DN 62018
DN 62018
DN 62018
General
FSCO-951 and FSCO-951A are intelligent, addressable carbon
monoxide (CO) detectors with integral communication to provide
point location for alarm communication and selective maintenance.
These detectors have point ID capability that enables each detec-
tor address to be set with rotary address switches providing exact
device locations. The modern design and expanded color options
support contemporary aesthetic demands. In addition, each detec-
tor is constructed for exceptional installation and maintenance effi-
ciency.
The FSCO-951 incorporates carbon monoxide (CO) detection prin-
ciples meeting the UL 2075 standard for system-connected life
safety carbon monoxide detection. FSCO-951A meets Canadian
standard CAN/ULC-S588. As an addressable detector, additional
modules are not needed for point ID which streamlines the installa-
tion process. This allows you to upgrade your addressable fire sys-
tem to meet new CO code requirements in applications with fuel
burning equipment such as furnace areas and laundry rooms.
Released through the incomplete burning of various fuels, CO is a
colorless, odorless and deadly gas that is virtually impossible to FSCO-951 installed in B200S-WH sounder base
detect with the human senses. Because the potential exists for
dangerous levels of CO to accumulate in almost any building, leg-
islation mandating the use of CO detection in commercial spaces ELECTRICAL SPECIFICATIONS
continues to grow. Operating Voltage Range: 15 to 32 VDC
FSCO-951 is recommended for use in conjunction with B200S Operating Current @ 24 VDC: 200 uA (one communication every
series intelligent sounder bases. For Canadian applications, use 5 seconds with green LED blink on communication)
B200SCOA series with FSCO-951A. These bases can generate a Maximum Alarm Current: 2 mA @ 24 VDC (one communication
Temp 4 pattern for CO alarm indication. They recognize the Sys- every 5 seconds with red LED solid on)
tem Sensor synchronization protocol.
Maximum Current: 4.5 mA @ 24 VDC (one communication every
5 seconds with amber LED solid on)
Features and Benefits
Isolator Load Rating: 0.0063
• Intelligent CO detector
• Automatic drift compensation of CO cell SYSTEM COMPATIBILITY
• RealTest® CO testing capability Communication Protocol: FlashScan®
• UL 2075 listed NFS2-3030: Firmware v27.0 or higher
• Canadian standards CAN/ULC-S588 NFS2-640, NFS-320: Firmware v27.01 or higher
• Audible signal for CO alarm when used with a B200S/B200SCOA
series base CO MONITORING UL STANDARD REFERENCE:
• 10-year CO cell with end-of-life warning and fault ALARM THRESHOLDS
• New modern profile Parts Per Million Detector Response Time
• Expanded color options 70 ± 5ppm 60 – 240 min.
150 ± 5ppm 10 – 50 min.
Detector Specifications
400 ± 10ppm 4 – 15 min.
PHYSICAL SPECIFICATIONS
Per UL standard 2075, the FSCO-951(A) has been tested to the sensi-
Height: 2.7 in. (69 mm) installed in B200S series sounder base tivity limits defined in UL 2034/CSA 6.19-01.
Diameter: 6.875 in. (175 mm) installed in B200S series sounder
bases
Weight: 3.4 oz. (95 g)
Color: White
Operating Humidity Range: 15% to 90% Relative Humidity, Non-
condensing
Operating Temperature Range: 32°F to 122°F (0°C to 50°C)
203.484.7161
www.notifier.com Country of Origin: Mexico