KFD2-STV3-Ex1-1: SMART Transmitter Power Supplies
KFD2-STV3-Ex1-1: SMART Transmitter Power Supplies
KFD2-STV3-Ex1-1: SMART Transmitter Power Supplies
Connection
Hazardous area
Input EEx ia IIC
SMART transmitter
• 1-channel
• Input EEx ia IIC; U0 = 28V SMART communicator
• 24 V DC nominal supply voltage
3- 1+
• SMART capable up to 40 kHz (-1dB)
• EMC acc. to NAMUR NE 21
Output 1 V ... 5 V 3- 1+
KFD2-STV3-Ex1-1
Function
Safe area
SMART transmitter power supplies
provide SMART transmitters with power
in hazardous areas and transfer the
4 mA ... 20 mA analogue values to KFD2-STV3-Ex1-1
only
output terminals 9+ and 10-.
Digital signals may be superimposed on
the analogue values in the hazardous - +
or safe area, which may be transferred
bidirectionally. 12 11+ 9+ 10- 7+ 8-
Handheld terminals should be Output Power Power Rail
connected as shown in the circuit block supply
diagram. A series circuit, i. e. for the SMART communicator
Bailey STT01, is also possible.
SMART transmitter power supplies are SMART communicator
delivered standard with terminals KF-
STP-BU and KF-STP-GN. Jacks are
integrated in these terminals for the
connection of the handheld units.
Composition
Application
• The supply of power to SMART
transmitters and the transfer of the
measurement current to the output
• suited for the following SMART
systems:
ABB, Bailey, Chessel,
Eckhardt-Foxboro,
Endress+Hauser, Fuji, Emerson,
Smar, Siemens, VEGA, Yokogawa
Release date 2006-05-31 10:25 Date of issue 2006-06-01 071831_ENG.xml
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 1
Technical data KFD2-STV3-Ex1-1
Supply
Connection Power Rail or terminals 7+, 8-
Rated voltage 20 ... 35 V DC
Ripple within the supply tolerance
Power loss 1.3 W
Power consumption ≤ 1.7 W
Input
Connection terminals 1+, 3-
Input signal 4 ... 20 mA
Available voltage approx. 16.5 V at 20 mA
Output
Connection terminals 9+, 10-, 11+
Output signal 1 ... 5 V , internal resistance approx. 305 Ω
Ripple
Transfer characteristics
Deviation ≤ 0.03 % of output signal range (voltage output)
≤ 0.05 % of output signal range (current output)
Influence of ambient temperature ≤ 20 p.p.m. / K
Frequency range hazardous area to safe area: bandwidth with 1 mAss signal 0 ... 40 kHz (-1 dB);
0 ... 100 kHz (-6 dB)
safe area to hazardous area: bandwidth with 1 Vss-signal 0 ... 40 kHz (-1 dB);
0 ... 100 kHz (-6 dB)
Rise time 10 µs
De-energized delay 10 µs
Electrical isolation
Input/output safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Output/power supply basic insulation acc. to DIN EN 50178, rated insulation voltage of AC 50 V
Directive conformity
Electromagnetic compatibility standards
Directive 89/336/EC EN 61326, EN 50081-2, NE 21
Standard conformity
Climatic conditions acc. to DIN IEC 721
Ambient conditions
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Mechanical specifications
Protection degree IP20
Mass approx. 150 g
Data for application in conjunction
with hazardous areas
Certificate of conformity BASEEFA No. Ex-89C2093 ; for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection [EEx ia] IIC (Tamb = 60 °C)
Voltage Uo 28 V DC
Current Io 93 mA
Power Po 660 mW
Internal capacitance Ci negligibly small
Internal inductance Li negligibly small
Release date 2006-05-31 10:25 Date of issue 2006-06-01 071831_ENG.xml
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 2
Technical data KFD2-STV3-Ex1-1
Safety parameter
UL control drawing E 106378
CSA control drawing LR 65756-13
Control drawing No. 116-0132
Connection terminals 1, 3
Input I
Safety parameter 28 V / 300 Ohm
Voltage VOC 28 V
Current ISC 93 mA
Explosion group A&B C&E D, F&G
Max. external capacitance Ca 0.14 µF 0.42 µF 1.14 µF
Max. external inductance La 3.1 mH 16.7 mH 34 mH
Supplementary information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity and instructions have to be observed. For
information see www.pepperl-fuchs.com.
Note
For test purposes or for commissioning the input of the transmitter power supply can be short-circuited for a short period. The
permissible duration of the short-circuit equals a maximum of 6 hours.
Accessories
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 3