QSP520GF 650KVA Perkins Diesel Generator
QSP520GF 650KVA Perkins Diesel Generator
QSP520GF 650KVA Perkins Diesel Generator
ASSEMBLY
The engine and alternator are close coupled by means of an SAE flange.A full torsional analysis has been carried out to
guarantee no harmful vibration will occur.
Anti-vibration pads are affixed between engine alternator feet and the base frame.Thus ensuring complete vibration isolation of
the rotating assemblies and enabling the machine to be placed on an uneven surface without any detrimental effects.
For durability and corrosion resistance,all iron and steel surfaces of canopy fabrications have been treated for coating by grit
blast cleaning.Then covered by special three layers painting which provides an excellent corrosion resistant surface.
WARRANTY
YANGKE Company provides one-source responsibility for the generator set and accessories.Each YANGKE generating set has
been got through 2 hours Load test for running 0% ,25%,50%,75%,100% and 110% load,all protective devices and control function
are simulated and checked before dispatch.
Engine and Alternator are guaranteed for a period of 12 months from the date of commissioning or 18 months from shipping,
whichever occurs first.
Convenience for operation and maintenance, backed by YUCHAI global service network.
CRITERION
ISO8528, GB/T2820, ISO3046, BS4999, BS5514, BS5000
EN12601:2001, EN60034-22:1997, EN60204-1:2006
ISO9001:2000, ISO14001:2004, SGS
Specifications may change without notice. - 1/5 - http://www.cndgss.com
ENGINE SPECIFICATION
UK Perkins Benefits
Power to Meet your needs: Hitting the key power nodes,
provide a clean & cost effective power solution.
State of Art Design: Common-rail fuel system, high power
density, low exhaust emissions with the minimum of heat
rejection and excellent fuel economy.
World-class Product Support: Network of 4000 distributors
and service outlets, easy specify & order part online guides
and service tools.
Long-term Power Solution: Designed to fully comply with
EU Stage emissions regulations, providing an emissions
compliant power solution for the future.
ENGINE BASIC DATA EXHAUST SYSTEM
NO. of Cylinder & type Vertical 6 in line Max.back of pressure (kPa) 6.9
Air intake way Turbocharged, Air to Air Diameter of exhaust pipe (mm) 202
Bore*Stroke(mm) 145183 FUEL SYSTEM
Cubic Capacity (L) 18.13 Type of Injection MEUI
BMPE(kpa) 2197 Injection pressure 200MPa
Compression ratio 14.5:1 Fuel atomizer MEUI
Rated speed(RPM) 1500 Feed pump operation pressure 600kPa
Rated power 565KW /706KVA Tolerance on fuel consumption N/A
Gross power 609KW/761KVA Maximum suction head 3m
Piston speed(m/s) 9 Maximum pressure head 4m
Engine Coolant flow(L/s) 6.1 Governor type of pump Electrical
Air intake flow(L/s) 40 CONSUMPTION
Exhaust flow(L/s) 110 110% (L/h) 440kw/550kva 141
Exhaust temperature () 550 100% (L/h) 400kw/500kva 127
Overall thermal efficiency 40% 75% (L/h) 300kw/375kva 95
LUBRICANTION SYSTEM 50% (L/h) 200kw/250kva 66
Maximum sump capacity 45 25% (L/h) 100kw/125kva 32
Minimum sump capacity 53 COOLING SYSTEM
Total system oil capacity(L) 62 Coolant capacity (L) 62
Normal oil temperature 113 Max. external system resistance 103
Oil pressure at bearings (kPa) 420 Thermostat operation range () 88-98
INDUCTION AIR SYSTEM ELECTRIC SYSTEM
Max. air intake restriction (paper element filter) Alternator 70amp
Clean filter (kPa) 3.7 Starter 9kw
Dirty filter (kPa) 6.35
Reliable performance
Voltage regulation Frequency/Speed undulation
Voltage regulation maintained with in 0.5% as follow: 0-100% load, Frequency/Speed Droop Ratio <5%.
Power factor between 0.8-1.0 lagging. 25-100% load, any steady load undulation <0.25%.
From no load to full load,any steady load. Effect factor of telecom
Speed droop variation under 5%. TIF(MAMG1-22)<50; THF(BS EN60034) < 2%
Brand LEROY SOMER YANGKE Alternators meet the requirement of BSEN 60034
Alternator Model LSA49.1 S4 QSW-520-4 and the relevant section of other international
Frequency and Speed 50Hz/1500rpm 50Hz/1500rpm standards such as BS5000, VDE0530, NEMA MG1-
Voltage(V) 400/230 400/230 32,IEC34,CSA22.2-100,As1359,and other standards
Prime Capacity(KVA) 660 650 and certifications can be considered on request.
The2/3 pitch design avoids excessive neutral
Prime Power(KW) 528 520
currents.With the 2/3 pitch and carefully selected
Power Efficiency(%) 93.9 95
pole and tooth designs,ensures very low waveform
Input Power(KW) 541 538
distortion.
Voltage Regulation 0.5% 0.5%
Brushless alternator with brushless pilot exciter for
Voltage regulator AVR AVR excellent load response.Class H insulation, easy
Rated Power Factor 0.8 0.8 paralleling with mains or other generators, standard
Stator Winding 2/3 2/3 2/3 pitch stator windings avoid excessive neutral
Sustained Short Circuit 300%(3IN): 10S 2900Amps currents.
Maximum Overspeed 2250min-1 2250min-1
Functions:
Automatic Start/Stop
3 start attempts failure and Automatic Crank Disconnect DSE5220
Parameters display(V/A/Hz/Hour)
Engine monitoring and protection
Charge alternator exciting and Charge alternator fail alarm
Warning:
Running hour counting
Settings can be adjustable via key buttons on front panel Alternator Under/Over Voltage
Alternator Under/Over Frequency
Shutdown:
Mains Under/Over Voltage
Loss of Speed Signal Mains Under/Over Frequency
Alternator Under/Over Voltage Under/Over Speed
Alternator Under/Over Frequency
Low Oil Pressure Pres-Alarm
Mains Under/Over Voltage
High Engine Temp. Pres-Alarm
Mains Under/Over Frequency
Under/Over Speed High/Low Battery Voltage
Low Oil Pressure Over-current
High Engine Temperature Periodic maintenance
Control Power-control