref RPM P 4-13 RPM
high limit
Size [0.01 - Enter the jog ramp time, i.e. the P 4-11 RPM
related* 3600 s] acceleration/deceleration time between 0 low limit
130BA064.10
and 100% are defined in the analog Imotor
[0] No function
IN RANGE
[2] Analog in 53
[4] Analog in 53 inv
ILOW
[6] Analog in 54 (P 4-50)
[8] Analog in 54 inv
nmotor [RPM]
[10] Analog in X30-11
[12] Analog in X30-11 nMIN nLOW REF nHIGH nMAX
(P 4-11) (P 4-52) (P 4-53) (P 4-13)
inv
Figure 6.6 Adjustable Warnings
[14] Analog in X30-12
[16] Analog in X30-12
inv
4-50 Warning Current Low
4-21 Speed Limit Factor SourceOption
Range: Function:
Option: Function: 0 A* [ 0 - par. Enter the ILOW value. When the motor current
Select an analog input for scaling 4-51 A] falls below this limit, the display reads Current
the settings in 4-19 Max Output Low. The signal outputs can be programmed
Frequency from 0% to 100% (or vice to produce a status signal on terminal 27 or
versa). The signal levels 29 and on relay output 01 or 02. Refer to
corresponding to 0% and 100% are Figure 6.6.
defined in the analog input scaling,
e.g. parameter group 6-1* Analog 4-51 Warning Current High
Input 1. This parameter is only active
Range: Function:
when 1-00 Configuration Mode is in
Size [ par. 4-50 Enter the IHIGH value. When the motor
Torque Mode.
related* - par. 16-37 current exceeds this limit, the display
[0] * No function
A] reads Current High. The signal outputs
[2] Analog input 53
can be programmed to produce a
[4] Analog input 53 inv
4-55 Warning Reference High [0] Off No alarm is displayed if a missing motor phase occurs.
Range: Function:
[1] On
999999.999 * [ par. 4-54 - Enter the upper reference limit.
999999.999 ] When the actual reference
exceeds this limit, the display
6.5.3 4-6* Speed Bypass
reads Ref High. The signal
outputs can be programmed to Some systems call for avoiding certain output frequencies
produce a status signal on or speeds, due to resonance problems in the system. A
terminal 27 or 29 and on relay maximum of four frequency or speed ranges can be
output 01 or 02. avoided.
Parameter group for configuring the digital input and 5-01 Terminal 27 Mode
output. Option: Function:
[0] * Input Defines terminal 27 as a digital input.
6.6.2 5-0* Digital In/Out Mode [1] Output Defines terminal 27 as a digital output.
Parameters for configuring the input functions for the input terminals.
The digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the
following functions:
Functions dedicated to only one digital input are stated in the associated parameter.
All digital inputs can be programmed to these functions: [6] Stop inverse Stop Inverted function. Generates a stop
function when the selected terminal goes
[0] No No reaction to signals transmitted to the from logical level ‘1’ to ‘0’. The stop is
operation terminal. performed according to the selected ramp
[1] Reset Resets frequency converter after a TRIP/ time (3-42 Ramp 1 Ramp Down Time,
ALARM. Not all alarms can be reset. 3-52 Ramp 2 Ramp Down Time, 3-62 Ramp 3
[2] Coast (Default Digital input 27): Coasting stop, Ramp down Time, 3-72 Ramp 4 Ramp Down
inverse inverted input (NC). The frequency converter Time).
leaves the motor in free mode. Logic ‘0’ ⇒ NOTICE!
coasting stop. When the frequency converter is at the
[3] Coast and Reset and coasting stop Inverted input (NC). torque limit and has received a stop
reset inverse Leaves motor in free mode and resets command, it may not stop by itself. To
frequency converter. Logic ‘0’ ⇒ coasting stop ensure that the frequency converter
and reset. stops, configure a digital output to [27]
[4] Quick stop Inverted input (NC). Generates a stop in Torque limit & stop and connect this
inverse accordance with quick-stop ramp time set in digital output to a digital input that is
3-81 Quick Stop Ramp Time. When motor configured as coast.
stops, the shaft is in free mode. Logic ‘0’ ⇒ [8] Start (Default Digital input 18): Select start for a
Quick-stop. start/stop command. Logic ‘1’ = start, logic ‘0’
[5] DC-brake Inverted input for DC braking (NC). Stops = stop.
inverse motor by energizing it with a DC current for [9] Latched The motor starts, if a pulse is applied for min.
a certain time period. See 2-01 DC Brake start 2 ms. The motor stops when Stop inverse is
Current to 2-03 DC Brake Cut In Speed [RPM]. activated.
The function is only active when the value in [10] Reversing (Default Digital input 19). Change the
2-02 DC Braking Time is different from 0. direction of motor shaft rotation. Select Logic
Logic ’0’ ⇒ DC braking.
[36] Mains failure Activates 14-10 Mains Failure. Mains 5-11 Terminal 19 Digital Input
inverse failure inverse is active in the Logic .0.
Option: Function:
situation.
[10] * Reversing Functions are described under parameter group
[39] Day/Night Reduce the max. frequency with the
5-1* Digital Inputs
Control setting in 28-74 Night Speed Drop [RPM].
[41] Latched Precise Sends a latched stop signal when the 5-12 Terminal 27 Digital Input
Stop inverse precise stop function is activated in Option: Function:
1-83 Precise Stop Function. The Latched
[2] * Coast inverse Functions are described under parameter
Precise stop inverse function is available
group 5-1* Digital Inputs
for terminals 18 or 19.
[55] DigiPot Increase INCREASE signal to the Digital Potenti- 5-13 Terminal 29 Digital Input
ometer function described in parameter Option: Function:
group 3-9* Digital Potmeter.
Select the function from the available
[56] DigiPot Decrease DECREASE signal to the Digital Potenti-
ometer function described in parameter
digital input range and the additional 6 6
options [60], [61], [63] and [64].
group 3-9* Digital Potmeter Counters are used in Smart Logic
[57] DigiPot Clear Clears the Digital Potentiometer Control functions.
reference described in parameter group [14] * Jog
3-9* Digital Potmeter
[60] Counter A (up)
[60] Counter A (Terminal 29 or 33 only) Input for
[61] Counter A (down)
increment counting in the SLC counter.
[63] Counter B (up)
[61] Counter A (Terminal 29 or 33 only) Input for
[64] Counter B (down)
decrement counting in the SLC counter.
[62] Reset Counter A Input for reset of counter A. 5-14 Terminal 32 Digital Input
[63] Counter B (Terminal 29 or 33 only) Input for Option: Function:
increment counting in the SLC counter.
Select the function from the available digital
[64] Counter B (Terminal 29 or 33 only) Input for input range.
decrement counting in the SLC counter.
No operation Functions are described under 5-1* Digital Inputs
[65] Reset Counter B Input for reset of counter B.
[70] Mech. Brake Brake feedback for hoisting applications 5-15 Terminal 33 Digital Input
Feedback Option: Function:
[71] Mech. Brake Inverted brake feedback for hoisting Select the function from the available digital
Feedback inv. applications input range and the additional options [60],
[80] PTC Card 1 All Digital Inputs can be set to [80] PTC [61], [63] and [64]. Counters are used in
Card 1. However, only one Digital Input Smart Logic Control functions.
must be set to this choice. [0] * No operation Functions are described under 5-1* Digital
[121] Lead Pump Inputs
Alternation
[130] Compressor Use with cascade controller. Logic 1 will 5-19 Terminal 37 Safe Stop
Interlock stop the fixed speed compressor and Option: Function:
give a warning [1] Safe Stop Alarm
[131] Compressor Use with cascade controller. Logic 1 will [3] Safe Stop Warning
Interlock stop the fixed speed compressor and [4] PTC 1 Alarm
give a warning [5] PTC 1 Warning
[132] Compressor Use with cascade controller. Logic 1 will [6] PTC 1 & Relay A
Interlock stop the fixed speed compressor and [7] PTC 1 & Relay W
give a warning
[8] PTC 1 & Relay A/W
5-10 Terminal 18 Digital Input [9] PTC 1 & Relay W/A
Option: Function:
[8] * Start Functions are described under parameter group 5-1*
Digital Inputs
6.6.4 5-3* Digital Outputs [13] Below current, The motor current is lower than set in
low 4-50 Warning Current Low.
Parameters for configuring the output functions for the [14] Above current, The motor current is higher than set in
output terminals. The 2 solid-state digital outputs are high 4-51 Warning Current High.
common for terminals 27 and 29. Set the I/O function for [15] Out of speed The output speed is outside the range
terminal 27 in 5-01 Terminal 27 Mode, and set the I/O range set in 4-52 Warning Speed Low and
function for terminal 29 in 5-02 Terminal 29 Mode. Digital 4-53 Warning Speed High.
outputs appear if 5-01 Terminal 27 Mode or 5-02 Terminal [16] Below speed, The output speed is lower than the
29 Mode are set to output. low setting in 4-52 Warning Speed Low.
[17] Above speed, The output speed is higher than the
NOTICE! high setting in 4-53 Warning Speed High.
These parameters cannot be adjusted while the motor is [18] Out of The feedback is outside the range set in
running. feedback range 4-56 Warning Feedback Low and
6 6 4-57 Warning Feedback High.
[19] Below feedback The feedback is below the limit set in
NOTICE! low 4-56 Warning Feedback Low.
Only for activating 24 V DC devices − restricted use for
[20] Above The feedback is above the limit set in
relays.
feedback high 4-57 Warning Feedback High .
[21] Thermal The thermal warning turns on when the
The digital outputs can be programmed warning temperature exceeds the limit in the
with these functions: motor, the frequency converter, the brake
[0] No operation Default for all digital outputs and relay resistor, or the thermistor.
outputs [25] Reverse Reversing. Logic ‘1’ = relay activated, 24 V
[1] Control ready The control board receives supply DC when CW rotation of the motor. Logic
voltage. ‘0’ = relay not activated, no signal, when
[2] Drive ready The frequency converter is ready for CCW rotation of the motor.
operation and applies a supply signal on [26] Bus OK Active communication (no time-out) via
the control board. the serial communication port.
[3] Drive ready / The frequency converter is ready for [27] Torque limit Use in performing a coasting stop and in
remote control operation and is in Auto On mode. and stop torque limit condition. If the frequency
[4] Stand-by / no The frequency converter is ready for converter has received a stop signal and
warning operation. No start or stop command is is at the torque limit, the signal is Logic
been given (start/disable). There are no ‘0’.
warnings. [28] Brake, no The brake is active and there are no
[5] Running The motor is running. warning warnings.
[6] Running / no The output speed is higher than the [29] Brake ready, no The brake is ready for operation and
warning speed set in 1-81 Min Speed for Function fault there are no faults.
at Stop [RPM]. The motor is running and [30] Brake fault The output is Logic ‘1’ when the brake
there are no warnings. (IGBT) IGBT is short-circuited. Use this function
[7] Run on The motor runs at reference speed. to protect the frequency converter if
reference / no there is a fault on the brake modules.
warning Use the output/relay to cut out the main
[8] Run in range / The motor runs in speed range. voltage from the frequency converter.
no warning [33] Safe Stop Indicates that the safe stop on terminal
[9] Alarm An alarm activates the output. There are Active 37 is active.
no warnings. [35] External External Interlock function has been
[10] Alarm or An alarm or a warning activates the Interlock activated via one of the digital inputs.
warning output. [40] Out of ref Active when the actual speed is outside
[11] At torque limit The torque limit set in 4-16 Torque Limit range the settings in 4-52 Warning Speed Low to
Motor Mode or 1-17 Voltage filter time 4-55 Warning Reference High.
const. has been exceeded. [41] Below Active when the actual speed is below
[12] Out of current The motor current is outside the range reference low the speed reference setting.
range set in 4-18 Current Limit.
[42] Above Active when the actual speed is above output will go high. Otherwise, it will be
reference high the speed reference setting. low.
[45] Bus Ctrl Control output via bus. The state of the [74] Logic Rule 4 See parameter group 13-4* Logic Rules. If
output is set in 5-90 Digital & Relay Bus Logic Rule 4 is evaluated as TRUE, the
Control. The output state is retained in output will go high. Otherwise, it will be
the event of bus time-out. low.
[46] Bus Ctrl 1 if Controls output via bus. The state of the [75] Logic Rule 5 See parameter group 13-4* Logic Rules. If
timeout output is set in 5-90 Digital & Relay Bus Logic Rule 5 is evaluated as TRUE, the
Control. In the event of bus time-out the output will go high. Otherwise, it will be
output state is set low (On). low.
[47] Bus Ctrl 0 if Controls output via bus. The state of the [80] SL Digital See 13-52 SL Controller Action. The input
timeout output is set in 5-90 Digital & Relay Bus Output A will go high whenever the Smart Logic
Control. In the event of bus time-out the Action [38] Set dig. out. A high is
[124] Running The output is high when the frequency Wiring diagrams and settings for parameter, see parameter
reverse converter is running counter clockwise group 25-** Cascade Pack Controller or more details.
(the logical product of the status bits
‘running’ AND ‘reverse’). 6.6.5 5-4* Relays (Dry Contacts)
[125] Drive in hand The output is high when the frequency
mode converter is in Hand on mode (as
indicated by the LED light above [Hand
NOTICE!
Relays 7, 8, and 9 are only available if MCB 105 relay card
on].
is installed.
[126] Drive in auto The output is high when the frequency
mode converter is in Hand on mode (as
indicated by the LED light above [Auto NOTICE!
on]. Relay 1 is dedicated to controlling the solenoid valve.
[139] Compressor Use with cascade controller. Logic will
5-57 Term. 33 Low Ref./Feedb. Value 5-63 Terminal 29 Pulse Output Variable
Range: Function: Option: Function:
0* [-999999.999 - Enter the low reference value [RPM] [0] No operation Select the desired display output for
999999.999 ] for the motor shaft speed. This is also terminal 29.
the low feedback value, see also
[45] Bus ctrl.
5-52 Term. 29 Low Ref./Feedb. Value.
[48] Bus ctrl., timeout
[51] MCO controlled
5-58 Term. 33 High Ref./Feedb. Value
[100] Output frequency
Range: Function:
[101] Reference
Size related* [-999999.999 - Enter the high reference [102] Feedback
999999.999 value [RPM] for the motor
[103] Motor Current
ReferenceFeedbackUnit] shaft speed. See also
[104] Torque rel to limit
6 6 5-53 Term. 29 High Ref./
Feedb. Value.
[105] Torq relate to rated
[106] Power
[107] Speed
5-59 Pulse Filter Time Constant #33
[108] Torque
Range: Function:
[109] Max Out Freq
100 ms* [1 - 1000 Enter the pulse filter time constant. The
ms] low-pass filter reduces the influence on 5-65 Pulse Output Max Freq #29
and dampens oscillations on the feedback Set the maximum frequency for terminal 29 corresponding to the
signal from the control. output variable set in 5-63 Terminal 29 Pulse Output Variable.
This is an advantage, e.g. if there is a
Range: Function:
great amount on noise in the system.
5000 Hz* [0 - 32000 Hz]
5-60 Terminal 27 Pulse Output Variable 5-90 Digital & Relay Bus Control
Option: Function: Range: Function:
[0] No operation Select the desired display output for 0* [0 - 2147483647 ] This parameter holds the state of the
terminal 27. digital outputs and relays that is
[45] Bus ctrl. controlled by bus.
[48] Bus ctrl., timeout A logical '1' indicates that the output is
[51] MCO controlled high or active.
[100] Output frequency A logical '0' indicates that the output is
low or inactive.
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[119] Torque % lim
6.7 Par. Group 6 - Analog In/Out 6-01 Live Zero Timeout Function
Option: Function:
Parameter group for configuration of the analog input and
[5] Stop and Overruled to stop with subsequent trip
output.
trip
1. 6-01 Live Zero Timeout Function 6-14 Terminal 53 Low Ref./Feedb. Value
Parameters for configuring the scaling and limits for Enter the time constant. This is a first-
analog input 2 (terminal 54). order digital low pass filter time constant
for suppressing electrical noise in terminal
130BB372.10
In case the norm motor current is equal to
Par 4-17 0% Torque Par 4-16
20 mA, the output setting of 6-52 Terminal 42 (200%) (200%)
6 6
A. 160% = 38.4 A. Motor norm current = 22 the maximum value of the current signal output.
A Read-out 11.46 mA. Scale the output to give a current lower than 20
16 mA x 22 A
+ 4 mA = 13.17 mA mA at full scale; or 20 mA at an output below
38.4 A
In case the norm motor current is equal to 100% of the maximum signal value. If 20 mA is
20 mA, the output setting of 6-62 Terminal the desired output current at a value between 0
X30/8 Max. Scale is: - 100% of the full-scale output, programme the
I VLT x 100 percentage value in the parameter, i.e. 50% = 20
Max 38.4 x 100
= = 175 % mA. If a current between 4 and 20 mA is desired
I Motor 22
Norm
at maximum output (100%), calculate the
[134] Torq.% lim The torque setting is related to setting in percentage value as follows:
4-20 mA 4-16 Torque Limit Motor Mode.
[135] Torq.% The torque setting is related to the motor 20 mA / desired maximum current x 100 %
nom 4-20 torque setting. 20
i .e . 10 mA : x 100 = 200 %
10
mA
130BA075.11
Current
20
4-20mA
[137] Speed Taken from 3-03 Maximum Reference. 20 mA
4-20mA = Value in 3-03 Maximum Reference.
0/4
[138] Torque Torque reference related to 160% torque. 0% Analog Analog 100% Variable for
output
output Min Output Max
example: Speed
4-20mA Scale Scale
par. 6-51 par. 6-52 (RPM)
[139] Bus ctrl. An output value set from fieldbus process Figure 6.9 Output Max Scale
0-20 mA data. The output will work independently of
internal functions in the frequency converter.
[140] Bus ctrl. An output value set from fieldbus process 6-53 Terminal 42 Output Bus Control
4-20 mA data. The output will work independently of
Range: Function:
internal functions in the frequency converter.
0 %* [0 - 100 %] Holds the level of Output 42 if controlled by
[141] Bus ctrl 4-54 Warning Reference Low defines the
bus.
0-20mA t.o. behavior of the analog output in case of bus
time-out.
[142] Bus ctrl 4-54 Warning Reference Low defines the
4-20mA t.o. behavior of the analog output in case of bus
time-out.
[150] Max Out Fr 0 Hz = 0 mA,4-19 Max Output Frequency = 20
4-20mA mA.
175ZA293.11
7-06 Speed PID Lowpass Filter Time Disturbed feedback signal
Range: Function:
Size [0.1 - Set a time constant for the speed control low-
related* 100 pass filter. The low-pass filter improves
ms] steady-state performance and dampens
oscillations on the feedback signal. This is an
advantage if there is a great amount on noise
in the system, see Figure 6.10. For example, if
a time constant (τ) of 100 ms is programmed,
the cut-off frequency for the low-pass filter
will be 1/0.1= 10 RAD/s., corresponding to
6 6 (10/2 x π) = 1.6 Hz. The PID regulator only
regulates a feedback signal that varies by a
frequency of less than 1.6 Hz. If the feedback
signal varies by a higher frequency than 1.6 0.6 t (Sec.)
NOTICE!
Severe filtering can be detrimental to dynamic
performance.
This parameter is used with 1-00 Configuration Mode [1]
Speed closed loop and [2] Torque control.
The filter time in flux sensorless must be adjusted to
3-5 ms.
0.6 t (Sec.)
Figure 6.10 Feedback Signal
7-38 Process PID Feed Forward Factor 7-61 Feedback 1 Source Unit
Range: Function: Option: Function:
control only affects the remaining fraction of the [73] kPa
control signal. Any change to this parameter will [74] m WG
thus affect the motor speed. When the FF factor [170] psi
is activated it provides less overshoot, and high [171] lb/in2
dynamics when changing the set point. [172] in WG
7-38 Process PID Feed Forward Factor is active [173] ft WG
when 1-00 Configuration Mode is set to [3]
Process. 7-62 Feedback 2 Conversion
Option: Function:
7-39 On Reference Bandwidth Selects the conversion to apply to the
6 6 Range:
5 %* [0 - 200
Function:
Enter the On Reference bandwidth. When the
feedback signal measured on the analog
input selected as feedback 2 source in 7-22
%] PID Control Error (the difference between the Process CL Feedback 2 Resource.
reference and the feedback) is less than the [0] * Linear No conversion is applied. The feedback
set value of this parameter the On Reference signal is assumed to be in the unit selected
status bit is high, i.e. =1. in 3-01 Reference/Feedback Unit and enters
the process controller unchanged.
[1] Square root The square root of the feedback signal is
6.8.2 7-6* Feedback Conversion calculated before passing it to the process
controller.
Select how the signals from the feedback sources must be [2] Pressure to The feedback signal is a pressure with units
converted. temperature as specified in 7-62 Feedback 2 Source Unit.
7-60 Feedback 1 Conversion It is converted to a temperature before
passing it to the process controller. The
Option: Function:
pressure to temperature conversion is
Selects the conversion to apply to the
based on the refrigerant selected in 7-70
feedback signal measured on the analog
Refrigerant.
input selected as feedback 1 source in 7-20
Process CL Feedback 1 Resource. 7-63 Feedback 2 Source Unit
[0] * Linear No conversion is applied. The feedback Option: Function:
signal is assumed to be in the unit selected
Select the pressure unit applicable to feedback
in 3-01 Reference/Feedback Unit and enters
source 1 defined in 7-22 Process CL Feedback 2
the process controller unchanged.
Resource.
[1] Square root The square root of the feedback signal is
[70] mbar
calculated before passing it to the process
[71] bar
controller.
[72] Pa
[2] Pressure to The feedback signal is a pressure with units
[73] kPa
temperature as specified in 7-61 Feedback 1 Source Unit.
[74] m WG
It is converted to a temperature before
[170] psi
passing it to the process controller. The
[171] lb/in2
pressure to temperature conversion is
based on the refrigerant selected in 7-70 [172] in WG
Refrigerant. [173] ft WG
The conversion of a feedback signal P in units of a pressure to a temperature T is accomplished via the formula:
T = A2/(log(P+1)-A1) – A3
6 6
The parameters in this group allow selection of a refrigerant, which implicitly determines the constants A1, A2 and A3.
Alternatively, user defined constants can be programmed explicitly.
7-70 Refrigerant 7-73 User Defined Refrigerant A3
Option: Function: Range: Function:
[0] R22 [200.000 – Selects the value used for the constant A3
[1] R134a 300.000] in the pressure to temperature conversion
[2] * R404A formula (see parameter group 7-7* Pressure
[3] R407C to Temperature Conversion).
[4] R410A
[5] R502 6.8.4 7-8* Thermostat/Pressostat Function
[6] R744
[7] User defined The Thermostat-Pressostat Function (TPF) can be used to
stop and start the compressor when running in closed
7-71 User Defined Refrigerant A1 loop. The TPF monitors and compares the resulting
Range: Function: feedback with the Cut-out value in 7-81 Cut-out Value.
[8.0000 – Selects the value used for the constant A1 When the resulting feedback gets below 7-81 Cut-out Value
12.0000] in the pressure to temperature conversion a stop signal is generated and the compressor stops. When
formula (see parameter group 7-7* Pressure the resulting feedback gets above the Cut-in value in
to Temperature Conversion). 7-82 Cut-in Value the stop signal is removed and the
compressor starts again.
7-72 User Defined Refrigerant A2
Range: Function: The Set-point should be set to a value in between Cut-in
[-3000.00 – Selects the value used for the constant A2 and Cut-out.
-1500.00] in the pressure to temperature conversion
formula (see parameter group 7-7* Pressure
to Temperature Conversion).
6 6
Figure 6.12 Thermostat/Pressostat Function
NOTICE!
When using the TPF together with the Cascade Controller
further consideration must be taken. The Cut-Out value
should be below the Override Bandwidth setting (see
25-21 Override Bandwidth). Cut-In should be set above the
set-point and below the value for Staging Bandwidth (see
25-20 Staging Bandwidth).
6.9 Parameters: 8-** Communications and 8-03 Control Word Timeout Time
Options Range: Function:
[1.0 s] 0.1-18000.0 s Enter the maximum time expected to
6.9.1 8-0* General Settings pass between the reception of two
consecutive telegrams. If this time is
exceeded, it indicates that the serial
8-01 Control Site communication has stopped. The
Option: Function: function selected in 8-04 Control Word
The setting in this parameter overrides Timeout Function is then carried out. A
the settings in 8-50 Coasting Select to valid control word triggers the time-out
8-56 Preset Reference Select. counter.
20 s* [ 0.1 - Enter the maximum time expected to
[0] Digital and Control by using both digital input and
18000.0 s] pass between the reception of two
ctrl.word control word.
consecutive telegrams. If this time is 6 6
[1] Digital only Control by using digital inputs only. exceeded, it indicates that the serial
communication has stopped. The
[2] Controlword only Control by using control word only.
function selected in 8-04 Control Word
Timeout Functionis then carried out. A
8-02 Control Word Source
valid control word triggers the time-out
Option: Function: counter.
NOTICE!
8-04 Control Word Timeout Function
This parameter cannot be adjusted while
the motor is running. Select the time-out function. The time-out function activates
when the control word fails to be updated within the time
period specified in 8-03 Control Word Timeout Time.
Select the source of the control word: one of
two serial interfaces or four installed options. Option: Function:
During initial power-up, the frequency [0] Off Resumes control via serial bus (fieldbus or
converter automatically sets this parameter to standard) using the most recent control
[3] Option A if it detects a valid fieldbus option word.
installed in slot A. If the option is removed,
[1] Freeze output Freezes output frequency until communi-
the frequency converter detects a change in
cation resumes.
the configuration, sets 8-02 Control Word
Source back to default setting RS-485, and the [2] Stop Stops with auto restart when communi-
frequency converter trips. If an option is cation resumes.
installed after initial power-up, the setting of [3] Jogging Runs the motor at JOG frequency until
8-02 Control Word Source does not change, but communication resumes.
the frequency converter trips and displays:
[4] Max. speed Runs the motor at maximum frequency until
Alarm 67 Option Changed.
communication resumes.
When retrofitting a bus option into a
frequency converter that did not have a bus [5] Stop and trip Stops the motor, then resets the frequency
option installed to begin with, take an ACTIVE converter to restart: via the fieldbus, via
decision to move the control to Bus based. [Reset], or via a digital input.
This is done for safety reasons to avoid an
[7] Select setup 1 Changes the set-up upon reestablishment of
accidental change.
communication following a control word
[0] None time-out. If communication resumes after a
[1] FC RS-485 time-out, 8-05 End-of-Timeout Function
[2] FC USB defines whether to resume the set-up used
[3] Option A before the time-out, or to retain the set-up
[4] Option B endorsed by the time-out function.
[5] Option C0 [8] Select setup 2 See [7] Select setup 1
[6] Option C1
[9] Select setup 3 See [7] Select setup 1
[30] External
Can [10] Select setup 4 See [7] Select setup 1
8-04 Control Word Timeout Function 6.9.2 8-1* Ctrl. Word Settings
Select the time-out function. The time-out function activates
when the control word fails to be updated within the time 8-10 Control Word Profile
period specified in 8-03 Control Word Timeout Time. Select the interpretation of the control and status words
Option: Function: corresponding to the installed fieldbus. Only the selections valid
[26] Trip for the fieldbus installed in slot A will be visible in the LCP
display.
NOTICE! For guidelines in selection of [0] FC profile and [1] PROFIdrive
To change the set-up after a time-out, the following profile, refer to the Serial communication via RS-485 Interface
configuration is required: section in the Design Guide.
Set 0-10 Active Set-up to [9] Multi set-up and select the For additional guidelines in the selection of [1] PROFIdrive profile,
relevant link in 0-12 This Set-up Linked to. refer to the Operating Instructions for the installed fieldbus.
8-31 Address
Range: Function:
Size related* [ 1 - 255 ] Enter the address for the FC (standard)
port.
Valid range: 1-126.
[3] Logic OR Activate the set-up selection via the fieldbus/ 6.9.6 8-9* Bus Jog
serial communication port OR via one of the
digital inputs.
8-90 Bus Jog 1 Speed
= NOTICE!
TRUE longer than..
SLC is only active in AUTO mode, not Hand On mode
...
...
6.10.2 13-0* SLC Settings
Figure 6.13 Smart Logic Control (SLC)
Use the SLC settings to activate, deactivate and reset the
Smart Logic Control sequence. The logic functions and
comparators are always running in the background, which
Events and actions are each numbered and linked together
opens for separate control of digital inputs and outputs.
in pairs (states). This means that when event [0] is fulfilled
(attains the value TRUE), action [0] is executed. After this, 13-00 SLC Controller Mode
the conditions of event [1] will be evaluated and if Option: Function:
evaluated TRUE, action [1] will be executed and so on. [ 0] * Off Disables the Smart Logic Control.
Only one event will be evaluated at any time. If an event is [1] On Enables the Smart Logic Control to start when a start
evaluated as FALSE, nothing happens (in the SLC) during command is present, e.g. via a digital input.
the current scan interval and no other events will be
evaluated. This means that when the SLC starts, it 13-01 Start Event
evaluates event [0] (and only event [0]) each scan interval. Select the boolean (TRUE or FALSE) input to activate Smart Logic
Only when event [0] is evaluated TRUE, will the SLC Control.
execute action [0] and start evaluating event [1]. It is
Option: Function:
possible to programme from 1 to 20 events and actions.
[0] FALSE Select the boolean (TRUE or FALSE)
input to activate Smart Logic Control.
[6] Current Limit The motor current limit, set in [26] Logic rule 0 Use the result of logic rule 0.
4-18 Current Limit, has been [27] Logic rule 1 Use the result of logic rule 1.
exceeded.
[28] Logic rule 2 Use the result of logic rule 2.
[7] Out of current The motor current is outside the
[29] Logic rule 3 Use the result of logic rule 3.
range range set in 4-18 Current Limit.
[33] Digital input DI18 Use the result of digital input 18.
[8] Below I low The motor current is lower than set
in 4-50 Warning Current Low. [34] Digital input DI19 Use the result of digital input 19.
[9] Above I high The motor current is higher than set [35] Digital input DI27 Use the result of digital input 27.
in 4-51 Warning Current High.
[36] Digital input DI29 Use the result of digital input 29.
[10] Out of speed range The speed is outside the range set in
[37] Digital input DI32 Use the result of digital input 32.
4-52 Warning Speed Low and
4-53 Warning Speed High. [38] Digital input DI33 Use the result of digital input 33.
[11] Below speed low The output speed is lower than the [39] Start command A start command is issued.
setting in 4-52 Warning Speed Low. [40] Drive stopped A stop command (Jog, Stop, Qstop,
[12] Above speed high The output speed is higher than the Coast) is issued – and not from the
setting in 4-53 Warning Speed High. SLC itself.
[13] Out of feedb. range The feedback is outside the range set [41] Reset Trip A reset is issued
in 4-56 Warning Feedback Low and [42] Auto-reset Trip An Auto reset is performed.
4-57 Warning Feedback High.
[43] OK key [OK] is pressed.
[14] Below feedb. low The feedback is below the limit set in
[44] Reset key [Reset] is pressed.
4-56 Warning Feedback Low.
[45] Left key [◄] is pressed.
[15] Above feedb. high The feedback is above the limit set in
4-57 Warning Feedback High. [46] Right key [►] is pressed.
[16] Thermal warning The thermal warning turns on when [47] Up key [▲] is pressed.
the temperature exceeds the limit in
the motor, the frequency converter,
[48] Down key [▼] is pressed.
the brake resistor or the thermistor. [50] Comparator 4 Use the result of comparator 4.
[17] Mains out of range The mains voltage is outside the [51] Comparator 5 Use the result of comparator 5.
specified voltage range.
[60] Logic rule 4 Use the result of logic rule 4.
[18] Reverse The output is high when the
[61] Logic rule 5 Use the result of logic rule 5.
frequency converter is running
[98] RS Flipflop 4
Comparators
[99] RS Flipflop 5 See parameter group 13-1* [34] Digital input DI19
Comparators [35] Digital input DI27
[36] Digital input DI29
[100] RS Flipflop 6 See parameter group 13-1*
[37] Digital input DI32
Comparators
[38] Digital input DI33
[101] RS Flipflop 7 See parameter group 13-1* [39] Start command
Comparators [40] Drive stopped
[41] Reset Trip
13-02 Stop Event
[42] Auto-reset Trip
Select the boolean (TRUE or FALSE) input to deactivate Smart [43] OK key
Logic Control. [44] Reset key
Option: Function: [45] Left key
[0] FALSE For descriptions [0]-[61], see [46] Right key
13-01 Start Event Start Event [47] Up key
6 6
fixed preset values.
164 ATEX ETR cur.lim.alarm is
active, the output will be 1.
Par. 13-11
130BB672.10
[91] ATEX ETR cur. alarm Selectable if 1-90 Motor Thermal Comparator Operator
Par. 13-10
Protection is set to [20] ATEX ETR
Comparator Operand
or [21] Advanced ETR. If the alarm
=
166 ATEX ETR freq.lim.alarm is TRUE longer than.
Par. 13-12
active, the output will be 1. Comparator Value ...
...
[92] ATEX ETR freq. warning Selectable if 1-90 Motor Thermal
Protection is set to [20] ATEX ETR
Figure 6.15 Comparators
or [21] Advanced ETR. If the alarm
163 ATEX ETR cur.lim.warning is
active, the output will be 1.
In addition, there are digital values that will be compared
[93] ATEX ETR freq. alarm Selectable if 1-90 Motor Thermal to fixed time values. See explanation in 13-10 Comparator
Protection is set to [20] ATEX ETR Operand. Comparators are evaluated once in each scan
or [21] Advanced ETR. If the interval. Use the result (TRUE or FALSE) directly. All
warning 165 ATEX ETR parameters in this parameter group are array parameters
freq.lim.warning is active, the with index 0 to 5. Select index 0 to programme
output will be 1. Comparator 0, select index 1 to programme Comparator 1,
[94] RS Flipflop 0 See parameter group 13-1* and so on.
Comparators 13-10 Comparator Operand
[95] RS Flipflop 1 See parameter group 13-1* Array [6]
Comparators
Option: Function:
[96] RS Flipflop 2 See parameter group 13-1* Choices [1] to [31] are variables which
Comparators will be compared based on their
[97] RS Flipflop 3 See parameter group 13-1* values. Choices [50] to [186] are digital
Comparators values (TRUE/FALSE) where the
comparison is based on the amount of
[98] RS Flipflop 4 See parameter group 13-1* time during which they are set to
Comparators TRUE or FALSE, respectively. See
[99] RS Flipflop 5 See parameter group 13-1* 13-11 Comparator Operator.
Comparators Select the variable to be monitored by
the comparator.
[100] RS Flipflop 6 See parameter group 13-1*
Comparators [0] DISABLED The comparator is disabled.
[101] RS Flipflop 7 See parameter group 13-1* [1] Reference The resulting remote reference (not
Comparators local) as a percentage.
[10] VLT temp. Expressed as a percentage. [62] Above ref, high The motor is running above the value
[14] Analog input [V]. AIFB10 is internal 10 V supply. [66] Current Limit The motor current limit, set in
AIFB10 4-18 Current Limit, has been exceeded.
[15] Analog input [V] Analog input AICCT [17] [°]. AIS24V
[67] Out of current The motor current is outside the range
AIS24V is switch mode power supply: SMPS
range set in 4-18 Current Limit.
24V.
[68] Below I low The motor current is lower than set in
[17] Analog input [°]. AICCT is control card temperature.
4-50 Warning Current Low.
AICCT
[18] Pulse input FI29 Expressed as a percentage. [69] Above I high The motor current is higher than set in
4-51 Warning Current High.
[19] Pulse input FI33 Expressed as a percentage.
[70] Out of speed The speed is outside the range set in
[20] Alarm number The error number. range 4-52 Warning Speed Low and
[21] Warning number 4-53 Warning Speed High.
[22] Analog input x30 [71] Below speed low The output speed is lower than the
11 setting in 4-52 Warning Speed Low.
[23] Analog input x30
[72] Above speed high The output speed is higher than the
12
setting in 4-53 Warning Speed High.
[30] Counter A Number of counts
[75] Out of feedb. The feedback is outside the range set
[31] Counter B Number of counts
range in 4-56 Warning Feedback Low and
[50] FALSE Enters the fixed value of false in the 4-57 Warning Feedback High.
comparator.
[76] Below feedback The feedback is below the limit set in
[51] TRUE Enters the fixed value of true in the low 4-56 Warning Feedback Low.
comparator.
[77] Above feedback The feedback is above the limit set in
[52] Control ready The control board receives supply high 4-57 Warning Feedback High.
voltage
[80] Thermal warning The thermal warning turns on when
[53] Drive ready The frequency converter is ready for the temperature exceeds the limit in
operation and applies a supply signal the motor, the frequency converter,
on the control board. the brake resistor or thermistor.
[54] Running The motor is running. [82] Line pwr out of The mains voltage is outside the
[55] Reversing The output is high when the range specified voltage range.
frequency converter is running counter [85] Warning A warning is active.
clockwise (the logical product of the
[86] ALARM (Trip) A (trip) alarm is active.
status bits “running” AND “reverse”).
[87] ALARM (Trip Lock) A (Trip lock) alarm is active.
[91] Torque limit & If the frequency converter has received [153] SL digital output Use the result of the SLC output D.
stop a stop signal and is at the torque limit, D
the signal is logic “0”. [154] SL digital output E Use the result of the SLC output E.
[92] Brake fault (IGBT) The brake IGBT is short circuited. [155] SL digital output F Use the result of the SLC output F.
[93] Mech. brake The mechanical brake is active. [160] Relay 1 Relay 1 is active
control [161] Relay 2 Relay 2 is active
[111] Logic rule 1 The result of Logic rule 1. [183] Drive stopped A stop command (Jog, Stop, Qstop,
Coast) is issued – and not from the
[112] Logic rule 2 The result of Logic rule 2.
SLC itself.
[113] Logic rule 3 The result of Logic rule 3.
[185] Drive in hand High when the frequency converter is
[114] Logic rule 4 The result of Logic rule 4. mode in hand mode.
[115] Logic rule 5 The result of Logic rule 5. [186] Drive in auto High when the frequency converter is
mode in auto mode.
[120] SL Timeout 0 The result of SLC timer 0.
[187] Start command
[121] SL Timeout 1 The result of SLC timer 1.
given
[122] SL Timeout 2 The result of SLC timer 2. [190] Digital input x30 2
[123] SL Timeout 3 The result of SLC timer 3. [191] Digital input x30 3
[192] Digital input x30 4
[124] SL Timeout 4 The result of SLC timer 4.
[193] Digital input x46 1
[125] SL Timeout 5 The result of SLC timer 5.
[194] Digital input x46 2
[126] SL Timeout 6 The result of SLC timer 6. [195] Digital input x46 3
[127] SL Timeout 7 The result of SLC timer 7. [196] Digital input x46 4
[197] Digital input x46 5
[130] Digital input DI18 Digital input 18. High = True.
[198] Digital input x46 6
[131] Digital input DI19 Digital input 19. High = True. [199] Digital input x46 7
[132] Digital input DI27 Digital input 27. High = True.
13-11 Comparator Operator
[133] Digital input DI29 Digital input 29. High = True. Array [6]
[134] Digital input DI32 Digital input 32. High = True. Option: Function:
[135] Digital input DI33 Digital input 33. High = True. Select the operator to be used in the
comparison. This is an array parameter
[150] SL digital output Use the result of the SLC output A.
containing comparator operators 0 to 5.
A
[151] SL digital output Use the result of the SLC output B. [0] < The result of the evaluation is TRUE, when the
B variable selected in 13-10 Comparator Operand
130BB960.10
S
Array [6]
R
Option: Function:
is smaller than the fixed value in Flip Flop Output
13-12 Comparator Value. The result is FALSE, if
Figure 6.17 Flip Flop Outputs
the variable selected in 13-10 Comparator
Operand is greater than the fixed value in
13-12 Comparator Value.
The two operators can be selected from a long list. As a
[1] = (equal) The result of the evaluation is TRUE, when the special case, the same digital input can be used as both
variable selected in 13-10 Comparator Operand Set and Reset, making it possible to use the same digital
is approximately equal to the fixed value in input as start/stop. The following settings can be used to
13-12 Comparator Value. set up the same digital input as start/stop (example given
[2] > Inverse logic of option < [0]. with DI32 but is not a requirement). 6 6
[5] TRUE longer
Parameter Setting Notes
than...
13-00 SL Controller Mode On
[6] FALSE longer
13-01 Start Event TRUE
than...
13-02 Stop Event FALSE
[7] TRUE shorter
than... [37] Digital
[8] FALSE 13-40 Logic Rule Boolean 1 [0]
Input DI32
shorter 13-42 Logic Rule Boolean 2 [0] [2] Running
than...
13-41 Logic Rule Operator 1 [3] AND
13-12 Comparator Value [0] NOT
Flipflop 0
Par. 13-15 and 13-16
RS-FF Operand S 13-52 SL Controller Action [0] [22] Run
Par. 13-16
RS-FF Operand R
[27]
13-51 SL Controller Event [1]
Logicrule 1
Figure 6.16 Reset/Set Flip Flops 13-52 SL Controller Action [1] [24] Stop
6 6 [14]
[15]
Below feedb. low
Above feedb. high
[80]
[81]
Digital input x46/3
Digital input x46/5
[16] Thermal warning [82] Digital input x46/7
[17] Mains out of range [83] Digital input x46/9
[18] Reverse [84] Digital input x46/11
[19] Warning [85] Digital input x46/13
[20] Alarm (trip) [90] ATEX ETR cur. warning
[21] Alarm (trip lock) [91] ATEX ETR cur. alarm
[22] Comparator 0 [92] ATEX ETR freq. warning
[23] Comparator 1 [93] ATEX ETR freq. alarm
[24] Comparator 2 [94] RS Flipflop 0
[25] Comparator 3 [95] RS Flipflop 1
[26] Logic rule 0 [96] RS Flipflop 2
[27] Logic rule 1 [97] RS Flipflop 3
[28] Logic rule 2 [98] RS Flipflop 4
[29] Logic rule 3 [99] RS Flipflop 5
[30] SL Timeout 0 [100] RS Flipflop 6
[31] SL Timeout 1 [101] RS Flipflop 7
[32] SL Timeout 2
13-16 RS-FF Operand R
[33] Digital input DI18
[34] Digital input DI19 Option: Function:
[35] Digital input DI27 [0] FALSE
[36] Digital input DI29 [1] TRUE
[37] Digital input DI32 [2] Running
[38] Digital input DI33 [3] In range
[39] Start command [4] On reference
[40] Drive stopped [5] Torque limit
[41] Reset Trip [6] Current Limit
[42] Auto-reset Trip [7] Out of current range
[43] OK key [8] Below I low
[44] Reset key [9] Above I high
[45] Left key [10] Out of speed range
[46] Right key [11] Below speed low
[47] Up key [12] Above speed high
[48] Down key [13] Out of feedb. range
[50] Comparator 4 [14] Below feedb. low
[51] Comparator 5 [15] Above feedb. high
[60] Logic rule 4 [16] Thermal warning
[61] Logic rule 5 [17] Mains out of range
130BB673.10
Logic Rule Operator 1 Logic Rule Operator 2
Par. 13-40
Array [6]
Logic Rule Boolean 1
Par. 13-42 Option: Function:
Logic Rule Boolean 2 ...
... [25] Comparator 3
...
... [26] Logic rule 0
Par. 13-44 [27] Logic rule 1
Logic Rule Boolean 3 [28] Logic rule 2
Figure 6.18 Logic Rules [29] Logic rule 3
[30] SL Timeout 0
[31] SL Timeout 1
Priority of calculation [32] SL Timeout 2
The results of 13-40 Logic Rule Boolean 1, 13-41 Logic Rule [33] Digital input DI18
6 6 Operator 1 and 13-42 Logic Rule Boolean 2 are calculated
first. The outcome (TRUE/FALSE) of this calculation is
[34]
[35]
Digital input DI19
Digital input DI27
combined with the settings of 13-43 Logic Rule Operator 2 [36] Digital input DI29
and 13-44 Logic Rule Boolean 3, yielding the final result
[37] Digital input DI32
(TRUE/FALSE) of the logic rule.
[38] Digital input DI33
13-40 Logic Rule Boolean 1 [39] Start command
Array [6] [40] Drive stopped
[91] ATEX ETR cur. alarm Selectable if1-90 Motor Thermal [6] NOT OR Evaluates the expression NOT [13-40] OR
Protection is set to [20] ATEX ETR [13-42].
or [21] Advanced ETR. If the alarm
[7] NOT AND NOT Evaluates the expression NOT [13-40] AND
166 ATEX ETR freq.lim.alarm is
NOT [13-42].
active, the output will be 1.
[8] NOT OR NOT Evaluates the expression NOT [13-40] OR
[92] ATEX ETR freq. warning Selectable if 1-90 Motor Thermal
NOT [13-42].
Protection is set to [20] ATEX ETR
or [21] Advanced ETR. If the alarm
13-42 Logic Rule Boolean 2
6 6
163 ATEX ETR cur.lim.warning is
Array [6]
active, the output will be 1.
Option: Function:
[93] ATEX ETR freq. alarm Selectable if 1-90 Motor Thermal
[0] FALSE Select the second boolean (TRUE
Protection is set to [20] ATEX ETR
or FALSE) input for the selected
or [21] Advanced ETR. If the
logic rule. See 13-01 Start Event
warning 165 ATEX ETR
([0] - [61]) and 13-02 Stop Event
freq.lim.warning is active, the
([70] - [75]) for further description.
output will be 1.
[1] TRUE
[94] RS Flipflop 0 See 13-1* Comparators
[2] Running
[95] RS Flipflop 1 See 13-1* Comparators
[3] In range
[96] RS Flipflop 2 See 13-1* Comparators [4] On reference
6 6 [40]
[41]
Drive stopped
Reset Trip
freq.lim.warning is active, the
output will be 1.
[42] Auto-reset Trip [94] RS Flipflop 0 See 13-1* Comparators
[43] OK key
[95] RS Flipflop 1 See 13-1* Comparators
[44] Reset key
[45] Left key [96] RS Flipflop 2 See 13-1* Comparators
[46] Right key [97] RS Flipflop 3 See 13-1* Comparators
[47] Up key
[98] RS Flipflop 4 See 13-1* Comparators
[48] Down key
[50] Comparator 4 [99] RS Flipflop 5 See 13-1* Comparators
[26] Logic rule 0 [91] ATEX ETR cur. alarm Selectable if 1-90 Motor Thermal
[27] Logic rule 1 Protection is set to [20] ATEX ETR
[28] Logic rule 2 or [21] Advanced ETR. If the alarm
[29] Logic rule 3 166 ATEX ETR freq.lim.alarm is
[30] SL Timeout 0 active, the output will be 1.
[31] SL Timeout 1 [92] ATEX ETR freq. warning Selectable if 1-90 Motor Thermal
[32] SL Timeout 2 Protection is set to [20] ATEX ETR
[33] Digital input DI18 or [21] Advanced ETR. If the alarm
[34] Digital input DI19 163 ATEX ETR cur.lim.warning is
[35] Digital input DI27 active, the output will be 1.
[36] Digital input DI29 [93] ATEX ETR freq. alarm Selectable if 1-90 Motor Thermal
[37] Digital input DI32 Protection is set to [20] ATEX ETR
[38] Digital input DI33 or [21] Advanced ETR]. If the
[39] Start command warning 165 ATEX ETR
[40] Drive stopped freq.lim.warning is active, the
[41] Reset Trip output will be 1.
[42] Auto-reset Trip [94] RS Flipflop 0 See 13-1* Comparators
[43] OK key
[3] Select set-up 2 Changes the active set-up 0-10 Active Set- [16] Select preset ref Selects preset reference 6.
up) to ‘2’. 6 If the active preset reference is changed,
it will merge with other preset reference
[17] Select preset ref Selects preset reference 7. [39] Set digital out B Any output with SL output B will be high.
7 If the active preset reference is changed, high
it will merge with other preset reference [40] Set digital out C Any output with SL output C will be high.
commands coming from either the digital high
inputs or via a fieldbus. [41] Set digital out D Any output with SL output D will be high.
high
[18] Select ramp 1 Selects ramp 1.
[42] Set digital out E Any output with SL output E will be high.
Selects ramp 3.
high
[43] Set digital out F Any output with SL output Fwill be high.
high
[21] Select ramp 4 Selects ramp 4.
[60] Reset Counter A Resets Counter A to zero.
[22] Run Issues a start command to the frequency
[61] Reset Counter B Resets Counter B to zero.
converter.
[70] Start timer 3 Start Timer 3, see 13-20 SL Controller Timer
[23] Run reverse Issues a start reverse command to the
for further description.
frequency converter.
[71] Start timer 4 Start Timer 4, see 13-20 SL Controller Timer
[24] Stop Issues a stop command to the frequency
for further description.
converter.
[72] Start timer 5 Start Timer 5, see 13-20 SL Controller Timer
[25] Qstop Issues a quick stop command to the
for further description.
frequency converter.
[73] Start timer 6 Start Timer 6, see 13-20 SL Controller Timer
[26] Dcstop Issues a DC stop command to the
for further description.
frequency converter.
[74] Start timer 7 Start Timer 7, see 13-20 SL Controller Timer
[27] Coast The frequency converter coasts
for further description.
immediately. All stop commands including
the coast command stop the SLC.
[32] Set digital out A Any output with SL output A will be low.
low
[33] Set digital out B Any output with SL output B will be low.
low
[34] Set digital out C Any output with SL output Cwill be low.
low
[35] Set digital out D Any output with SL output D will be low.
low
[36] Set digital out E Any output with SL output E will be low.
low
[37] Set digital out F Any output with SL output F will be low.
low
[1] Warning
[2] Trip
[3] Trip Lock
Parameter group containing compressor drive information [1] Reset counter Press [OK] to reset the kWh counter to zero
such as (see 15-02 kWh Counter).
15-03 Power-ups
Range: Function:
0* [0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
[0] No
[1] Yes
6 6
Bit 3 Digital input term. 27
42 Output.
Bit 4 Digital input term. 19
Bit 5 Digital input term. 18 16-66 Digital Output [bin]
Bit 6 Digital input term. 37
Range: Function:
Bit 7 Digital input GP I/O term. X30/4
0* [0 - 15 ] View the binary value of all digital outputs.
Bit 8 Digital input GP I/O term. X30/3
Bit 9 Digital input GP I/O term. X30/2
16-67 Pulse Input #29 [Hz]
Bit 10-63 Reserved for future terminals
Range: Function:
Table 6.11 Active Digital Inputs 0* [0 - 130000 ] View the actual frequency rate on terminal
29.
0 0 0 0 0 0 0 0 0 0 0 0 0 00 00
130BA894.10
DI T -33
DI T -32
16-68 Freq. Input #33 [Hz]
DI T -29
DI T -27 Range: Function:
DI T -19
DI T -18
0* [0 - 130000 ] View the actual value of the frequency
DI T -37 applied at terminal 33 as an impulse input.
DI X30/4
DI X30/3
DI X30/2
DI X46/13
16-69 Pulse Output #27 [Hz]
DI X46/11
DI X46/9 Range: Function:
DI X46/7
DI X46/5 0* [0 - 40000 ] View the actual value of pulses applied to
DI X46/3
DI X46/1 terminal 27 in digital output mode.
Figure 6.21 Relay Settings
16-70 Pulse Output #29 [Hz]
Range: Function:
0* [0 - 40000 ] View the actual value of pulses at terminal 29
16-61 Terminal 53 Switch Setting in digital output mode.
Option: Function:
View the setting of input terminal 53.
[0] Current
[1] Voltage
[0] Current
6.14 Par. Group 25 - Cascade Controller To configure the Cascade Controller to the actual system
and the desired control strategy, it is recommended to
Parameters for configuring the Basic Cascade Controller for follow the below sequence, starting with parameter group
sequence control of multiple compressors. 25-0* System Settings, and next parameter group 25-5*
Alternation Settings.These parameters can normally be set
in advance.
Parameters in parameter group 25-2* Bandwidth Settings
and 25-4* Staging settings will often be dependent on the
dynamic of the system and final adjustment to be done at
the commissioning of the plant.
NOTICE!
The Cascade Controller is supposed to operate in closed
loop controlled by the built-in PI controller ([1] Speed 6 6
Closed Loop selected in 1-00 Configuration Mode). If [0]
Speed Open Loop is selected in 1-00 Configuration Mode, all
fixed speed compressors will be destaged, but the variable
speed compressor will still be controlled by the frequency
converter, now as an open loop configuration:
6 6
130BA370.11
175ZA672.12
OBW (27-71)
SBW (27-20)
SBW (27-70)
Actual head
Setpoint
Setpoint
SBW (27-70)
SBW (27-20)
OBW (27-71)
OBW timer (27-25)
[1] At Staging Alternation of the lead compressor function For the Basic Cascade Controller all compressors
will take place when staging another are equal size.
compressor. Disabled [0]: The lead compressor alternation will
[2] At Alternation of the lead compressor function take place at any compressor capacity.
Command will take place at an external command Enabled [1]: The lead compressor function will be
signal or a pre-programmed event. See alternated only if the numbers of compressors
25-51 Alternation Event for available options. running are providing less than 50% of total
[3] At Staging Alternation of the variable speed (lead) compressor capacity.
or at compressor will take place at staging or the Only valid if 25-50 Lead Compressor Alternation is
Command “At Command” signal (See above). different from [0] Off.
6 6
Mains running.
Off All compressors have been stopped by means
of a Stop command applied to the frequency 25-82 Lead Compressor
converter. Option: Function:
In Open Loop 1-00 Configuration Mode has been set for [0]
0 N/A Readout parameter for the actual variable speed
Open Loop. All fixed speed compressors are
compressor in the system. It is updated to reflect the
stopped. The variable speed compressor will
current variable speed compressor in the system when
continue to run.
an alternation takes place. If no lead compressor is
Frozen Staging/destaging of compressors has been selected (Cascade Controller disabled or all
locked and reference locked. compressors interlocked) the display will show NONE.
Jogging All fixed speed compressors are stopped. When
stopped, the variable speed compressor will run 25-83 Relay Status
at jog speed. Array [2]
Running A Start command is applied to the frequency
converter and the Pack controller is controlling On
the compressors. Off Read out of the status for each of the relays assigned to
Running FSBW The frequency converter is tripped off and the control the compressors. Every element in the array
Pack Controller is controlling the fixed speed represents a relay. If a relay is activated, the corresponding
compressors based on 4-14 Motor Speed High element is set to “On”. If a relay is deactivated, the
Limit [Hz]. corresponding element is set to “Off”.
Staging The Pack Controller is staging fixed speed 25-84 Compressor ON Time
compressors.
Array [2]
Destaging The Pack Controller is destaging fixed speed
compressors. 0 [0 – Readout of the value for Compressor ON
Lead Not Set No compressor available to be assigned as h* 2147483647 Time. The Cascade Controller has sete
variable speed compressor. h] counters for the compressors and for the
relays that control the compressors.
25-81 Compressor Status Compressor ON Time monitors the
Option: Function: “operating hours” of each compressor. The
Compressor Status shows the status for the value of each Compressor ON Time counter
number of compressors selected in can be reset to 0 by writing in the
25-06 Number Of Pumps. It is a readout of the parameter, e.g. if the compressor is replaced
status for each of the compressors showing a in case of service.
string, which consists of compressor number
25-85 Relay ON Time
and the current status of the compressor.
Example: Readout is with the abbreviation like Array [2]
“1:D 2:O” This means that compressor 1 is
0 [0 – Readout of the value for Relay ON time. The
running and speed controlled by the
h* 2147483647 Cascade Controller has set counters for the
frequency converter and compressor 2 is
h] compressors and for the relays that control
stopped.
the compressors. Compressor cycling is
[X] Disabled The compressor is interlocked either via
always done based on the relay counters,
25-90 Pump Interlock, or signal on a digital
Array [2]
6.15 Par. Group 28 - Compressor Functions 6.15.2 28-1* Oil Return Management
6.15.1 28-0* Short Cycle Protection Insufficient lubrication can be the result of oil depositing
itself in pipes and bends. Return oil deposits to the
When controlling refrigeration compressors, there is often crankcase by increasing velocity for short periods at
a need for limiting the numbers of starts. One way to limit regular time intervals or by ensuring adequate oil return
the starts is to ensure a minimum run time (time between when velocity is too low.
a start and a stop) and a minimum interval between starts.
28-02 Minimum Run Time can override any normal stop With Oil Return Management, these two oil return
command and 28-01 Interval between Starts can override mechanisms can be programmed into the Compressor
any normal start command (Start/Jog/Freeze). Drive™. With Oil Return Management enabled, the
None of the two functions are active if Hand On or Off frequency converter performs oil return by boosting the
modes have been activated via the LCP. If selecting Hand compressor speed to 4200 RPM (70 Hz) for a selectable
6 6 On or Off, the two timers will be reset to 0, and not start
counting until Auto is pressed and an active start
duration. Programme the duration in 28-13 Boost Duration.
The boosts are performed at fixed time intervals
command applied. (programmed in 28-12 Fixed Boost Interval) or if the
28-00 Short Cycle Protection compressor speed has been less than 3000 RPM (50 Hz) for
too long (as programmed in 28-11 Low Speed Running
Option: Function:
Time), whichever occurs first. Thus, the maximum time
[0] Disabled Timer set in 28-01 Interval between Starts is
between two consecutive oil return boosts is as
disabled.
programmed in 28-12 Fixed Boost Interval. A text message
[1] * Enabled Timer set in 28-01 Interval between Starts is
on the LCP indicates oil return boosts.
enabled.
NOTICE! NOTICE!
This parameter can only be [1] Enabled if 25-00 Cascade If 4-13 Motor Speed High Limit [RPM] or 4-14 Motor Speed
Controller is set to [0] Disabled. High Limit [Hz] is set to the boost speed 4200 RPM an oil
boost may cause unwanted staging or destaging if
28-01 Interval Between Starts parameter group 25-** Cascade Controller is active.
Range: Function:
28-10 Oil Return Management
300 s* [0 - 3600 s] Sets the time desired as minimum time
between two starts. Any normal start Option: Function:
command (Start/Jog/Freeze) is disregarded [0] * Off No function
until the timer has expired. [1] On Oil return mechanism is active.
28-12 Fixed Boost Interval Discharge temperatures in the range from warning level to
Range: Function: emergency level trigger a warning and an action set by
parameter par. 28-25 Warning Action. The action can be
occurred due to low flow speed (28-11 Low
None or Decrease cooling. If the action is set to Decrease
Speed Running Time).
cooling, cooling is decreased as a preventive action in an
28-13 Boost Duration attempt to lower the discharge temperature.
Range: Function:
30 s * [10 – 120 s ] This parameter controls the duration of oil Cooling is decreased by step-wise lowering of the shaft
return boosts. speed until the discharge temperature either drops below
warning level or exceeds emergency level. Each step
represents a three-minute period during which the
6.15.3 28-2* Discharge Temperature maximum allowed shaft speed is 10 Hz lower than the
Monitor previous step. The initial step occurs when the discharge
Figure 6.38
NOTICE!
If the cascade controller is active, unwanted staging or de-
staging may result if the discharge temperature monitor
reduces the speed to Motor Speed Low Limit, par. 4-11 or
4-12.
Figure 6.37
28-20 Temperature Source
Option: Function:
Discharge temperatures above the emergency level cause Selects the input terminal to which the
an alarm and an immediate trip to prevent damage to the discharge temperature measurement device is
compressor. connected.
[0] * None No Source. The Discharge Temperature Monitor
is not active.
Normal operations apply for discharge temperatures below
warning level. The discharge temperature is passively [1] Analog The measurement device is connected to input
monitored without affecting drive operations. input 53 terminal 53. Program 6-10 Terminal 53 Low
Voltage to 6-15 Terminal 53 High Ref./Feedb.
Value to match the characteristics of the device.
Option: Function: Low Limit + Δ / 6 ≤ Speed < Motor Speed Low Limit + Δ / 2
[0] * Disabled
[1] Enabled Full: Motor Speed
6 6
current ] percentage of the rated motor intervals become
current in 1-24 Motor Current.
28-42 DC Braking Time Low: 1800 RPM ≤ speed < 2350 RPM
Range: Function: Med: 2350 RPM ≤ speed < 3450 RPM
2.0 s* [0 – 60.0 s] Set the duration of the DC-brake current. High: 3450 RPM ≤ speed < 4550 RPM
28-43 DC Brake Cut-in Speed [RPM] Full: 4550 RPM ≤ speed ≤ 5400 RPM
Range: Function: The profile is presented on the LCP as a histogram. In each
700 RPM [0 – max Set the speed where the DC-brake speed interval, the indicated running time is accurate to
‘0’ = Off* motor speed] Current should cut in. The speed within 1 hour.
must be higher than 0 RPM for the
DC-brake to activate before the
motor is coasted at 0 RPM to
prevent a reverse rotation.
Off: Speed = 0
6 6
Table 6.12
6.16.1 Conversion
Examples:
0s ⇒ conversion index 0
0.00s ⇒ conversion index -2
0ms ⇒ conversion index -3
0.00ms ⇒ conversion index -5
6 6
0-10 Active Set-up [1] Set-up 1 1 set-up TRUE - Uint8
0-11 Programming Set-up [9] Active Set-up All set-ups TRUE - Uint8
0-12 This Set-up Linked to [0] Not linked All set-ups FALSE - Uint8
0-13 Readout: Linked Set-ups 0 N/A All set-ups FALSE 0 Uint16
0-14 Readout: Prog. Set-ups / Channel 0 N/A All set-ups TRUE 0 Int32
0-2* LCP Display
0-20 Display Line 1.1 Small ExpressionLimit All set-ups TRUE - Uint16
0-21 Display Line 1.2 Small ExpressionLimit All set-ups TRUE - Uint16
0-22 Display Line 1.3 Small ExpressionLimit All set-ups TRUE - Uint16
0-23 Display Line 2 Large ExpressionLimit All set-ups TRUE - Uint16
0-24 Display Line 3 Large ExpressionLimit All set-ups TRUE - Uint16
0-25 My Personal Menu ExpressionLimit 1 set-up TRUE 0 Uint16
0-3* LCP Custom Readout
0-30 Custom Readout Unit [1] % All set-ups TRUE - Uint8
0-31 Custom Readout Min Value ExpressionLimit All set-ups TRUE -2 Int32
0-32 Custom Readout Max Value 100 CustomReadoutUnit All set-ups TRUE -2 Int32
0-37 Display Text 1 0 N/A 1 set-up TRUE 0 VisStr[25]
0-38 Display Text 2 0 N/A 1 set-up TRUE 0 VisStr[25]
0-39 Display Text 3 0 N/A 1 set-up TRUE 0 VisStr[25]
0-4* LCP Keypad
0-40 [Hand on] Key on LCP [1] Enabled All set-ups TRUE - Uint8
0-41 [Off] Key on LCP [1] Enabled All set-ups TRUE - Uint8
0-42 [Auto on] Key on LCP [1] Enabled All set-ups TRUE - Uint8
0-43 [Reset] Key on LCP [1] Enabled All set-ups TRUE - Uint8
0-5* Copy/Save
0-50 LCP Copy [0] No copy All set-ups FALSE - Uint8
0-51 Set-up Copy [0] No copy All set-ups FALSE - Uint8
0-6* Password
0-60 Main Menu Password 100 N/A 1 set-up TRUE 0 Int16
0-61 Access to Main Menu w/o Password [0] Full access 1 set-up TRUE - Uint8
0-65 Personal Menu Password 200 N/A 1 set-up TRUE 0 Int16
0-66 Access to Personal Menu w/o Password [0] Full access 1 set-up TRUE - Uint8
0-67 Bus Password Access 0 N/A All set-ups TRUE 0 Uint16
0-7* Clock Settings
0-70 Set Date and Time ExpressionLimit All set-ups TRUE 0 TimeOfDay
0-71 Date Format ExpressionLimit 1 set-up TRUE - Uint8
0-72 Time Format ExpressionLimit 1 set-up TRUE - Uint8
0-74 DST/Summertime [0] Off 1 set-up TRUE - Uint8
0-76 DST/Summertime Start ExpressionLimit 1 set-up TRUE 0 TimeOfDay
6 6
6 6
1-15 Low Speed Filter Time Const. ExpressionLimit All set-ups TRUE -2 Uint16
1-16 High Speed Filter Time Const. ExpressionLimit All set-ups TRUE -2 Uint16
1-17 Voltage filter time const. ExpressionLimit All set-ups TRUE -3 Uint16
1-2* Motor Data
1-20 Motor Power [kW] ExpressionLimit All set-ups FALSE 1 Uint32
1-21 Motor Power [HP] ExpressionLimit All set-ups FALSE -2 Uint32
1-22 Motor Voltage ExpressionLimit All set-ups FALSE 0 Uint16
1-23 Motor Frequency ExpressionLimit All set-ups FALSE 0 Uint16
1-24 Motor Current ExpressionLimit All set-ups FALSE -2 Uint32
1-25 Motor Nominal Speed ExpressionLimit All set-ups FALSE 67 Uint16
1-26 Motor Cont. Rated Torque ExpressionLimit All set-ups FALSE -1 Uint32
1-28 Motor Rotation Check [0] Off All set-ups FALSE - Uint8
1-29 Automatic Motor Adaptation (AMA) [0] Off All set-ups FALSE - Uint8
1-3* Adv. Motor Data
1-30 Stator Resistance (Rs) ExpressionLimit All set-ups FALSE -4 Uint32
1-31 Rotor Resistance (Rr) ExpressionLimit All set-ups FALSE -4 Uint32
1-35 Main Reactance (Xh) ExpressionLimit All set-ups FALSE -4 Uint32
1-36 Iron Loss Resistance (Rfe) ExpressionLimit All set-ups FALSE -3 Uint32
1-37 d-axis Inductance (Ld) ExpressionLimit All set-ups FALSE -6 Int32
1-39 Motor Poles ExpressionLimit All set-ups FALSE 0 Uint8
1-40 Back EMF at 1000 RPM ExpressionLimit All set-ups FALSE 0 Uint16
1-5* Load Indep. Setting
1-50 Motor Magnetization at Zero Speed 100 % All set-ups TRUE 0 Uint16
1-51 Min Speed Normal Magnetizing [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-52 Min Speed Normal Magnetizing [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-58 Flystart Test Pulses Current ExpressionLimit All set-ups FALSE 0 Uint16
1-59 Flystart Test Pulses Frequency ExpressionLimit All set-ups FALSE 0 Uint16
1-6* Load Depen. Setting
1-60 Low Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-61 High Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-62 Slip Compensation 0% All set-ups TRUE 0 Int16
1-63 Slip Compensation Time Constant ExpressionLimit All set-ups TRUE -2 Uint16
1-64 Resonance Dampening 100 % All set-ups TRUE 0 Uint16
1-65 Resonance Dampening Time Constant 5 ms All set-ups TRUE -3 Uint8
1-66 Min. Current at Low Speed ExpressionLimit All set-ups TRUE 0 Uint8
1-7* Start Adjustments
1-70 PM Start Mode [1] Parking All set-ups TRUE - Uint8
1-71 Start Delay 00 s All set-ups TRUE -1 Uint16
1-72 Start Function ExpressionLimit All set-ups TRUE - Uint8
6 6
1-81 Min Speed for Function at Stop [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-82 Min Speed for Function at Stop [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-86 Compressor Min. Speed for Trip [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-87 Compressor Min. Speed for Trip [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-9* Motor Temperature
1-90 Motor Thermal Protection ExpressionLimit All set-ups TRUE - Uint8
1-91 Motor External Fan [0] None All set-ups TRUE - Uint8
1-93 Thermistor Source [0] None All set-ups TRUE - Uint8
6 6
3-13 Reference Site [0] Linked to Hand / Auto All set-ups TRUE - Uint8
3-14 Preset Relative Reference 0% All set-ups TRUE -2 Int32
3-15 Reference 1 Source [1] Analog Input 53 All set-ups TRUE - Uint8
3-16 Reference 2 Source [20] Digital pot.meter All set-ups TRUE - Uint8
3-17 Reference 3 Source [0] No function All set-ups TRUE - Uint8
3-19 Jog Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
3-4* Ramp 1
3-41 Ramp 1 Ramp Up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-42 Ramp 1 Ramp Down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-5* Ramp 2
3-51 Ramp 2 Ramp Up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-52 Ramp 2 Ramp Down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-8* Other Ramps
3-80 Jog Ramp Time ExpressionLimit All set-ups TRUE -2 Uint32
3-81 Quick Stop Ramp Time ExpressionLimit 2 set-ups TRUE -2 Uint32
3-82 Starting Ramp Up Time ExpressionLimit 2 set-ups TRUE -2 Uint32
3-9* Digital Pot.Meter
3-90 Step Size 0.10 % All set-ups TRUE -2 Uint16
3-91 Ramp Time 1s All set-ups TRUE -2 Uint32
3-92 Power Restore [0] Off All set-ups TRUE - Uint8
3-93 Maximum Limit 100 % All set-ups TRUE 0 Int16
3-94 Minimum Limit 0% All set-ups TRUE 0 Int16
3-95 Ramp Delay 1 N/A All set-ups TRUE -3 TimD
6 6
4-17 Torque Limit Generator Mode 100 % All set-ups TRUE -1 Uint16
4-18 Current Limit ExpressionLimit All set-ups TRUE -1 Uint32
4-19 Max Output Frequency ExpressionLimit All set-ups FALSE -1 Uint16
4-5* Adj. Warnings
4-50 Warning Current Low 0A All set-ups TRUE -2 Uint32
4-51 Warning Current High ImaxVLT (P1637) All set-ups TRUE -2 Uint32
4-52 Warning Speed Low 0 RPM All set-ups TRUE 67 Uint16
4-53 Warning Speed High outputSpeedHighLimit (P413) All set-ups TRUE 67 Uint16
4-54 Warning Reference Low -999999 N/A All set-ups TRUE -3 Int32
4-55 Warning Reference High 999999 N/A All set-ups TRUE -3 Int32
-999999 ReferenceFeed-
4-56 Warning Feedback Low backUnit All set-ups TRUE -3 Int32
999999 ReferenceFeed-
4-57 Warning Feedback High backUnit All set-ups TRUE -3 Int32
4-58 Missing Motor Phase Function ExpressionLimit All set-ups TRUE - Uint8
4-6* Speed Bypass
4-60 Bypass Speed From [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-61 Bypass Speed From [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-62 Bypass Speed To [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-63 Bypass Speed To [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-64 Semi-Auto Bypass Set-up [0] Off All set-ups FALSE - Uint8
6 6
5-12 Terminal 27 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-13 Terminal 29 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-14 Terminal 32 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-15 Terminal 33 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-16 Terminal X30/2 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-17 Terminal X30/3 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-18 Terminal X30/4 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-19 Terminal 37 Safe Stop [1] Safe Stop Alarm All set-ups TRUE - Uint8
5-3* Digital Outputs
5-30 Terminal 27 Digital Output [0] No operation All set-ups TRUE - Uint8
5-31 Terminal 29 Digital Output [0] No operation All set-ups TRUE - Uint8
5-32 Term X30/6 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint8
5-33 Term X30/7 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint8
5-4* Relays
5-40 Function Relay ExpressionLimit All set-ups TRUE - Uint8
5-41 On Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-42 Off Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-5* Pulse Input
5-50 Term. 29 Low Frequency 100 Hz All set-ups TRUE 0 Uint32
5-51 Term. 29 High Frequency 100 Hz All set-ups TRUE 0 Uint32
5-52 Term. 29 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
5-53 Term. 29 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int32
5-54 Pulse Filter Time Constant #29 100 ms All set-ups FALSE -3 Uint16
5-55 Term. 33 Low Frequency 100 Hz All set-ups TRUE 0 Uint32
5-56 Term. 33 High Frequency 100 Hz All set-ups TRUE 0 Uint32
5-57 Term. 33 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
5-58 Term. 33 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int32
5-59 Pulse Filter Time Constant #33 100 ms All set-ups FALSE -3 Uint16
5-6* Pulse Output
5-60 Terminal 27 Pulse Output Variable [0] No operation All set-ups TRUE - Uint8
5-62 Pulse Output Max Freq #27 5000 Hz All set-ups TRUE 0 Uint32
5-63 Terminal 29 Pulse Output Variable [0] No operation All set-ups TRUE - Uint8
5-65 Pulse Output Max Freq #29 5000 Hz All set-ups TRUE 0 Uint32
5-66 Terminal X30/6 Pulse Output Variable [0] No operation All set-ups TRUE - Uint8
5-68 Pulse Output Max Freq #X30/6 5000 Hz All set-ups TRUE 0 Uint32
5-9* Bus Controlled
5-90 Digital & Relay Bus Control 0 N/A All set-ups TRUE 0 Uint32
5-93 Pulse Out #27 Bus Control 0% All set-ups TRUE -2 N2
5-94 Pulse Out #27 Timeout Preset 0% 1 set-up TRUE -2 Uint16
6 6
6 6
6-12 Terminal 53 Low Current 4 mA All set-ups TRUE -5 Int16
6-13 Terminal 53 High Current 20 mA All set-ups TRUE -5 Int16
6-14 Terminal 53 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
6-15 Terminal 53 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-16 Terminal 53 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-17 Terminal 53 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-2* Analog Input 54
6-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-21 Terminal 54 High Voltage 10 V All set-ups TRUE -2 Int16
6-22 Terminal 54 Low Current 4 mA All set-ups TRUE -5 Int16
6-23 Terminal 54 High Current 20 mA All set-ups TRUE -5 Int16
6-24 Terminal 54 Low Ref./Feedb. Value -1 N/A All set-ups TRUE -3 Int32
6-25 Terminal 54 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-26 Terminal 54 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-27 Terminal 54 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-3* Analog Input X30/11
6-30 Terminal X30/11 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-31 Terminal X30/11 High Voltage 10 V All set-ups TRUE -2 Int16
6-34 Term. X30/11 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
6-35 Term. X30/11 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int32
6-36 Term. X30/11 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-37 Term. X30/11 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-4* Analog Input X30/12
6-40 Terminal X30/12 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-41 Terminal X30/12 High Voltage 10 V All set-ups TRUE -2 Int16
6-44 Term. X30/12 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
6-45 Term. X30/12 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int32
6-46 Term. X30/12 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-47 Term. X30/12 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-5* Analog Output 42
6-50 Terminal 42 Output [100] Output frequency All set-ups TRUE - Uint8
6-51 Terminal 42 Output Min Scale 0% All set-ups TRUE -2 Int16
6-52 Terminal 42 Output Max Scale 100 % All set-ups TRUE -2 Int16
6-53 Terminal 42 Output Bus Control 0% All set-ups TRUE -2 N2
6-54 Terminal 42 Output Timeout Preset 0% 1 set-up TRUE -2 Uint16
6-6* Analog Output X30/8
6-60 Terminal X30/8 Output [0] No operation All set-ups TRUE - Uint8
6-61 Terminal X30/8 Min. Scale 0% All set-ups TRUE -2 Int16
6-62 Terminal X30/8 Max. Scale 100 % All set-ups TRUE -2 Int16
6 6
6 6
7-07 Speed PID Feedback Gear Ratio 1.0000 N/A All set-ups FALSE -4 Uint32
7-08 Speed PID Feed Forward Factor 0% All set-ups FALSE 0 Uint16
7-09 Speed PID Error Correction w/ Ramp 300RPM All set-ups TRUE 67 Uint32
7-1* Torque PI Ctrl.
7-12 Torque PI Proportional Gain 100% All set-ups TRUE 0 Uint16
7-13 Torque PI Integration Time 0.020 s All set-ups TRUE -3 Uint16
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource [0] No function All set-ups TRUE - Uint8
7-22 Process CL Feedback 2 Resource [0] No function All set-ups TRUE - Uint8
7-3* Process PID Ctrl.
7-30 Process PID Normal/ Inverse Control [0] Normal All set-ups TRUE - Uint8
7-31 Process PID Anti Windup [1] On All set-ups TRUE - Uint8
7-32 Process PID Start Speed 0 RPM All set-ups TRUE 67 Uint16
7-33 Process PID Proportional Gain 0.01 N/A All set-ups TRUE -2 Uint16
7-34 Process PID Integral Time 10000.00 s All set-ups TRUE -2 Uint32
7-35 Process PID Differentiation Time 0.00 s All set-ups TRUE -2 Uint16
7-36 Process PID Diff. Gain Limit 5.0 N/A All set-ups TRUE -1 Uint16
7-38 Process PID Feed Forward Factor 0% All set-ups TRUE 0 Uint16
7-39 On Reference Bandwidth 5% All set-ups TRUE 0 Uint8
6 6
8-07 Diagnosis Trigger [0] Disable 2 set-ups TRUE - Uint8
8-1* Ctrl. Word Settings
8-10 Control Word Profile [0] FC profile All set-ups TRUE - Uint8
8-13 Configurable Status Word STW [1] Profile Default All set-ups TRUE - Uint8
8-16 Store Data Values [0] Off All set-ups TRUE - Uint8
8-3* FC Port Settings
8-30 Protocol [0] FC 1 set-up TRUE - Uint8
8-31 Address 1 N/A 1 set-up TRUE 0 Uint8
8-32 FC Port Baud Rate ExpressionLimit 1 set-up TRUE - Uint8
8-33 Parity / Stop Bits ExpressionLimit 1 set-up TRUE - Uint8
8-35 Minimum Response Delay 10 ms 1 set-up TRUE -3 Uint16
8-36 Max Response Delay ExpressionLimit 1 set-up TRUE -3 Uint16
8-37 Max Inter-Char Delay ExpressionLimit 1 set-up TRUE -5 Uint16
8-4* FC MC protocol set
8-40 Telegram Selection [1] Standard telegram 1 2 set-ups TRUE - Uint8
8-42 PCD Write Configuration ExpressionLimit 2 set-ups TRUE - Uint16
8-43 PCD Read Configuration ExpressionLimit 2 set-ups TRUE - Uint16
8-5* Digital/Bus
8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint8
8-51 Quick Stop Select [3] Logic OR All set-ups TRUE - Uint8
8-52 DC Brake Select [3] Logic OR All set-ups TRUE - Uint8
8-53 Start Select [3] Logic OR All set-ups TRUE - Uint8
8-54 Reversing Select [3] Logic OR All set-ups TRUE - Uint8
8-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint8
8-56 Preset Reference Select [3] Logic OR All set-ups TRUE - Uint8
8-8* FC Port Diagnostics
8-80 Bus Message Count 0 N/A All set-ups TRUE 0 Uint32
8-81 Bus Error Count 0 N/A All set-ups TRUE 0 Uint32
8-82 Slave Messages Rcvd 0 N/A All set-ups TRUE 0 Uint32
8-83 Slave Error Count 0 N/A All set-ups TRUE 0 Uint32
8-9* Bus Jog
8-90 Bus Jog 1 Speed 100 RPM All set-ups TRUE 67 Uint16
8-91 Bus Jog 2 Speed 200 RPM All set-ups TRUE 67 Uint16
6 6
14-11 Mains Voltage at Mains Fault ExpressionLimit All set-ups TRUE 0 Uint16
14-12 Function at Mains Imbalance [1] Warning All set-ups TRUE - Uint8
14-13 Mains Failure Step Factor 1 N/A All set-ups TRUE -1 Uint8
14-2* Trip Reset
14-20 Reset Mode [10] Automatic reset x 10 All set-ups TRUE - Uint8
14-21 Automatic Restart Time 30 s All set-ups TRUE 0 Uint16
14-22 Operation Mode [0] Normal operation All set-ups TRUE - Uint8
14-23 Typecode Setting ExpressionLimit 2 set-ups FALSE - Uint8
14-25 Trip Delay at Torque Limit 60 s All set-ups TRUE 0 Uint8
14-26 Trip Delay at Inverter Fault ExpressionLimit All set-ups TRUE 0 Uint8
14-28 Production Settings [0] No action All set-ups TRUE - Uint8
14-29 Service Code 0 N/A All set-ups TRUE 0 Int32
14-3* Current Limit Ctrl.
14-30 Current Lim Cont, Proportional Gain 100 % All set-ups FALSE 0 Uint16
14-31 Current Lim Contr, Integration Time 0.020 s All set-ups FALSE -3 Uint16
14-32 Current Lim Ctrl, Filter Time 26 ms All set-ups TRUE -4 Uint16
14-4* Energy Optimizing
14-40 VT Level 66 % All set-ups FALSE 0 Uint8
14-41 AEO Minimum Magnetisation 40 % All set-ups TRUE 0 Uint8
14-42 Minimum AEO Frequency 30 Hz All set-ups TRUE 0 Uint8
14-43 Motor Cosphi ExpressionLimit All set-ups TRUE -2 Uint16
14-5* Environment
14-50 RFI Filter [1] On 1 set-up FALSE - Uint8
14-52 Fan Control [0] Auto All set-ups TRUE - Uint8
14-53 Fan Monitor [0] Disabled All set-ups TRUE - Uint8
14-55 Output Filter [0] No Filter 1 set-up FALSE - Uint8
14-56 Capacitance Output Filter 2 uF 1 set-up FALSE -7 Uint16
14-57 Inductance Output Filter 7 mH 1 set-up FALSE -6 Uint16
14-6* Auto Derate
14-60 Function at Over Temperature [1] Derate All set-ups TRUE - Uint8
14-61 Function at Inverter Overload [1] Derate All set-ups TRUE - Uint8
14-62 Inv. Overload Derate Current 95 % All set-ups TRUE 0 Uint16
14-9* Fault Settings
14-90 Fault Level ExpressionLimit 1 set-up TRUE - Uint8
6 6
15-06 Reset kWh Counter [0] Do not reset All set-ups TRUE - Uint8
15-07 Reset Running Hours Counter [0] Do not reset All set-ups TRUE - Uint8
15-08 Number of Starts 0 N/A All set-ups FALSE 0 Uint32
15-1* Data Log Settings
15-10 Logging Source 0 2 set-ups TRUE - Uint16
15-11 Logging Interval ExpressionLimit 2 set-ups TRUE -3 TimD
15-12 Trigger Event [0] False 1 set-up TRUE - Uint8
15-13 Logging Mode [0] Log always 2 set-ups TRUE - Uint8
15-14 Samples Before Trigger 50 N/A 2 set-ups TRUE 0 Uint8
15-2* Historic Log
15-20 Historic Log: Event 0 N/A All set-ups FALSE 0 Uint8
15-21 Historic Log: Value 0 N/A All set-ups FALSE 0 Uint32
15-22 Historic Log: Time 0 ms All set-ups FALSE -3 Uint32
15-23 Historic log: Date and Time ExpressionLimit All set-ups FALSE 0 TimeOfDay
15-3* Alarm Log
15-30 Alarm Log: Error Code 0 N/A All set-ups FALSE 0 Uint8
15-31 Alarm Log: Value 0 N/A All set-ups FALSE 0 Int16
15-32 Alarm Log: Time 0s All set-ups FALSE 0 Uint32
15-33 Alarm Log: Date and Time ExpressionLimit All set-ups FALSE 0 TimeOfDay
15-34 Alarm Log: Status 0 N/A All set-ups FALSE 0 Uint8
15-35 Alarm Log: Alarm Text 0 N/A All set-ups FALSE 0 VisStr[32]
15-4* Drive Identification
15-40 FC Type 0 N/A All set-ups FALSE 0 VisStr[6]
15-41 Power Section 0 N/A All set-ups FALSE 0 VisStr[20]
15-42 Voltage 0 N/A All set-ups FALSE 0 VisStr[20]
15-43 Software Version 0 N/A All set-ups FALSE 0 VisStr[5]
15-44 Ordered Typecode String 0 N/A All set-ups FALSE 0 VisStr[40]
15-45 Actual Typecode String 0 N/A All set-ups FALSE 0 VisStr[40]
15-46 Frequency Converter Ordering No 0 N/A All set-ups FALSE 0 VisStr[8]
15-47 Power Card Ordering No 0 N/A All set-ups FALSE 0 VisStr[8]
15-48 LCP Id No 0 N/A All set-ups FALSE 0 VisStr[20]
15-49 SW ID Control Card 0 N/A All set-ups FALSE 0 VisStr[20]
15-50 SW ID Power Card 0 N/A All set-ups FALSE 0 VisStr[20]
15-51 Frequency Converter Serial Number 0 N/A All set-ups FALSE 0 VisStr[10]
15-53 Power Card Serial Number 0 N/A All set-ups FALSE 0 VisStr[19]
15-6* Option Ident
15-60 Option Mounted 0 N/A All set-ups FALSE 0 VisStr[30]
15-61 Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
15-62 Option Ordering No 0 N/A All set-ups FALSE 0 VisStr[8]
6 6
15-9* Parameter Info
15-92 Defined Parameters 0 N/A All set-ups FALSE 0 Uint16
15-93 Modified Parameters 0 N/A All set-ups FALSE 0 Uint16
15-99 Parameter Metadata 0 N/A All set-ups FALSE 0 Uint16
6 6
16-1* Motor Status
16-10 Power [kW] 0 kW All set-ups FALSE 1 Int32
16-11 Power [hp] 0 hp All set-ups FALSE -2 Int32
16-12 Motor Voltage 0V All set-ups FALSE -1 Uint16
16-13 Frequency 0 Hz All set-ups FALSE -1 Uint16
16-14 Motor current 0A All set-ups FALSE -2 Int32
16-15 Frequency [%] 0% All set-ups FALSE -2 N2
16-16 Torque [Nm] 0 Nm All set-ups FALSE -1 Int32
16-17 Speed [RPM] 0 RPM All set-ups FALSE 67 Int32
16-18 Motor Thermal 0% All set-ups FALSE 0 Uint8
16-22 Torque [%] 0% All set-ups FALSE 0 Int16
16-3* Drive Status
16-30 DC Link Voltage 0V All set-ups FALSE 0 Uint16
16-32 Brake Energy /s 0 kW All set-ups FALSE 0 Uint32
16-33 Brake Energy /2 min 0 kW All set-ups FALSE 0 Uint32
16-34 Heatsink Temp. 0 °C All set-ups FALSE 100 Uint8
16-35 Inverter Thermal 0% All set-ups FALSE 0 Uint8
16-36 Inv. Nom. Current ExpressionLimit All set-ups FALSE -2 Uint32
16-37 Inv. Max. Current ExpressionLimit All set-ups FALSE -2 Uint32
16-38 SL Controller State 0 N/A All set-ups FALSE 0 Uint8
16-39 Control Card Temp. 0 °C All set-ups FALSE 100 Uint8
16-40 Logging Buffer Full [0] No All set-ups TRUE - Uint8
16-41 LCP Bottom Statusline 0 N/A All set-ups TRUE 0 VisStr[50]
16-5* Ref. & Feedb.
16-50 External Reference 0 N/A All set-ups FALSE -1 Int16
16-52 Feedback[Unit] 0 ProcessCtrlUnit All set-ups FALSE -3 Int32
16-53 Digi Pot Reference 0 N/A All set-ups FALSE -2 Int16
16-54 Feedback 1 [Unit] 0 ProcessCtrlUnit All set-ups FALSE -3 Int32
16-55 Feedback 2 [Unit] 0 ProcessCtrlUnit All set-ups FALSE -3 Int32
16-56 Feedback 3 [Unit] 0 ProcessCtrlUnit All set-ups FALSE -3 Int32
16-6* Inputs & Outputs
16-60 Digital Input 0 N/A All set-ups FALSE 0 Uint16
16-61 Terminal 53 Switch Setting [0] Current All set-ups FALSE - Uint8
16-62 Analog Input 53 0 N/A All set-ups FALSE -3 Int32
16-63 Terminal 54 Switch Setting [0] Current All set-ups FALSE - Uint8
16-64 Analog Input 54 0 N/A All set-ups FALSE -3 Int32
16-65 Analog Output 42 [mA] 0 N/A All set-ups FALSE -3 Int16
16-66 Digital Output [bin] 0 N/A All set-ups FALSE 0 Int16
16-67 Pulse Input #29 [Hz] 0 N/A All set-ups FALSE 0 Int32
6 6
16-8* Fieldbus & FC Port
16-80 Fieldbus CTW 1 0 N/A All set-ups FALSE 0 V2
16-82 Fieldbus REF 1 0 N/A All set-ups FALSE 0 N2
16-84 Comm. Option STW 0 N/A All set-ups FALSE 0 V2
16-85 FC Port CTW 1 0 N/A All set-ups FALSE 0 V2
16-86 FC Port REF 1 0 N/A All set-ups FALSE 0 N2
16-9* Diagnosis Readouts
16-90 Alarm Word 0 N/A All set-ups FALSE 0 Uint32
16-91 Alarm Word 2 0 N/A All set-ups FALSE 0 Uint32
16-92 Warning Word 0 N/A All set-ups FALSE 0 Uint32
16-93 Warning Word 2 0 N/A All set-ups FALSE 0 Uint32
16-94 Ext. Status Word 0 N/A All set-ups FALSE 0 Uint32
16-95 Ext. Status Word 2 0 N/A All set-ups FALSE 0 Uint32
16-96 Maintenance Word 0 N/A All set-ups FALSE 0 Uint32
6 6
25-22 - Zone [unit] 3 ReferenceFeedbackUnit All set-ups TRUE -2 Uint32
25-23 Fixed Speed neutral Zone [unit] 4 ReferenceFeedbackUnit All set-ups TRUE -2 Uint32
25-24 + Zone Delay 120 s All set-ups TRUE 0 Uint32
25-25 - Zone Delay 60 s All set-ups TRUE 0 Uint32
25-26 ++ Zone Delay 60 s All set-ups TRUE 0 Uint32
25-27 -- Zone Delay 30 s All set-ups TRUE 0 Uint32
25-3* Staging Functions
25-30 Destage At No-Flow [0] Disabled All set-ups TRUE - Uint8
25-31 Stage Function [0] Disabled All set-ups TRUE - Uint8
25-32 Stage Function Time 15 s All set-ups TRUE 0 Uint16
25-33 Destage Function [0] Disabled All set-ups TRUE - Uint8
25-34 Destage Function Time 15 s All set-ups TRUE 0 Uint16
25-4* Staging Settings
25-42 Staging Threshold ExpressionLimit All set-ups TRUE 0 Uint8
25-43 Destaging Threshold ExpressionLimit All set-ups TRUE 0 Uint8
25-44 Staging Speed [RPM] 0 RPM All set-ups TRUE 67 Uint16
25-45 Staging Speed [Hz] 0 Hz All set-ups TRUE -1 Uint16
25-46 Destaging Speed [RPM] 0 RPM All set-ups TRUE 67 Uint16
25-47 Destaging Speed [Hz] 0 Hz All set-ups TRUE -1 Uint16
25-8* Status
VisStr[2
25-80 Pack Status 0 N/A All set-ups TRUE 0 5]
VisStr[2
25-81 Compressor Status 0 N/A All set-ups TRUE 0 5]
25-82 Lead Compressor 0 N/A All set-ups TRUE 0 Uint8
VisStr[4
25-83 Relay Status 0 N/A All set-ups TRUE 0 ]
25-84 Compressor ON Time 0h All set-ups TRUE 74 Uint32
25-85 Relay ON Time 0h All set-ups TRUE 74 Uint32
25-86 Reset Relay Counters [0] Do not reset All set-ups TRUE - Uint8
25-87 Inverse Interlock 0 N/A All set-ups TRUE 0 Uint16
25-88 Pack capacity [%] 0% All set-ups TRUE 0 Uint16
25-9* Service
25-90 Compressor Interlock [0] Off All set-ups TRUE - Uint8
25-91 Manual Alternation 0 N/A All set-ups TRUE 0 Uint8
6 6
28-12 Fixed Boost Interval 24 h All set-ups TRUE 74 Uint8
28-13 Boost Duration 30 s All set-ups FALSE 0 Uint8
28-2* Discharge Temperature Monitor
28-20 Temperature Source [0] None All set-ups FALSE - Uint8
28-21 Temperature Unit [60] °C All set-ups FALSE - Uint8
28-24 Warning Level 130 N/A All set-ups FALSE 0 Uint16
28-25 Warning Action [1] Decrease cooling All set-ups FALSE - Uint8
28-26 Emergency Level 145 N/A All set-ups FALSE 0 Uint16
28-27 Discharge Temperature 0 DTM_ReadoutUnit All set-ups TRUE 0 Int32
28-3* Crankcase Heating
28-30 Crankcase Heating Control ExpressionLimit All set-ups TRUE - Uint8
28-31 Heating DC Current ExpressionLimit All set-ups TRUE 0 Uint8
28-32 Crankcase Heating Delay 5s All set-ups TRUE 0 Uint16
28-4* Anti-reverse Protection at Stop
28-40 Reverse Protection Control [0] Disabled All set-ups TRUE - Uint8
28-41 DC Brake Current 90 % All set-ups TRUE 0 Uint16
28-42 DC Braking Time ExpressionLimit All set-ups TRUE -1 Uint16
28-43 DC Brake Cut In Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
28-44 DC Brake Cut In Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
28-5* Load Profile
28-50 Reset Load Profile [0] Do not reset All set-ups TRUE - Uint8
28-59 Load Profile Data 0 N/A All set-ups TRUE 0 Uint16
28-7* Day/Night Settings
28-74 Night Speed Drop [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
28-76 Night Speed Drop [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
7 Troubleshooting
7 7
26 Brake resistor power limit (X) (X) 2-13 Brake Power
Monitoring
27 Brake chopper short-circuited X X
28 Brake check (X) (X) 2-15 Brake Check
29 Heatsink temp X X X
30 Motor phase U missing (X) (X) (X) 4-58 Missing Motor
Phase Function
31 Motor phase V missing (X) (X) (X) 4-58 Missing Motor
Phase Function
32 Motor phase W missing (X) (X) (X) 4-58 Missing Motor
Phase Function
33 Inrush Fault X X
34 Fieldbus communication fault X X
35 Option Fault
36 Mains failure X X
37 Phase imbalance X
38 Internal Fault X X
39 Heatsink sensor X X
40 Overload of Digital Output Terminal 27 (X) 5-00 Digital I/O Mode,
5-01 Terminal 27 Mode
41 Overload of Digital Output Terminal 29 (X) 5-00 Digital I/O Mode,
5-02 Terminal 29 Mode
42 Ovrld X30/6-7 (X)
43 Ext. Supply (option)
45 Ground Fault 2 X X
46 Pwr. card supply X X
47 24 V supply low X X X
48 1.8 V supply low X X
49 Speed limit X 1-86 Trip Speed Low
[RPM]
50 AMA calibration failed X
51 AMA check Unom and Inom X
52 AMA low Inom X
53 AMA motor too big X
54 AMA motor too small X
55 AMA parameter out of range X
7 7 149
150
Too many inter.
No ext. 24 V
151 GOSUB > limit
152 Return @ limit
154 D.out overload
155 LINK failed
156 Illegal double arg.
160 Internal Intr. error
162 Memory error
163 ATEX ETR cur.lim.warning X
164 ATEX ETR cur.lim.alarm X
165 ATEX ETR freq.lim.warning X
166 ATEX ETR freq.lim.alarm X
246 Pwr.card supply
250 New spare parts X
251 New Type Code X X
A trip is the action following an alarm. The trip coasts the Warning yellow
motor and is reset by pressing [Reset] or by a digital input Alarm flashing red
(parameter group 5-1* Digital Inputs [1]). The origin event Trip locked yellow and red
that caused an alarm cannot damage the frequency
converter or cause dangerous conditions. A trip lock is an Table 7.2 LED Indication
action when an alarm occurs, which could damage the
frequency converter or connected parts. A trip lock
situation can only be reset by a power cycling.
Bit Hex Dec Alarm Word Alarm Word Warning Word Warning Extended Extended
2 Word 2 Status Word Status Word 2
Alarm Word Extended Status Word
0 00000001 1 Brake Check ServiceTrip, Brake Check (W28) Start Ramping Off
(A28) Read/Write Delayed
1 00000002 2 Pwr.card temp ServiceTrip, Pwr.card temp (A69) Stop AMA Running Hand/Auto
(A69) (reserved) Delayed
2 00000004 4 Ground Fault
(A14)
ServiceTrip,
Typecode/
Ground Fault (W14) reserved Start CW/CCW Profibus OFF1
start_possible is active
7 7
Sparepart active, when the
DI selections [12]
OR [13] are
active and the
requested
direction
matches the
reference sign
3 00000008 8 Ctrl.Card Temp ServiceTrip, Ctrl.Card Temp (W65) reserved Slow Down Profibus OFF2
(A65) (reserved) slow down active
command active,
e.g. via CTW bit
11 or DI
4 00000010 16 Ctrl. Word TO ServiceTrip, Ctrl. Word TO (W17) Catch Up Profibus OFF3
(A17) (reserved) catch up active
command active,
e.g. via CTW bit
12 or DI
5 00000020 32 Over Current reserved Over Current (W13) reserved Feedback High Relay 123 active
(A13) feedback > 4-57
6 00000040 64 Torque Limit reserved Torque Limit (W12) reserved Feedback Low Start Prevented
(A12) feedback < 4-56
7 00000080 128 Motor Th Over reserved Motor Th Over (W11) reserved Output Current Control Ready
(A11) High
current > 4-51
8 00000100 256 Motor ETR Over reserved Motor ETR Over reserved Output Current Drive Ready
(A10) (W10) Low
current < 4-50
9 00000200 512 Inverter Overld. Discharge Inverter Overld (W9) Discharge Output Freq Quick Stop
(A9) High High High
speed > 4-53
10 00000400 1024 DC under Volt Start Failed DC under Volt (W8) Multi- Output Freq Low DC Brake
(A8) motor speed < 4-52
underloa
d
Bit Hex Dec Alarm Word Alarm Word Warning Word Warning Extended Extended
2 Word 2 Status Word Status Word 2
11 00000800 2048 DC over Volt Speed Limit DC over Volt (W7) Multi- Brake Check OK Stop
(A7) motor brake test NOT
Overload ok
12 00001000 4096 Short Circuit External DC Voltage Low (W6) Compress Braking Max Stand by
(A16) Interlock or BrakePower >
Interlock BrakePowerLimit
(2-12)
13 00002000 8192 Inrush Fault Illegal Option DC Voltage High Mechanic Braking Freeze Output
(A33) Combi. (W5) al Brake Request
Sliding
14 00004000 16384 Mains ph. Loss No Safety Mains ph. Loss (W4) Safe Out of Speed Freeze Output
(A4) Option Option Range
Warning
15 00008000 32768 AMA Not OK reserved No Motor (W3) Auto DC OVC Active Jog Request
7 7 16 00010000 65536 Live Zero Error reserved Live Zero Error (W2)
Braking
AC Brake Jog
(A2)
17 00020000 131072 Internal Fault KTY error 10V Low (W1) KTY Warn Password Start Request
(A38) Timelock
number of
allowed
password trials
exceeded -
timelock active
18 00040000 262144 Brake Overload Fans error Brake Overload Fans Password Start
(A26) (W26) Warn Protection
0-61 =
ALL_NO_ACCESS
OR
BUS_NO_ACCESS
OR
BUS_READONLY
19 00080000 524288 U phase Loss ECB error Brake Resistor (W25) ECB Warn Reference High Start Applied
(A30) reference > 4-55
20 00100000 1048576 V phase Loss reserved Brake IGBT (W27) reserved Reference Low Start delay
(A31) reference < 4-54
21 00200000 2097152 W phase Loss reserved Speed Limit (W49) reserved Local Reference Sleep
(A32) reference site =
REMOTE -> auto
on pressed &
active
22 00400000 4194304 Fieldbus Fault reserved Fieldbus Fault (W34) reserved Protection mode Sleep Boost
(A34) notifikation
23 00800000 8388608 24 V Supply reserved 24V Supply Low reserved Unused Running
Low (A47) (W47)
24 01000000 16777216 Mains Failure reserved Mains Failure (W36) reserved Unused Drive Bypass
(A36)
25 02000000 33554432 1.8V Supply Current Limit Current Limit (W59) reserved Unused Fire Mode
Low (A48) (A59)
26 04000000 67108864 Brake Resistor reserved Low Temp (W66) reserved Unused External Interlock
(A25)
Bit Hex Dec Alarm Word Alarm Word Warning Word Warning Extended Extended
2 Word 2 Status Word Status Word 2
27 08000000 134217728 Brake IGBT reserved Voltage Limit (W64) reserved Unused Firemode Limit
(A27) Exceed
28 10000000 268435456 Option Change reserved Encoder loss (W90) reserved Unused FlyStart active
(A67)
29 20000000 536870912 Drive Encoder loss Output freq. lim. BackEMF Unused
Initialized(A80) (A90) (W62) too High
30 40000000 1073741824 Safe Stop (A68) PTC Safe Stop (W68) PTC Unused
Thermistor Thermist
(A74) or (W74)
31 80000000 2147483648 Mech. brake Dangerous Extended Status Protection Mode
low (A63) failure (A72) Word
Table 7.3 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for
diagnostics. See also 16-94 Ext. Status Word.
7 7
WARNING 1, 10 Volts low WARNING/ALARM 4, Mains phase loss
The control card voltage is below 10 V from terminal 50. A phase is missing on the supply side, or the line voltage
Remove some of the load from terminal 50, as the 10 V imbalance is too high. This message also appears for a
supply is overloaded. Max. 15 mA or minimum 590 Ω. fault in the input rectifier on the adjustable frequency
drive. Options are programmed at 14-12 Function at Mains
This condition can be caused by a short in a connected
Imbalance.
potentiometer or improper wiring of the potentiometer.
Troubleshooting
Troubleshooting
Check the supply voltage and supply currents to the
Remove the wiring from terminal 50. If the warning clears,
adjustable frequency drive.
the problem is with the customer wiring. If the warning
does not clear, replace the control card.
WARNING 5, DC link voltage high
WARNING/ALARM 2, Live zero error
The intermediate circuit voltage (DC) is higher than the
This warning or alarm only appears if programmed by the
high voltage warning limit. The limit is dependent on the
user in 6-01 Live Zero Timeout Function. The signal on one
adjustable frequency drive voltage rating. The unit is still
of the analog inputs is less than 50% of the minimum
active.
value programmed for that input. Broken wiring or faulty
device sending the signal can cause this condition. WARNING 6, DC link voltage low
The intermediate circuit voltage (DC) is lower than the low
Troubleshooting
voltage warning limit. The limit is dependent on the
Check connections on all the analog input
adjustable frequency drive voltage rating. The unit is still
terminals. Control card terminals 53 and 54 for
active.
signals, terminal 55 common. MCB 101 terminals
11 and 12 for signals, terminal 10 common. MCB WARNING/ALARM 7, DC overvoltage
109 terminals 1, 3, 5 for signals, terminals 2, 4, 6 If the intermediate circuit voltage exceeds the limit, the
common. frequency converter trips after a time.
Check that the adjustable frequency drive Troubleshooting
programming and switch settings match the Connect a brake resistor
analog signal type. Extend the ramp time
Perform Input Terminal Signal Test. Change the ramp type
Activate the functions in 2-10 Brake Function
WARNING/ALARM 3, No motor Increase 14-26 Trip Delay at Inverter Fault
No motor has been connected to the output of the
frequency converter. If the alarm/warning occurs during a power sag,
use kinetic back-up (14-10 Line Failure)
Compare the output current shown on the LCP WARNING/ALARM 12, Torque limit
with measured motor current. The torque has exceeded the value in 4-16 Torque Limit
Display the Thermal Drive Load on the LCP and Motor Mode or the value in 4-17 Torque Limit Generator
monitor the value. When running above the Mode. 14-25 Trip Delay at Torque Limit can change this from
adjustable frequency drive continuous current a warning only condition to a warning followed by an
rating, the counter increases. When running alarm.
below the adjustable frequency drive continuous Troubleshooting
current rating, the counter decreases. If the motor torque limit is exceeded during
WARNING/ALARM 10, Motor overload temperature ramp-up, extend the ramp-up time.
According to the electronic thermal protection (ETR), the If the generator torque limit is exceeded during
motor is too hot. Select whether the adjustable frequency ramp-down, extend the ramp-down time.
drive issues a warning or an alarm when the counter
If torque limit occurs while running, possibly
reaches 100% in 1-90 Motor Thermal Protection. The fault
increase the torque limit. Make sure that the
occurs when the motor runs with more than 100%
system can operate safely at a higher torque.
overload for too long.
Check the application for excessive current draw
Troubleshooting
on the motor.
Check for motor overheating.
WARNING/ALARM 13, Over current
Check if the motor is mechanically overloaded
The inverter peak current limit (approximately 200% of the
Check that the motor current set in 1-24 Motor rated current) is exceeded. The warning lasts about 1.5 s,
Current is correct. then the adjustable frequency drive trips and issues an
Ensure that Motor data in parameters 1-20 to alarm. This fault can be caused by shock loading or quick
1-25 are set correctly. acceleration with high inertia loads. It can also appear after
kinetic backup if the acceleration during ramp-up is quick.
If an external fan is in use, check in 1-91 Motor
If extended mechanical brake control is selected, trip can
External Fan that it is selected.
be reset externally.
Check the sensors on the heatsink and control Remove power from the adjustable frequency drive and
card. check motor phase U.
WARNING 25, Brake resistor short circuit ALARM 31, Motor phase V missing
The brake resistor is monitored during operation. If a short Motor phase V between the adjustable frequency drive
circuit occurs, the brake function is disabled and the and the motor is missing.
warning appears. The adjustable frequency drive is still Remove power from the adjustable frequency drive and
operational but without the brake function. Remove power check motor phase V.
to the adjustable frequency drive and replace the brake
resistor (see 2-15 Brake Check). ALARM 32, Motor phase W missing
Motor phase W between the adjustable frequency drive
WARNING/ALARM 26, Brake resistor power limit and the motor is missing.
The power transmitted to the brake resistor is calculated as
a mean value over the last 120 seconds of run time. The Remove power from the adjustable frequency drive and
calculation is based on the intermediate circuit voltage and check motor phase W.
the brake resistance value set in 2-16 AC Brake Max. ALARM 33, Inrush fault
Current. The warning is active when the dissipated braking Too many power-ups have occurred within a short time
7 7
energy is higher than 90% of the brake resistance power. If period. Let the unit cool to operating temperature.
[2] Trip is selected in 2-13 Brake Power Monitoring, the
WARNING/ALARM 34, Fieldbus communication fault
adjustable frequency drive trips when the dissipated
The serial communication bus on the communication
braking energy reaches 100%.
option card is not working.
WARNING/ALARM 27, Brake chopper fault
WARNING/ALARM 35, Option fault
The brake transistor is monitored during operation and if a
An option alarm is received. The alarm is option-specific.
short circuit occurs, the brake function is disabled and a
The most likely cause is a power-up or a communication
warning is issued. The adjustable frequency drive is still
fault.
operational but, since the brake transistor has short-
circuited, substantial power is transmitted to the brake WARNING/ALARM 36, Mains failure
resistor, even if it is inactive. This warning/alarm is only active if the supply voltage to
Remove power to the adjustable frequency drive and the adjustable frequency drive is lost and 14-10 Mains
remove the brake resistor. Failure is NOT set to [0] No Function. Check the fuses to the
adjustable frequency drive and line power supply to the
WARNING/ALARM 28, Brake check failed
unit.
The brake resistor is not connected or not working.
Check 2-15 Brake Check. ALARM 37, Phase imbalance
There is a current imbalance between the power units
ALARM 29, Heatsink temp
The maximum temperature of the heatsink has been ALARM 38, Internal fault
exceeded. The temperature fault will not reset until the When an internal fault occurs, a code number defined in
temperature falls below a defined heatsink temperature. Table 7.4 is displayed.
The trip and reset points are different based on the Troubleshooting
adjustable frequency drive power size. Cycle power
Troubleshooting Check that the option is properly installed
Check for the following conditions.
Check for loose or missing wiring
Ambient temperature too high.
It may be necessary to contact your Danfoss supplier or
Motor cable too long.
service department. Note the code number for further
Incorrect airflow clearance above and below the troubleshooting directions.
adjustable frequency drive.
Blocked airflow around the adjustable frequency No. Text
drive. 0 Serial port cannot be initialized. Contact your
Danfoss supplier or Danfoss Service Department.
Damaged heatsink fan.
256-258 Power EEPROM data is defective or too old.
Dirty heatsink. Replace power card.
ALARM 30, Motor phase U missing 512-519 Internal fault. Contact your Danfoss supplier or
Motor phase U between the adjustable frequency drive Danfoss Service Department.
and the motor is missing.
No. Text For X30/7, check the load connected to X30/7 or remove
783 Parameter value outside of min/max limits the short-circuit connection. Check 5-33 Term X30/7 Digi
1024-1284 Internal fault. Contact your Danfoss supplier or the Out (MCB 101).
Danfoss Service Department. ALARM 43, Ext. supply
1299 Option SW in slot A is too old MCB 113 Ext. Relay Option is mounted without ext. 24V
1300 Option SW in slot B is too old DC. Either connect an ext. 24V DC supply or specify that
1302 Option SW in slot C1 is too old no external supply is used via 14-80 Option Supplied by
1315 Option SW in slot A is not supported (not allowed) External 24VDC [0]. A change in 14-80 Option Supplied by
1316 Option SW in slot B is not supported (not allowed) External 24VDC requires a power cycle.
1318 Option SW in slot C1 is not supported (not ALARM 45, Earth fault 2
allowed) Ground fault on start-up.
1379-2819 Internal fault. Contact your Danfoss supplier or
Troubleshooting
Danfoss Service Department.
Check for proper grounding and loose
2561 Replace control card
connections.
2820 LCP stack overflow
Check for proper wire size.
7 7
2821 Serial port overflow
2822 USB port overflow Check motor cables for short-circuits or leakage
3072-5122 Parameter value is outside its limits currents.
5123 Option in slot A: Hardware incompatible with
ALARM 46, Power card supply
control board hardware
The supply on the power card is out of range.
5124 Option in slot B: Hardware incompatible with
control board hardware There are three power supplies generated by the switch
5125 Option in slot C0: Hardware incompatible with
mode power supply (SMPS) on the power card: 24 V, 5 V,
control board hardware ±18 V. When powered with 24 V DC with the MCB 107
option, only the 24 V and 5 V supplies are monitored.
5126 Option in slot C1: Hardware incompatible with
When powered with three phase AC line voltage, all three
control board hardware
supplies are monitored.
5376-6231 Internal fault. Contact your Danfoss supplier or
Danfoss Service Department. Troubleshooting
Check for a defective power card.
Table 7.4 Internal Fault Codes
Check for a defective control card.
ALARM 39, Heatsink sensor Check for a defective option card.
No feedback from the heatsink temperature sensor. If a 24 V DC power supply is used, verify proper
The signal from the IGBT thermal sensor is not available on supply power.
the power card. The problem could be on the power card, WARNING 47, 24 V supply low
on the gate drive card, or the ribbon cable between the The 24 V DC is measured on the control card. The external
power card and gate drive card. 24 V DC backup power supply may be overloaded,
WARNING 40, Overload of digital output terminal 27 otherwise contact the Danfoss supplier.
Check the load connected to terminal 27 or remove short- WARNING 48, 1.8 V supply low
circuit connection. Check 5-00 Digital I/O Mode and The 1.8 V DC supply used on the control card is outside of
5-01 Terminal 27 Mode. allowable limits. The power supply is measured on the
WARNING 41, Overload of digital output terminal 29 control card. Check for a defective control card. If an
Check the load connected to terminal 29 or remove short- option card is present, check for an overvoltage condition.
circuit connection. Check 5-00 Digital I/O Mode and WARNING 49, Speed limit
5-02 Terminal 29 Mode. When the speed is not within the specified range in
WARNING 42, Overload of digital output on X30/6 or 4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed
overload of digital output on X30/7 High Limit [RPM], the adjustable frequency drive shows a
For X30/6, check the load connected to X30/6 or remove warning. When the speed is below the specified limit in
the short-circuit connection. Check 5-32 Term X30/6 Digi 1-86 Trip Speed Low [RPM] (except when starting or
Out (MCB 101). stopping), the adjustable frequency drive will trip.
ALARM 50, AMA calibration failed higher output frequency. The warning will clear when the
Contact your Danfoss supplier or Danfoss Service output drops below the maximum limit.
Department. ALARM 63, Mechanical brake low
The actual motor current has not exceeded the “release
ALARM 51, AMA check Unom and Inom brake” current within the “Start delay” time window.
The settings for motor voltage, motor current and motor WARNING/ALARM 65, Control card over temperature
power are wrong. Check the settings in parameters 1-20 to The cut-out temperature of the control card is 176 °F [80
1-25.
°C].
ALARM 52, AMA low Inom
Troubleshooting
The motor current is too low. Check the settings.
• Check that the ambient operating temperature is
ALARM 53, AMA motor too big within limits.
The motor is too big for the AMA to operate.
• Check for clogged filters.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
• Check fan operation.
again (when the motor temperature reaches an acceptable ALARM 80, Drive initialized to default value
level) and when the Digital Input from the MCB 112 is Parameter settings are initialized to default settings after a
deactivated. When that happens, a reset signal must be is manual reset. Reset the unit to clear the alarm.
be sent (via Bus, Digital I/O, or by pressing [Reset]). ALARM 81, CSIV corrupt
ALARM 72, Dangerous failure CSIV file has syntax errors.
Safe Stop with Trip Lock. The Dangerous Failure Alarm is ALARM 82, CSIV parameter error
issued if the combination of safe stop commands is CSIV failed to init a parameter.
unexpected. This is the case if VLT PTC Thermistor Card
enables X44/10 but safe stop is somehow not enabled. ALARM 83, Illegal option combination
Furthermore, if the MCB 112 is the only device using safe The mounted options are not supported to work together.
stop (specified through selection [4] or [5] in 5-19 Terminal ALARM 84, No safety option
37 Safe Stop), an unexpected combination is activation of The safety option was removed without applying a general
safe stop without the X44/10 being activated. The reset. Reconnect the safety option.
following table summarizes the unexpected combinations
ALARM 88, Option detection
that lead to Alarm 72.
A change in the option layout has been detected. This
NOTICE!
Iif X44/10 is activated in selection 2 or 3, this signal is
alarm occurs when 14-89 Option Detection is set to [0]
Frozen configuration and the option layout for some reason 7 7
ignored. However, the MCB 112 will still be able to activate has changed. An option layout change has to be enabled
Safe Stop. in 14-89 Option Detection before the change is accepted. If
the change of configuration is not accepted, it is only
WARNING 73, Safe stop auto restart possible to reset Alarm 88 (Trip-lock) when the option
Safe stopped. With automatic restart enabled, the motor configuration has been re-established/corrected.
may start when the fault is cleared. WARNING 89, Mechanical brake sliding
ALARM 74, PTC Thermistor The hoist brake monitor has detected a motor speed > 10
Alarm related to the ATEX option. The PTC is not working. RPM.
WARNING 77, Reduced power mode WARNING/ALARM 104, Mixing fan fault
This warning indicates that the frequency converter is The fan monitor checks that the fan is spinning at power-
operating in reduced power mode (i.e. less than the up or whenever the mixing fan is turned on. If the fan is
allowed number of inverter sections). This warning is not operating, then the fault is annunciated. The mixing-
generated on power cycle when the frequency converter is fan fault can be configured as a warning or an alarm trip
set to run with fewer inverters, and remains on. by 14-53 Fan Monitor.
8 General Specifications
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within ±15% (tolerance relates to variety in voltage and
cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the
frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses.
(Though typical only 4 W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (±5%).
5) The three values for the max. cable cross section are for single core, flexible wire and flexible wire with sleeve, respectively.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within ±15% (tolerence relates to variety in voltage and
cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the
frequency converter and vice versa.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses.
(Though typical only 4 W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (±5%).
5) The three values for the max. cable cross section are for single core, flexible wire and flexible wire with sleeve, respectively.
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1. Terminals 27 and 29 can also be programmed as output.
2. Except safe stop input Terminal 37.
3. Terminal 37 can only be used as safe stop input.
Terminal 37 is suitable for category 3 installations according to EN 954-1 (safe stop according to category 0 EN 60204-1) as
required by the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in conformance with
EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use of the Safe Stop function follow the
related information and instructions in the Application Guidelines.
Analog Inputs
Number of analog inputs 2
Terminal number 53, 54
Modes Voltage or current
Mode select Switch S201 and switch S202
Voltage mode Switch S201/switch S202 = OFF (U)
Voltage level -10 to +10 V (scaleable)
Input resistance, Ri: approx 10 kΩ
Max. voltage ± 20 V
Current mode Switch S201/switch S202 = ON (I)
Current level 0/4 to 20 mA (scaleable)
Input resistance, Ri approx. 200 Ω
Max. current 30 mA
Resolution for analog inputs 10 bit (+ sign)
Accuracy of analog inputs
Bandwidth
Max. error 0.5% of full scale
100 Hz
8 8
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Digital Output
Programmable digital/pulse outputs 2
Terminal number 27, 291)
Voltage level at digital/frequency output 0-24 V
Max. output current (sink or source) 40 mA
Max. load at frequency output 1 kΩ
Max. capacitive load at frequency output 10 nF
Minimum output frequency at frequency output 0 Hz
Maximum output frequency at frequency output 32 kHz
Accuracy of frequency output Max. error: 0.1 % of full scale
Resolution of frequency outputs 12 bit
1)Terminal 27 and 29 can also be programmed as input. The digital output is galvanically isolated from the supply voltage
(PELV) and other high-voltage terminals.
Analog Output
Number of programmable analog outputs 1
Terminal number 42
Current range at analog output 0/4 to 20 mA
Max. load to common at analog output 500 Ω
Accuracy on analog output Max. error: 0.5 % of full scale
Resolution on analog output 12 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB
ground connection is not galvanically isolated from protection ground. Use only isolated laptop as PC connection to the
USB connector on the frequency converter drive
Relay Outputs
Programmable relay outputs 2
Relay 01 Terminal number 1-3 (break),1-2 (make)
Max. terminal load (AC-1)1) on 1-3 (NC), 1-2 (NO) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)1) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)1) on 1-2 (NO), 1-3 (NC) (Resistive load) 60 V DC, 1 A
Max. terminal load (DC-13)1) (Inductive load) 24 V DC, 0.1 A
Relay 02 (CDS 302 only) Terminal number 4-6 (break), 4-5 (make)
Max. terminal load (AC-1)1) on 4-5 (NO) (Resistive load) 400 V AC, 2 A
Max. terminal load (AC-15)1) on 4-5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)1) on 4-5 (NO) (Resistive load) 80 V DC, 2 A
Surroundings
Enclosure ≤ enclosure type A IP20, IP55
Enclosure ≥ enclosure type A, B IP21, IP55
Enclosure kit available ≤ enclosure type A IP21/TYPE 1/IP 4X top
Vibration test 1.0 g
Max. relative humidity 5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated class 3C2
Aggressive environment (IEC 721-3-3), coated class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature Max. 122 °F/50 °C
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation 32 °F/0 °C
Minimum ambient temperature at reduced performance 14 °F/-10 °C
Temperature during storage/transport -13 to 149 °F/-25 to +65/70 °C
Maximum altitude above sea level without derating 3280 ft/1000 m
Maximum altitude above sea level with derating 9842 ft/3000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2, 8 8
EMC standards, Immunity EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
8 8
Index
E
ETR......................................................................................................... 5-60
A
Access To Control Terminals........................................................... 2-8
Accessory Bag................................................................... 2-9, 2-10, 3-1 F
FC
Adjustable Warnings, 4-5*............................................................. 5-13
Port Diagnostics, 8-8*................................................................. 5-38
Alarm Messages................................................................................... 6-1 Port Settings, 8-3*........................................................................ 5-36
AMA............................................................................................... 6-8, 6-12 Feedback............................................................................................. 6-11
Ambient Temperature And Altitude............................................ 2-1 Fieldbus & FC Port, 16-8*............................................................... 5-63
Analog Fuses........................................................................................... 6-10, 2-15
Input......................................................................................... 5-26, 6-7
Inputs.................................................................................................. 7-5
Outputs.............................................................................................. 7-6 G
Signal.................................................................................................. 6-7 General
Settings, 8-0*................................................................................. 5-35
Status, 16-0*................................................................................... 5-59
B Graphical Display........................................................................ 4-1, 4-4
Braking................................................................................................. 6-10
Ground Leakage Current....................................................... 1-2, 2-14
Branch Circuit Protection............................................................... 2-15
C I
Input Terminal...................................................................................... 6-7
Cable
Entry.................................................................................................... 2-4 Inputs And Outputs......................................................................... 5-62
Lengths And Cross Sections....................................................... 7-4 Intermediate Circuit........................................................................... 1-2
Catch Up.............................................................................................. 5-18
Communication Option................................................................. 6-10
K
Comparators, 13-1*.......................................................................... 5-42 Keypad.................................................................................................... 1-2
Conductors............................................................................................ 2-7 Knockouts.............................................................................................. 2-4
Configuration..................................................................................... 5-35
Control L
Cables......................................................................... 2-11, 2-12, 2-10 LCP...................... 1-2, 3-1, 4-3, 4-4, 5-5, 5-6, 5-56, 5-68, 5-76, 5-79
Card............................................................ 5-55, 6-7, 5-55, 5-56, 7-6
Terminal............................................................................................. 7-4 Leakage Current............................................................... 2-7, 2-14, 1-2
Terminals........................................................................................... 4-3 Local Reference.................................................................................... 5-2
Ctrl. Word Settings, 8-1*................................................................. 5-36 Logic Rules, 13-4*............................................................................. 5-47
Current Rating...................................................................................... 6-8
M
D Mains
Data Readouts, 16-**....................................................................... 5-59 Connection For B1, B2 And B3................................................... 2-1
Connection For B4, C1 And C3................................................... 2-1
DC Link........................................................................................... 1-1, 6-7 Supply................................................. 1-2, 2-10, 4-3, 5-55, 7-1, 7-4
Decoupling Plate...................................................................... 2-7, 2-10 MCT 10.................................................................................................... 4-3
Default Settings............................................ 1-1, 4-3, 5-56, 2-9, 5-81 Mechanical
Diagnosis Read-Outs, 16-9*.......................................................... 5-63 Dimensions....................................................................................... 2-3
Mounting........................................................................................... 2-2
Digital
Input................................................ 5-16, 5-55, 5-72, 5-75, 6-8, 7-6
Inputs...................................................................... 4-3, 5-9, 5-20, 7-4
Output................................................................................... 5-16, 5-55
Outputs............................................................................................ 5-20
Digital/Bus, 8-5*................................................................................ 5-37
Motor
Compressor Cable.......................................................................... 2-7
Compressor Connection.............................................................. 2-6
V
Connection....................................................................................... 1-2 Voltage
Current.................................................... 5-20, 5-78, 5-79, 6-12, 5-5 Imbalance.......................................................................................... 6-7
Data.......................................................................................... 6-8, 6-12 Level................................................................................... 1-2, 7-4, 7-5
Limits, 4-1*...................................................................................... 5-13
Overload Protection...................................................................... 1-1
Power............................................................................................... 6-12 W
Status................................................................................................ 5-59 Warnings................................................................................................ 6-1
O
Operating Mode.................................................................................. 5-2
Output Current.................................................................................... 6-8
P
Phase Loss.............................................................................................. 6-7
Programming....................................................................................... 6-7
R
Ramp Up Time................................................................................... 5-10
Relay Outputs............................................................................ 5-20, 7-6
Reset............................................................................................. 6-8, 6-13
RS Flip Flops, 13-1*........................................................................... 5-45
S
Safe
Stop.................................................................................. 3-1, 2-10, 7-4
Torque Off......................................................................................... 1-2
Safety Instructions.............................................................................. 1-1
Screened/armored.......................................................... 2-7, 2-12, 7-4
Sequence Of Operation.................................................................... 0-2
Shielded/armoured............................................................... 2-10, 2-11
Short
Circuit.................................................................................................. 6-9
Circuit Protection......................................................................... 2-15
Speed Bypass, 4-6*........................................................................... 5-14
States, 13-5*........................................................................................ 5-52
Stripping................................................................................................. 2-9
Supply Voltage.................................................................................. 6-10
Surroundings........................................................................................ 7-7
T
Terminal 54......................................................................................... 6-13
Thermal Load..................................................................................... 5-60
Timers, 13-2*...................................................................................... 5-47