TAMA - Sequencer
TAMA - Sequencer
TAMA - Sequencer
PLEASE READ THE WHOLE USER MANUAL CAREFULLY BEFORE INSTALLING THE EQUIPMENT
DESCRIPTION
Sequencer for dedusting plant cleaning cycle control with
digital dP control by internal transducer. Device with
microprocessor management and zero-crossing detection
for the outputs activation to give high immunity from
external interference and low field emission.
Max 3 output relays, Max 3 digital voltfree input
DOCUMENTATION INDEX
- Introduction
- Installation rules and technical features
- Enter datas in SET MODE
- RUNNING MODE and Alarms description
- Standard features details
- Option on request
- Electrical Wiring Diagram
- Board layout
- Housing and Dimension
- Problems solution
- CE certificate
STANDARD FEATURES
Avoid arranging the device in the proximity of or in direct contact with any source of heat and electromagnetic field. Connect the
device on supply lines different from those used for motor drives or other devices that may cause some noise on the net.
For all input control signals to the Timer (D1a, D5, D6,...) use anti-flame wires with a minimum section of 0.5 mm².
Before acting on the device for any operation, check for safe conditions. For electrical operations never forget to disconnect the
power supply, wait for 30 seconds for the internal capacitors discharge before opening. At the end of the operations close the
device to restore the protection degree before powering again.
For the electrical connection of the supply voltage and filter cleaning electrovalves use anti-flame wires with a minimum section
of 0.75 mm². For output relay contacts use anti-flame wires with a minimum section of 1.5 mm2.
For the output signal 4÷20 mA use anti-flame shielded wire with minimum section of 0,5 mm².
For the electrical connections use antiflame shielded cable 3 x 0,75 mm²
ATTENTION: with output voltage 230VAC use connectors with RC filter or insert it on every supply line of any ev.
If filters are not used, an operating malfunction could happen.
TECHNICAL FEATURES
A wrong supply voltage connection might cause irreparable damages to the device.
The fuse wire protect only from any short circuit and not necessarily from wrong supply voltage.
When supply voltage switch On the cleaning cycle starts if all the necessary conditions for running are
present.
Press key B to enter in SET MODE.
The upper line of the display shows the code and the description of the selected function and the line
below shows the referement code and the value of the fuction indicated (See table SET DATA).
Press key B to increase the number of the selected function.
Press key D to decrease the number of the selected function.
Press key A to increase the set value.
Press key C to decrease the set value.
Press key E to store the SET UP data and to enter in RUNNING MODE.
If for 5 minutes no key is pressed the device change automatically in RUN MODE.
03 PULSE TIME Activation time from 0.05 to 5.00 sec. 0.01÷5.00 B2x 1.00 sec
B3x 1 sec.
04 INTERVAL TIME Interval time between ev. from 1 to 999 sec. 001÷999 B3x 5 sec
B3x 005 sec.
05 POSTCL INT. Interval time between ev. during post-cleaning 001÷999 B3c 5 sec
B3c 005 sec.
08 TEST EV. Manual activation of every single output from keyboard B10
B10 001 OFF
11 FAN THRESHOLD dP threshold for cycle activation after fan stop 0.01÷0.99 D1bx 0.10
D1bx 0.10 kPa
13 dP STOP CYCLE 1st dP threshold, STOP washing since dP low 0.01÷9.99 C1a 1.00
C1a 1.00 kPa
14 dP START CYCLE 2nd dP threshold, START washing since dP high 0.01÷9.99 C1b 2.00
C1b 2.00 kPa
18 EV. VOLTAGE Output voltage setup for ev. (see HVB) (Necessary for right B operating of HV
HV Vout = 24 V B8b)
Pg. 3
INFO MODE
In run mode by pressing key D the device enter in INFO MODE. In this modality is avaliable a
description of keys function in SET UP and RUN MODE.
Press key B to go on in the informations visualization.
Press key E to exit and come back to RUN MODE.
If for 5 minutes no key is pressed the device change automatically in RUN MODE.
NOTE: When the device enter in INFO MODE the cleaning cycle stops. It restart from the beginning
when the device return in RUN MODE.
B Next
E Exit
DISPLAY DESCRIPTION
KEY FUNCTION
IN OPERATING
KEYS FUNCTION
IN SETUP
Pg. 4
RUNNING MODE
When supply voltage switch On the cleaning cycle starts if all the necessary conditions for running are
present.
The upper line of the display shows the differential pressure reading or TC signal reading depend on
the selection (option) and the type of operating mode (Manual / Automatic).
The line below shows a series of informations of the run status and the alarm situations active (See
table below / alarm description).
If no one key is pressed for 30 seconds the backlight brightness decrease, to ensure upper energy
safe and longer life of the display, up to a key is pressed again.
B Enter in SET UP
D Enter in INFO MODE
A Active alarm Scrolling
C Change visualization dP/TC (option)
E Alarm Reset
Cycle waiting for fan start or dP under set fan threshold D1x
VENTILATOR STOP
Pg. 5
ALARMS DESCRIPTION
In run mode the lower line of the display shows the active alarm situations.
By pressing key A it is possible to scroll all the active alarms.
By pressing key E it is possible to reset the alarms.
The table below shows all the possible alarm situations. Some of these are related to particular
options on request and they are not present in Standard version.
The alarm visualization got the priority on other visualization on the 2nd line of the display.
A Alarms scrolling
E Alarms Reset
E6 COMPR. AIR Cycle stop since no consent from compressed air pressure switch D5a
LACK D5a OPEN
Pg. 6
STANDARD FEATURES
Pg. 8
Pg. 9
Pg. 10
Pg. 11
ENCLOSURE TECHNICAL DATAS [7.1]
Pg. 12
PROBLEMS SOLUTION
Display OFF Fuse burnt. Check the protection fuse on supply line.
Supply voltage. Check if supply voltage is present and if it agrees with
Jumper for input voltage selection supply voltage needed by the device (clamps 1 and 2).
Check jumper JP1
No output activation Output voltage. Check that sequencer output voltage and electrovalve
Connection to the electrovalves. coils have the same voltage.
Jumper for output voltage selection Check the connection between sequencer and
electrovalves and do manual test of the outputs (See
B10).
Check jumper JP2 and JP3.
Wrong differential pressure reading. Pneumatic connection not free. Disconnect the 2 pipe to the Timer and verify that dP
Pipe damaged reading is 0.00 kPa. If it is OK check the pipe for air
connection from the device to the filter.
The cleaning cycle do not run in The memory of the microprocessor could be Remove the supply voltage from the Timer. At the same
according to the set value. modified by external factor. time press key B and switch on the supply voltage. By
means of this operation the default data are loaded in
set up. Adjust the zero dP reading and the other
parameters according to the filter's needs.
WARRANTY
The warranty lasts 4 years. The company will replace any defective electronic component, exclusively at our laboratory,
unless otherwise agreed, upon the Company's prior consent.
WARRANTY EXCLUSION
Pg. 13
DICHIARAZIONE DI CONFORMITA' DEL COSTRUTTORE
Direttiva Bassa Tensione (DBT) 2006/95/CE Low Voltage Directive 2006/95/CE related to the
rispondente alle norme Europee armonizzate European Standard EN 60947-1:2004
EN 60947-1:2004
G. BELLINELLI
Amministratore delegato / Managing director