33 11 KV Substation Training Report
33 11 KV Substation Training Report
33 11 KV Substation Training Report
TRAINING
REPORT ON
A
training Report Submitted In Partial Fulfillment of the
Requirements for the award of Degree of
ACKNOWLEDGEMENT i
LIST OF FIGURES ii
1. Introduction 1-2
4. Substation 7-13
5.1.1 Applications 14
7. Insulators 20-25
8.1 Relay 26
9.2 Fuse 31
9.3 Bus coupler 31
References 35
ACKNOWLEDGEMENT
Training has an important role in exposing the real-life situation in an industry. It was a
great experience for me to work on training at UTTAR PRADESH POWER COOPERATION
LIMITED through which I could learn how to work in a professional environment.
Now, I would like to thank the people who guided me and have been a constant source of
inspiration throughout the tenure of my summer training.
I am sincerely grateful to MR. Satyarth Gangwar (Sub Divisional Officer) at 33/11
KV substation, MAHANAGAR COLONY who rendered me his valuable assistance, constant
encouragement and able guidance which made this training actually possible.
I wish my deep sense of gratitude to MR. Govind Chauhan(Junior Engineer) whose
affectionate guidance has enabled me to complete this training successfully. I also wish my deep
sense of gratitude to MR. DESH DEEPAK SHARMA (HOD: EE Department) and my
project guide MR./MRS. ______________ and other faculty members whose guidance and
encouragement made my training successful.
APOORV SAXENA
List of figures
1. INTRODUCTION
The creation of Uttar Pradesh Power Corporation Ltd. (UPPCL) on January 14,
2000 is the result of power sector reforms and restructuring in UP (India) which is the focal point
of the Power Sector, responsible for planning and managing the sector through its transmission,
distribution and supply of electricity.
UPPCL will be professionally managed utility supplying reliable and cost-efficient
electricity to every citizen of the state through highly motivated employees and state of art
technologies, providing an economic return to our owners and maintaining leadership in the
country.
We shall achieve this being a dynamic, forward looking, reliable, safe and trustworthy
organization, sensitive to our customers interests, profitable and sustainable in the long run,
providing uninterrupted supply of quality power, with transparency and integrity in operation
1.1 ABOUT 33/11KV SUBSTATION MAHANAGAR
2. TRANSFORMERS
a) Current transformer
b) Potential transformer
2.1.3 AUTO TRANSFORMER:
3.1 Standard: IS-2785 3.2 Highest System Voltage: 145 KV 3.3 Frequency: 50Hz
3.4 C.T. Current: 25 KA/1Sec.
3.5 Rated primary current: 800 Ampere
4. SUBSTATIONS
Figure 4.1 View of substation
The present-day electrical power system is A.C. i.e. electrical power is generated,
transmitted & distributed in the form of the alternating current. The electric power is produced at
power plant stations which are located at favorable places generally quite away from the
consumers. It is delivered to the consumers through a large network of transmission 7
distribution.
At many places in the power system, it may be desirable and necessary to change some
characteristics e.g. voltage, ac to dc, frequency, power factor etc. of electric supply. This
accomplished by suitable apparatus called substation. For example; generation voltage (11 KV or
33 KV) at the power station is set up to high voltage (say 220 KV or 132 KV) for transmission of
electric power. The assembly of apparatus (e.g. transformer etc.) used for this purpose in the
substation. Similarly, near the consumer’s localities, the voltage may have to be step down to
utilization level. This job is again accomplished by suitable apparatus called substation.
The assembly of apparatus to change some characteristic of electric power supply is
called substation.
The two most ways to classify substation are:-
4.2.1 Each circuit is protected by its own circuit breaker and hence plant outage does not
necessarily result in loss of supply.
4.2.2 A fault on the feeder or transformer circuit breaker causes loss of the transformer
and feeder circuit, one of which may be restored after isolating the faulty circuit
breaker.
4.2.3 A fault on the bus section circuit breaker causes complete shutdown of the
substation. All circuits may be restored after isolating the faulty circuit breaker.
4.2.4 Maintenance of a feeder or transformer circuit breaker involves loss of the circuit.
4.2.5 Introduction of bypass isolators between bus bar and circuit isolator allows circuit
breaker maintenance facilities without loss of that circuit.
The First Step in designing a Substation is to design an Earthing and Bonding System.
Calculations for earth impedances, touch and step potentials are based on site
measurements of ground resistivity and system fault levels. A grid layout with particular
conductors is then analyzed to determine the effective substation earthing resistance, from which
the earthing voltage is calculated.
In practice, it is normal to take the highest fault level for substation earth grid calculation
purposes. Additionally, it is necessary to ensure a sufficient margin such that expansion of the
system is catered for.
To determine the earth resistivity, probe tests are carried out on the site. These tests are
best performed in dry weather such that conservative resistivity readings are obtained.
4.3.3.4 Conductors:
Bare copper conductor is usually used for the substation earthing grid. The copper bars
themselves usually have a cross-sectional area of 95 square millimeters, and they are laid at a
shallow depth of 0.25-0.5m, in 3-7m squares. In addition to the buried potential earth grid, a
separate above ground earthing ring is usually provided, to which all metallic substation plant is
bonded.
4.3.3.4 Connections:
Connections to the grid and other earthing joints should not be soldered because the heat
generated during fault conditions could cause a soldered joint to fail. Joints are usually bolted.
The switchyard fence earthing practices are possible and are used by different
utilities. These are:
4.3.4.1 Extend the substation earth grid 0.5m-1.5m beyond the fence perimeter. The fence
is then bonded to the grid at regular intervals.
4.3.4.2 Place the fence beyond the perimeter of the switchyard earthing grid and bond the
fence to its own earthing rod system. This earthing rod system is not coupled to the
main substation earthing grid.
4.4.1 Should be capable of carrying the specified load currents and short time currents.
4.4.2 Should be able to withstand forces on it due to its situation. These forces comprise self
weight, and weight of other conductors and equipment, short circuit forces and
atmospheric forces such as wind and ice loading.
4.4.3 Should be corona free at rated voltage.
4.4.4 Should have the minimum number of joints.
4.4.5 Should need the minimum number of supporting insulators.
4.4.6 Should be economical.
The most suitable material for the conductor system is copper or aluminums. Steel may
be used but has limitations of poor conductivity and high susceptibility to corrosion.
In an effort to make the conductor ideal, three different types have been utilized, and
these include: Flat surfaced Conductors, Stranded Conductors, and Tubular Conductors
The choice is influenced by the height of towers and the proximity to the substation. The
following clearances should be observed:
VOLTAGE MINIMUM GROUND CLEARANCE
LEVEL
less than 11kV 6.1m
Introduction:
Figure 5.1: PLCC (POWER LINE CARRIER COMMUNICATION)
Reliable & fast communication is necessary for safe efficient & economic power supply.
To reduce the power failure in extent & time, to maintain the interconnected grid system in
optimum working condition; to coordinate the operation of various generating unit
communication network is indispensable for state electricity board.
In state electricity boards, the generating & distribution stations are generally located at a
far distance from cities. Where P & T communication provided through long overhead lines in
neither reliable nor quick.
As we have available very reliable physical paths viz. the power lines, which
interconnected, hence power line carrier communication is found to be most economical and
reliable for electricity boards.
5.1.1 APPLICATIONS:
The PLCC can be used for the following facilities:
5.1.1.1 Telephony
5.1.1.2 Teleprotection
5.1.1.3 Remote control or indication
5.1.1.4 Telemetry
5.1.1.5 Teleprinting
When numbers of generators or feeders operating at the same voltage have to be directly
connected electrically, bus bar is used as the common electrical component. Bus bars are made
up of copper rods operate at constant voltage. The following are the important bus bars
arrangements used at substations:
6.1 Single bus bar system
6.2 Single bus bar system with section alisation.
6.3 Duplicate bus bar system
In large stations it is important that break downs and maintenance should interfere as little
as possible with continuity of supply to achieve this, duplicate bus bar system is used. Such a
system consists of two bus bars, a main bus bar and a spare bus bar with the help of bus coupler,
which consist of the circuit breaker and isolator.
In substations, it is often desired to disconnect a part of the system for general maintenance and
repairs. An isolating switch or isolator accomplishes this. Isolator operates under no load
condition. It does not have any specified current breaking capacity or current making capacity. In
some cases isolators are used to breaking charging currents or transmission lines.
While opening a circuit, the circuit breaker is opened first then isolator while closing a
circuit the isolator is closed first, then circuit breakers. Isolators are necessary on supply side of
circuit breakers, in order to ensure isolation of the circuit breaker from live parts for the purpose
of maintenance.
A transfer isolator is used to transfer main supply from main bus to transfer bus by using
bus coupler (combination of a circuit breaker with two isolators), if repairing or maintenance of
any section is required.
7. INSULATORS
The insulator serves two purposes. They support the conductors (bus bar) and confine the
current to the conductors. The most common used material for the manufacture of insulator is
porcelain. There are several types of insulators (e.g. pin type, suspension type, post insulator etc.)
and their use in substation will depend upon the service requirement. For example, post insulator
is used for bus bars. A post insulator consists of a porcelain body, cast iron cap and flanged cast
iron base. The hole in the cap is threaded so that bus bars can be directly bolted to the cap.
With the advantage of power system, the lines and other equipment operate at very high
voltage and carry high current.
The arrangements of switching along with switches cannot serve the desired function of
switchgear in such high capacity circuits. This necessitates employing a more dependable means
of control such as is obtain by the use of the circuit breakers. A circuit breaker can make or break
a circuit either manually or automatically under all condition as no load, full load and short
circuit condition.
A circuit breaker essentially consists of fixed and moving contacts. These contacts can be
opened manually or by remote control whenever desired. When a fault occurs on any part of the
system, the trip coils of breaker get energized and the moving contacts are pulled apart by some
mechanism, thus opening the circuit.
When contacts of a circuit breaker are separated, an arc is struck; the current is thus able
to continue. The production of arcs are not only delays the current interruption, but is also
generates the heat. Therefore, the main problem is to distinguish the arc within the shortest
possible time so that it may not reach a dangerous value. The general way of classification is on
the basis of the medium used for arc extinction.
Note: SF6 and Vacuum circuit breaker are being used in 33KV distribution substation.
Fast operations, suitability for repeated operation, auto reclosure, unit type multi break
constructions, simple assembly, modest maintenance are some of the main features of air blast
circuit breakers. A compressors plant necessary to maintain high air pressure in the air receiver.
The air blast circuit breakers are especially suitable for railways and arc furnaces, where the
breaker operates repeatedly. Air blast circuit breakers is used for interconnected lines and
important lines where rapid operation is desired.
Figure 7.4 Air blast circuit breaker
High pressure air at a pressure between 20 to 30 kg/ cm2 stored in the air reservoir. Air is
taken from the compressed air system. Three hollow insulator columns are mounted on the
reservoir with valves at their basis. The double arc extinguished chambers are mounted on the
top of the hollow insulator chambers. The current carrying parts connect the three arc extinction
chambers to each other in series and the pole to the neighboring equipment. Since there exists a
very high voltage between the conductor and the air reservoir, the entire arc extinction chambers
assembly is mounted on insulators.
In such circuit breaker, sulphar hexafluoride (SF6) gas is used as the arc quenching
medium. The SF6 is an electronegative gas and has a strong tendency to absorb free electrons.
The SF6 circuit breaker have been found to a very effective for high power and high voltage
service. SF6 circuit breakers have been developed for voltage 115 KV to 230 KV, power rating
10 MVA.
It consists of fixed and moving contacts. It has chamber, contains SF6 gas. When the
contacts are opened, the mechanism permits a high pressure SF 6 gas from reservoir to flow
towards the arc interruption chamber. The moving contact permits the SF 6 gas to let through
these holes.
Vacuum circuit breakers are circuit breakers which are used to protect medium and high
voltage circuits from dangerous electrical situations. Like other types of circuit breakers, vacuum
circuit breakers literally break the circuit so that energy cannot continue flowing through it,
thereby preventing fires, power surges, and other problems which may emerge. These devices
have been utilized since the 1920s, and several companies have introduced refinements to make
them even safer and more effective.
8.1 RELAY:
This type of relay works when current in the circuit exceeds the predetermined value. The
actuating source is the current in the circuit supplied to the relay from a current transformer.
These relay are used on A.C. circuit only and can operate for fault flow in the either direction.
This relay operates when phase to phase fault occurs.
8.1.5 DIRECTIONAL RELAY:
Figure8.4 Directional Relay
This relay operates during earth faults. If one phase touch the earth due to any fault. A
directional power relay is so designed that it obtains its operating torque by the interaction of
magnetic field derived from both voltage and current source of the circuit it protects. The
direction of torque depends upon the current relative to voltage.
An auxiliary relay is used to indicate the fault by glowing bulb alert the employee.
9. MISCELLANOUS EQUIPMENT
9.2 FUSE:
Figure 9.2 Substation Fuse
A fuse is a short piece of wire or thin strip which melts when excessive current through it
for sufficient time. It is inserted in series with the circuit under normal operating conditions; the
fuse element is at a nature below its melting point. Therefore it carries the normal load current
overheating. It is worthwhile to note that a fuse performs both detection and interruption
functions.
11. CONCLUSION
Now from this report we can conclude that electricity plays an important role in our life.
We are made aware of how the transmission of electricity is done. We too came to know about
the various parts of the Substation system.
The Uttar Pradesh Cooperation Limited has got radio communication in microwave
range in order to transmit and receive data with various Substations in Uttar Pradesh to get
reliable transmission and distribution of electricity.