Hpmont 3N
Hpmont 3N
Hpmont 3N
HD30/HD3N/HD50 Series
Simple Manual
Safety Information
A Danger Information which is Critical for Avoiding Safety Hazard
• Electrical installation must be performed by a qualified electrical
Danger engineer and maintained by a professionally trained and authorized
professional.
• The inverter should be installed on a flame-retardant object such as
metal, away from flammable and explosive objects.
• After the inverter is powered off for 10 minutes, confirm that the
internal charge indicator is off and the voltage between the power
terminals (+) and (-) is lower than 36V, only then can operate.
• After the external power emergency stop terminal is turned on, be
sure to confirm that its action is effective and reliable.
• The inverter has a leakage current greater than 3mA to the ground.
The specific value is determined by the use conditions. The inverter
and the motor must use two independent grounding wires to ensure
safety. It is also recommended that users install Type B leakage
protection devices (ELCB/RCD).
• Before starting the motor and mechanical equipment, please make
sure that the motor and mechanical equipment are working within
the allowable range.
• Please note that do not touch the inverter terminals when the inverter
is powered. Do not connect the power terminals of the inverter to the
product housing, and do not short-circuit the power terminals.
• When the operating environment exceeds 40℃ , the inverter needs to
be derated. For every 1℃ increase, it needs to be derated by 2%. The
Max. working environment temperature is 50℃ .
• When the altitude exceeds 1000 meters, derating is required.
A Warning Information which is Critical for Avoiding Damage to the
Product and other Device
Warning • Do not drop wires, screws, or drilling residue into the inverter during
installation work.
• The inverter has passed the withstand voltage test before leaving the
factory, so it can not be tested again.
• For products stored for more than 2 years, the power supply shall be
boosted slowly through the voltage regulator when power on.
• Please tighten the terminal reliably.
• Do not connect the input power line to the output U/V/W terminal.
• Do not connect the phase shift capacitor to the output loop.
• Switch the motor or perform variable frequency/power frequency
switching when the inverter stops outputting.
• Do not short-circuit the inverter DC bus terminals.
Product Model
Product model can be confirmed on the product packaging and on the product
nameplate.
HDXX-4T5P5G-X
Product Series Special Function
Configuration
Power Supply Voltage Product Type
2 = 200 - 240VAC G = General type
4 = 380 - 460VAC P = Special type for fan
6 = 500 - 690VAC blower/water pump
Motor Power
Input Phase
0P2 = 0.25kW
S = Single phase input
0P4 = 0.4kW
D = Single/three phase input
...
...
T = Three phase input
630 = 630kW
Keypad
Description
The layout and description of the keypad are shown below.
HD30/HD3N
HD09/HD09-S
HD07-S FWD REV ALM LO/RE LOCK
1 1
1
Hz A V RPM %
2 11 3 6
9 2 3 2 3
8 6 PRG
6 JOG
4 5 8 9 10
8 SHF ENT 9
7
4 5
7 4 RUN STOP 5
7
1 1
Hz A V RPM %
11
2 PRG
6 JOG 3 2 PRG
6 JOG 3
10 10
8 SHF ENT 9 8 SHF ENT 9
4 RUN STOP 5 4 RUN STOP 5
7 7
HD20 HD50
Key Description
1 Display LCD/LED display
Programming/exit key:
2 PRG
• Enter or exit key
Jog key:
3 JOG
• Jog start the inverter when keypad controls
Run key:
4 RUN
• Start the inverter when keypad controls
Stop/reset key:
5 STOP • Stop the inverter when keypad controls
• Reset fault when a fault is detected
6 Increase/decrease key:
• The parameter value
7 • The setting value of the parameter
Shift key:
8 • When selecting a parameter or setting value, cycle to
the right to select a 1-digit value
Enter/confirm key:
9 • Go to the sub menu
• Save the set value
Multi-function key:
10 - M
• Set specific functions by F00.12
The same as AI terminal function
11 Potentiometer
• Set specific functions by F16.00
Keypad
HD09/HD09-S
Non-removable.
HD07-S
Press the buckles of the keypad at
both ends at the same time, and
pull out to remove the keypad.
HD20/HD30/HD3N/HD50
PRG JOG
SHF ENT
RUN STOP
Installation
The keypad is parallel to the
inverter. Press down in the vertical
direction of the keypad until hear a
"click".
Note: Do not install the keypad from
other direction, otherwise it will
cause poor contact of the keypad.
Electrical Installation
Note:
1) Remove the shorting piece of terminals P1 and (+) when connecting a DC reactor.
2) R is the braking resistor.
3) When wiring for HD09/HD09-S, the teminal is GND, DO, AI, AO.
When wiring for HD07-S, the teminal is AO.
DC1)
reactor
R2) Brake unit R2)
P1 (+) BR (-)
MCCB
R L1 U
Power S L2 V M
input
T L3
HDXX W
PE
DO 3)
Digital input 1 Digital output
DI1
GND 3)
Digital input 2
DI2 DO1
Digital input 3 Digital output 1
DI3
CME
Digital input 4
DI4
DO2
Digital output 2
Digital input 5
DI5
COM
Digital input 6
DI6
R1C
COM/GND 3) R1B Relay output 1
R1A
+10
Analog input 1
AI/AI13) AO/AO13) Analog output 1
Analog input 2 AO2 Analog output 2
AI2
Analog input 3 GND
AI3
PGP PGP
A B+
Modbus
HD-PG1-OC
communication B B- B-
Z+
Keypad or master RJ45
computer Z- Z-
PE
• The bare metal part of the power terminal wiring must be wrapped
with insulating tape.
Danger • The control circuit and power circuit are basically insulated. Do not
touch the inverter after it is powered on.
• Make sure that the AC input voltage is consistent with the rated input
voltage of the inverter.
Warning • If the control circuit is connected to an external device with an
accessible port during power-on, an additional level of insulation
protection and isolation should be added to ensure that the original
voltage level of the external device is not changed.
• If the communication terminals of the control circuit are connected
to a PC, use an RS485/232 isolated converter that meets safety
requirements.
• Never connect control terminals other than relay terminals to AC 220V.
Electrical Installation
Power Terminal
See power terminal descriptions below.
Control Terminal
See control terminal layout below.
DI1 ● ● ● ● ● ● ●
DI2 ● ● ● ● ● ● ●
DI3 ● ● ● ● ● ● ●
DI4 ● ● 2) ● 2) ● ● ● ●
DI5 ● 2) ● ● ● ●
DI6 ● 2) ● 2) ● 2) ● 2)
DO/DO11) ● ● 2) ● 2) ● ● ● ●
DO2 ● 2)
● 2)
● 2)
● 2)
● 2)
AI/AI11) ● 3) ● 3) ● 3) ● ● ● ●
AI2 ● ● 3) ● 3) ● 3) ● 3)
AI3 ● 3)
1)
AO/AO1 ● ● ● ● 3) ● 3) ● 3) ● 3)
AO2 ● 3)
● 3)
● 3)
● 3)
RLY1 ● ● ● ● ● ● ●
+10V ● ● ● ● ● ● ●
-10V ●
RJ45 ● ● ● ● ● ●
A/B ● ●
Encoder ●
1): DO, AI, AO is for HD09/HD09-S, AO is for HD07-S, DO1, AI1, AO1 is for the rest
products.
2): The terminal can be selected as high-speed pulse input/output.
3): The terminal can be selected as input voltage/current. HD07-S is set through
F16.29, and other products are set through jumpers or DIP switches.
Encoder Card
HD50 products are equipped with HD-PG1-OC as standard. See terminal
descriptions below.
Terminal Description
PGP +12V power output
HD-PG1-OC
COM Power ground
A+, A- Encoder A+/A- signal
B+, B- Encoder B+/B- signal
Z+, Z- Encoder Z+/Z- signal
Function Parameters
Instruction:
For the description of each product terminal, see control terminal (electrical
installation) or remarks (function parameter).
Ref. Register
Function Remark
Code Address
Status Display Parameters
D00.08 Inverter rated current (A) 0x3308
D00.14 Setting frequency (Hz) 0x330E
D00.15 Given frequency (Hz) 0x330F
D00.16 Output frequency (Hz) 0x3310
D00.17 Setting speed (rpm) 0x3311
D00.18 Running speed (rpm) 0x3312
D00.20 Output voltage (V) 0x3314
D00.21 Output current (A) 0x3315
D00.22 Torque reference (%) 0x3316
D00.23 Output torque (%) 0x3317
D00.24 Output power (kW) 0x3318
D00.25 DC bus voltage (V) 0x3319
D00.27 AI1 input voltage (V) 0x331B HD09/HD09-S is AI
D00.29 AI2 input voltage (V) 0x331D
D00.31 AI3 input voltage (V) 0x331F
DI6 terminal pulse input frequency HD07-S is DI5
D00.35 0x3323
(Hz) HD09/HD09-S is DI4
HD07-S/HD09/
D00.36 AO1 output 0x3324
HD09-S is AO
D00.37 AO2 output 0x3325
DO2 high-speed output pulse
D00.38 0x3326 HD09/HD09-S is DO
frequency (Hz)
D00.39 Radiator temperature (℃ ) 0x3327 HD07-S none
D00.50 Input terminal status 0x3332
D00.51 Output terminal status 0x3333
Ref.
Function Setting Range Default Remark
Code
Basic Parameters
0: V/f control without PG Only
Motor control mode
F00.01 2: Vector control without PG 0 HD50
selection
5: PM with PG vector control has 5
Max. output
F00.06 50.00 - 400.00Hz 50.00Hz
frequency of inverter
Max. running
F00.08 0.00Hz - F00.06 50.00Hz
frequency
Min. running
F00.09 0.00Hz - F00.08 0.00Hz
frequency
0: Keypad setting
1: Terminal setting
2: SCI communication HD09/
setting HD20
Frequency setting
F00.10 3: Analog setting 0 don,t
channel selection
4: Terminal pulse setting have
6 - 9: AI1 - AI4 setting 6 - 10
10: Keypad potentiometer
setting
0: Keypad setting
Command setting 1: Terminal setting
F00.11 0
channel selection 2: SCI communication
setting
Starting frequency
F00.13 0.00Hz - Max. frequency 50.00Hz
digital setting
Jog operation
F00.15 frequency 0.00Hz - Max. frequency 5.00Hz
digital setting 1
Running direction 0: Same direction
F00.17 0
selection 1: Reverse direction
F01.00 User password 00000 - 65535 0
0: No operation
1: Restore factory
Function code parameters
parameter 2/3: The keypad storage
F01.02 initialization parameter 1/2 is copied to 0
(parameter control board and update
download) the current parameter
setting value
4: Clear the fault
Function Parameters
Ref.
Function Setting Range Default Remark
Code
0: No operation
Parameter copy to 1/2: The current parameter
F01.03 keypad (parameter setting value is copied 0
upload) to the keypad storage
parameter 1/2
F03.01 Acc. time 1 0.1 - 6000.0s Depend
on
F03.02 Dec. time 1 0.1 - 6000.0s model
Multi-segment
F06.00 -
frequency command F00.09 - Max. frequency 5.00Hz
F06.07
1-8
PID Parameter
0: Invalid
F04.00 PID control selection 0
1: Valid
0: Digital given
1: Analog given HD07-S
Given channel 2: Terminal pulse given doesn,t
F04.01 0
selection 3 - 6: AI1 - AI4 given have
7: Keypad potentiometer 3-7
given
0: Analog feedback
1: Terminal pulse feedback
HD07-S
2 - 5: AI1 - AI4 given
Feedback channel doesn,t
F04.02 6: Keypad potentiometer 0
selection have
given
2-7
7: Speed closed-loop
feedback
Quantitative digital
F04.03 -100.0 - +100.0% 0.0%
setting
Proportional gain
F04.04 0.0 - 500.0 50.0
(P1)
F04.05 Integration time (I1) 0.01 - 10.00s 1.00s
F04.07 Derivative time (D1) 0.00 - 10.00s 0.00s
Ref.
Function Setting Range Default Remark
Code
Digital and Analog I/O Terminal Parameters
0: Unused
1: Inverter is enabled
F15.00 DI1 terminal function 2, 3: FWD/REV function 2
13 - 16: Multi-segment
frequency terminal 1 - 4
20, 21: FWD/REV Jog 1
F15.01 DI2 terminal function command control input 3
(JOGF1/JOGR1)
43: Emergency stop
46: External reset (RST)
input
F15.02 - DI3 - DI6 terminal 53: Pulse frequency input
(HD07-S is DI5, HD09/ 0
F15.05 function
HD09-S is DI4, the rest is
DI6)
Terminal detection
F15.14 0 - 10000 2
filtering times
Bit0 - Bit8 corresponds to
DI1 - DI9
Terminal input
Bitx: DIy terminal input
F15.15 positive and negative 000
positive and negative logic
logic setting
0: Positive logic
1: Negative logic
0: Unused HD09/
DO1 terminal 2: Inverter running (RUN)
F15.18 2 HD09-S
function 9: Frequency level detection is DO
signal
DO2 terminal 11: Frequency arrival signal
F15.19 (FAR) 0
function
31: Inverter fault
38: High-speed pulse
F15.20 RLY1 relay function output (HD09/HD09-S is DO, 31
the rest is DO2)
F15.27 FAR detection width 0.00 - 100.00Hz 2.50Hz
HD07-S
is DI5
Max. input pulse
F16.17 0 - 50000Hz 10000Hz HD09/
frequency
HD09-S
is DI4
HD07-S/
AO1 terminal 0: Unused HD09/
F16.19 1: Output frequency (0 - 2
function HD09-S
Max. output frequency) is AO
2: Given frequency (0 - Max.
AO2 terminal output frequency)
F16.20 0
function 3: Motor RPM (0 - Max.
output frequency)
High-speed pulse 4: Output current (0 - twice
F16.21 motor’s rated current) 0
output function
HD09/
DO2 Max. output
F16.26 0.1 - 50.0kHz 10.0kHz HD09-S
pulse frequency
is DO
AI1 voltage current 0: Voltage input Only
F16.29 0
input selection 1: Current input HD07-S
Function Parameters
Ref.
Function Setting Range Default Remark
Code
Communication Parameters
0: 1-8-2 format, no parity,
RTU
1: 1-8-1 format, even parity,
RTU
F17.00 Data format 0
2: 1-8-1 format, odd parity,
RTU
6: 1-8-1 format, no parity,
RTU
0: 1200bps
1: 2400bps
2: 4800bps HD09/
3: 9600bps HD20
F17.01 Baud rate selection 4: 19200bps 3 does n,t
5: 38400bps have
6: 57600bps 6-8
7: 76800bps
8: 115200bps
F17.02 Local address 0 - 247 2
Ref.
Function
Code
Fault Parameters
F20.21 Fifth (latest) failure type
F20.22 Given frequency at the last fault
F20.23 Running frequency at the last fault
F20.24 Bus voltage at the last fault
F20.25 Output voltage at the last fault
F20.26 Output current at the last fault
F20.27 Input terminal status at the last fault
F20.28 Output terminal status at the last fault
F20.29 Interval at the last fault
F20.30 Fourth fault type
F20.31 Fourth fault interval
F20.32 Third fault type
F20.33 Third fault interval
F20.34 Second fault type
F20.35 Second fault interval
F20.36 First fault type
F20.37 First fault interval
F20.38 Last fault interval
Troubleshooting
Mode 1: Use the Keypad to Control Start and Stop and Set the
Running Frequency
1. Use the keypad to set the motor parameters and the parameters see the
table below.
3. When K1 turns on, the motor runs forward, and when K1 turns off, the
motor stops running.
When K2 turns on, the motor runs in reverse, and when K2 turns off, the
motor stops running.
When K1 and K2 turn on/off at the same time, the motor will stop running.
4. SCI communication modify the operating frequency (function code 0x06
write register 0x3201).
Note: For details of the Modbus communication protocol, please refer to the user
manual of each product.
Hpmont Group Company
Shenzhen Hpmont Technology Co., Ltd.
Add: Building 28, Wangjingkeng Industry Park, Xili Town, Nanshan District,
Shenzhen, China
Tel: +86 755-26791688
Fax: +86 755-26558128
Email: marketing@hpmont.com
HPMONT (Hong Kong) Co., Ltd.
Add: Room 709, 7/F, Silvercord Tower 1, 30 Canton Road, Tsim Sha Tsui,
-Kowloon. Hong Kong
Tel: +852 6607 2243
Email: info.hk@hpmont.com.hk
Mont Korea Co., Ltd.
Add: Ace pyungchon tower, #811, 361 Slimin-daero, Dongan-gu, Anyang-si,
Gyeonggi-Do, 14057
Tel: +82-31-345-8181
Email: info.kr@hpmont.com.hk
Hpmont (Malaysia) Sdn Bhd
Add: VO3-11-20, Lingkaran SV, Sunway Velocity, 55100 Kuala Lumpur
Tel: +603 9202 8812
Email: info.ma@hpmont.com.hk
Hpmont (Taiwan) Co., Ltd.
Add: 17F., No. 368-3, Sec. 2, Gaotie S. Rd., Zhongli Dist., Taoyuan City 320, Taiwan
Tel: +886 905 333 600
Email: info.tw@hpmont.com.hk
Hpmont (Turkey) Teknoloji Ltd. Sti.
Add: Floor 3, Building 20, Fil Yokuşu Street, Cevizli District, Maltepe/Istanbul
Tel: +90 533 261 38 76
Email: info.tr@hpmont.com.hk
www.hpmont.com