Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

KFD2-STV3-Ex1-1: SMART Transmitter Power Supplies

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

SMART transmitter power supplies KFD2-STV3-Ex1-1

Connection

Hazardous area
Input EEx ia IIC

SMART transmitter
• 1-channel
• Input EEx ia IIC; U0 = 28V SMART communicator
• 24 V DC nominal supply voltage
3- 1+
• SMART capable up to 40 kHz (-1dB)
• EMC acc. to NAMUR NE 21
Output 1 V ... 5 V 3- 1+

KFD2-STV3-Ex1-1

Function

Safe area
SMART transmitter power supplies
provide SMART transmitters with power
in hazardous areas and transfer the
4 mA ... 20 mA analogue values to KFD2-STV3-Ex1-1
only
output terminals 9+ and 10-.
Digital signals may be superimposed on
the analogue values in the hazardous - +
or safe area, which may be transferred
bidirectionally. 12 11+ 9+ 10- 7+ 8-
Handheld terminals should be Output Power Power Rail
connected as shown in the circuit block supply
diagram. A series circuit, i. e. for the SMART communicator
Bailey STT01, is also possible.
SMART transmitter power supplies are SMART communicator
delivered standard with terminals KF-
STP-BU and KF-STP-GN. Jacks are
integrated in these terminals for the
connection of the handheld units.
Composition
Application
• The supply of power to SMART
transmitters and the transfer of the
measurement current to the output
• suited for the following SMART
systems:
ABB, Bailey, Chessel,
Eckhardt-Foxboro,
Endress+Hauser, Fuji, Emerson,
Smar, Siemens, VEGA, Yokogawa
Release date 2006-05-31 10:25 Date of issue 2006-06-01 071831_ENG.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 1
Technical data KFD2-STV3-Ex1-1

Supply
Connection Power Rail or terminals 7+, 8-
Rated voltage 20 ... 35 V DC
Ripple within the supply tolerance
Power loss 1.3 W
Power consumption ≤ 1.7 W
Input
Connection terminals 1+, 3-
Input signal 4 ... 20 mA
Available voltage approx. 16.5 V at 20 mA
Output
Connection terminals 9+, 10-, 11+
Output signal 1 ... 5 V , internal resistance approx. 305 Ω
Ripple
Transfer characteristics
Deviation ≤ 0.03 % of output signal range (voltage output)
≤ 0.05 % of output signal range (current output)
Influence of ambient temperature ≤ 20 p.p.m. / K
Frequency range hazardous area to safe area: bandwidth with 1 mAss signal 0 ... 40 kHz (-1 dB);
0 ... 100 kHz (-6 dB)
safe area to hazardous area: bandwidth with 1 Vss-signal 0 ... 40 kHz (-1 dB);
0 ... 100 kHz (-6 dB)
Rise time 10 µs
De-energized delay 10 µs
Electrical isolation
Input/output safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Output/power supply basic insulation acc. to DIN EN 50178, rated insulation voltage of AC 50 V
Directive conformity
Electromagnetic compatibility standards
Directive 89/336/EC EN 61326, EN 50081-2, NE 21
Standard conformity
Climatic conditions acc. to DIN IEC 721
Ambient conditions
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Mechanical specifications
Protection degree IP20
Mass approx. 150 g
Data for application in conjunction
with hazardous areas
Certificate of conformity BASEEFA No. Ex-89C2093 ; for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection [EEx ia] IIC (Tamb = 60 °C)
Voltage Uo 28 V DC
Current Io 93 mA
Power Po 660 mW
Internal capacitance Ci negligibly small
Internal inductance Li negligibly small
Release date 2006-05-31 10:25 Date of issue 2006-06-01 071831_ENG.xml

Type of protection [EEx ia]


Explosion group IIA IIB IIC
External capacitance 1.04 µF 0.39 µF 0.13 µF
External inductance 33.6 mH 12.6 mH 4.2 mH
Electrical isolation
Input/output safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Entity parameter
Certification number 4Z6A5.AX
FM control drawing No. 116-0129
Suitable for installation in division 2 yes
Connection terminals 1, 3
Input I
Voltage VOC 28 V
Current It 93 mA
Explosion group A&B C&E D, F&G
Max. external capacitance Ca 0.14 µF 0.43 µF 1.14 µF
Max. external inductance La 4.18 mH 16.83 mH 34.21 mH

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 2
Technical data KFD2-STV3-Ex1-1

Safety parameter
UL control drawing E 106378
CSA control drawing LR 65756-13
Control drawing No. 116-0132
Connection terminals 1, 3
Input I
Safety parameter 28 V / 300 Ohm
Voltage VOC 28 V
Current ISC 93 mA
Explosion group A&B C&E D, F&G
Max. external capacitance Ca 0.14 µF 0.42 µF 1.14 µF
Max. external inductance La 3.1 mH 16.7 mH 34 mH

Supplementary information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity and instructions have to be observed. For
information see www.pepperl-fuchs.com.

Note

For test purposes or for commissioning the input of the transmitter power supply can be short-circuited for a short period. The
permissible duration of the short-circuit equals a maximum of 6 hours.

Accessories

Power Rail PR-03


Power Rail UPR-03
Power feed module KFD2-EB2...
Using Power Rail PR-03 or UPR-03 the devices are supplied with 24 V DC by means of the power feed modules. If no Power
Rails are used, power supply of the individual devices is possible directly via their device terminals.
Each power feed module is used for fusing and monitoring groups with up to 100 individual devices. The Power Rail PR-03 is
an inset component for the DIN rail. The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium
profile rail 35 mm x 15 mm x 2000 mm. To make electrical contact, the devices are simply engaged.
The Power Rail must not be fed via the device terminals of the individual devices!
Release date 2006-05-31 10:25 Date of issue 2006-06-01 071831_ENG.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 3