Third Floor Beam Design Calculation
Third Floor Beam Design Calculation
Third Floor Beam Design Calculation
Group : G1
Beam No : B1
Analysis Reference (Member) 6.6m : 78
Beam Length : 3500 mm
Breadth (B) : 250 mm
Depth (D) : 300 mm
Effective Depth (d) : 265 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (f'c) : C21 N/sqmm
Grade Of Steel : Fy230 N/sqmm
Clear Cover (Cmin) : 25 mm
Es : 2x10^5 N/sqmm
Mubal : 93.37 kNm
As,min (flex) (B) : 403.26 sqmm
As,nominal (Bn) : 86.12 sqmm
As,min(user input)(B') : 86.12 sqmm
Ast = Max {B, C+D, A+D} (for Mu > 0 and C x 1.33 > B)
Ast = Max{B', C x 1.33 + D, A+D} (for Mu > 0 and C x 1.33 < B)
Ast = Bn (for Mu = 0)
Where,
Compression reinforcement required for
A = Asc (flex) =
bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement
C = As (flex) =
calculated at a given section
Distributed longitudinal torsional
D = Al (Dist) =
reinforcement at section considered
Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B +
Ast (Dist) (sqmm) =
2D))
Basic
Spc1 =d/2 = 132 mm
Spc2 = 300 mm
Skin reinforcement