Polywater Pedfloor Sealant Barrier: Description
Polywater Pedfloor Sealant Barrier: Description
Polywater Pedfloor Sealant Barrier: Description
SEALANT BARRIER
DESCRIPTION
Polywater® PedFloor™ seals pad-mounted
equipment openings to prevent outages and
service disruptions due to entry of rodents, water,
and humidity. This resilient, impermeable ground
barrier improves service reliability. PedFloor is
ideal for equipment replacement where pad
opening dimensions and/or pad positions have
changed.
Once PedFloor is mixed and poured into pad
openings, its self-leveling expansion fills voids PedFloor repairs and creates a barrier for cabinet bases.
around conduit stub-ups and cable to create a
smooth yet strong barrier. PedFloor adheres to PRODUCT BENEFITS
fiberglass, polymer concrete, and concrete pads.
The strong, lightweight seal withstands freeze- • Deterrent – Keeps mice, rats, snakes, insects,
thaw cycles and environmental extremes. It will and water from entering the pedestal or
not settle, crack, shrink, or crumble. cabinet.
• Easy to Use – Ready to mix and apply. No
SELF-LEVELING APPLICATION water needed.
PedFloor is easy to install. It flows into the target • Strong – Structural, cross-linked matrix creates
area and expands into voids. a sturdy seal.
• Seals – Flows and self-levels before expansion
to seal the entire opening.
• Re-Enterable – Saw or drill after installation to
install new ducts or cables.
• Protects – Cured product offers permanent
PedFloor is mixed and poured
protection through weather extremes.
PedFloor is engineered with a time delay that
allows the material to flow throughout the target END USE
area. As the surface is covered, it expands and PedFloor repairs small or large areas and can be
cross-links into its final, durable form. It will used to level enclosure bases. Use it with:
naturally flow into small spaces without need for
troweling. • Pedestals
• Cabinets
• Other enclosures
PROPERTY
PART A PART B (CURING PedFloor is cured around a one-inch bar at a depth
(RESIN) AGENT) of 1.5 inches (3.8 cm). Force required to remove
Color Brown Gray the bar is measured. Adhesion is calculated based
Form Viscous liquid Viscous liquid on seal surface area.
300 cps 1,100 cps
MATERIAL ADHESION VALUE
Specific
gravity 1.24 1.07
PVC Excellent 100 psi (0.69 N/mm²)
VOC content 0 g/L 0 g/L
Copper Excellent 90 psi (0.62 N/mm²)
Aluminum Excellent 95 psi (0.66 N/mm²)
CURED PROPERTIES
HDPE Good 25 psi (0.17 N/mm²)
PedFloor cures to form a solid, closed-cell matrix.
PROPERTY TYPICAL RESULT WATER RESISTANCE
Appearance Light gray with small, even PedFloor was tested for water blocking
cells
performance, using ASTM D2842. A large block of
Closed-cell content 98%
the cured material was submersed in water for 96
Density 8 lbs/ft3 (128 kg/m3) hours. Weight water absorbed as a percentage was
Compressive strength 77 psi (0.53 N/mm²) calculated.
(ASTM D1691)
Tensile strength 101 psi (0.70 N/mm2) WATER ABSORPTION
(ASTM D1623) 1.24%
Flexural strength 87 psi (0.60 N/mm2) PedFloor does not hold water. It keeps moisture
(ASTM D790)
out of the system and limits the effect of corrosion.
Seal strength, water 1 ft (0.3 m) water head,
continuous
Dielectric value 61 V/mil ENVIRONMENTAL RESISTANCE
(ASTM D149) PedFloor withstands the rigors of the environment.
Temperature Use Range
MATERIAL COMPATIBILITY -20°F to 200°F (-30°C to 95°C) Continuous
PedFloor is compatible with all cable jacket -40°F to 250°F (-40°C to 120°C) Peak
materials. The foam is an inert solid that will not PedFloor withstands direct sunlight with no
attack the jacket material. decrease in functionality. Surfaces exposed to UV
will discolor and yellow. The cured product retains
CHEMICAL RESISTANCE its hardness and continues to act as a barrier.
PedFloor is resistant to gasoline, oils, dilute acids Discoloration will not harm the performance of the
and bases, and most unsaturated hydrocarbons. material.
PedFloor may also be protected with a
weatherproofing paint or coating. Acrylic, urethane,
and epoxy-based products have excellent adhesion
to the foam.
APPLICATION CURE RATE
Field-Ready Kits Application Temperature
PedFloor is a two-part system packaged in pre- PedFloor will set up and cure more quickly in
measured quantities for easy on-site mixing. warmer temperatures.
Application Temperature TEMPERATURE SEAL FULL
Working temperature for PedFloor is 35°F to FORMATION CURE
110°F (4°C to 43°C). 35°F (2°C) 1 hour 12 hours
70°F (20°C) 20 minutes 4 hours
Usage Quantity
Carefully measure the area to be sealed by 110°F (43°C) 8 minutes 2 hours
multiplying the width by the length of the opening
pad in the structure. Do not subtract any conduits REENTERING
or other stub-up utilities. Use this measurement to
estimate the minimum quantity required. Round up Additional conduits or cables may be passed
to determine the quantity of PedFloor required. It through PedFloor with relative ease. Cured
is best to use field measurements rather than PedFloor may be drilled with auger bits or hole
measurements from plans or specs to calculate a saws designed for wood. The overall integrity of the
job quantity, as the openings to be filled in the field seal allows such drilling without collapsing the seal,
may not have the same dimensions as the an advantage over grout. Simply drill through the
drawing. PedFloor and pass through the conduit or cable.
Once the new conduit or cable is in place, an
Example: Pedestal measuring 1.25 feet (.38 m) by additional application of PedFloor can reseal the
1.5 feet (.45 m). area against future intrusion.
• Pedestal floor is 1.88 ft2 (.17 m2).
• Seal requires one PF-2 kit to cover 2 ft2 at 3 SAFETY
inches depth (.2 m2 at 7.6 cm depth).
PedFloor is a two-part urethane containing reactive
KIT SIZE COVERAGE (3-IN, VOLUME chemicals. Polyurethanes are common in the
7.5-CM DEPTH) COVERAGE construction industry and have been used for many
PF-1 1 ft2, 0.1 m2 0.25 ft3, 7 L years. Some individuals may become sensitized to
PF-2 2 ft2, 0.2 m2 0.50 ft3, 14 L components in the unreacted resin. Precautions
must be observed during use and handling of these
PF-3 3 ft2, 0.3 m2 0.75 ft3, 21 L
materials.
Area Preparation and Application The use of PedFloor in the prepackaged containers
Prepare target area by filling holes and leveling controls and reduces exposure. Use of protective
the surface. Cover pea gravel with one inch of gloves and eyewear is recommended. Once
sand or dirt. Mix two parts well for at least 30 reacted, the foam is a solid, closed-cell
seconds until the product is a uniform gray color. polyurethane. The finished product may be
Slowly pour onto target surface. considered non-toxic. See SDS for more
information.
Circumstances may require an elevated or shelf
application. Plastic sheeting for this method is
included in the product kit. CLEAN-UP
For full installation information, please see the Any unreacted material may be cleaned from
Polywater PedFloor Installation Instructions for surfaces using Polywater’s Grime-Away™
PF-1 and PF-2 or PF-3. Multipurpose Cleaner. Reacted material must be
removed mechanically by scraping or sanding.
STORAGE AND HANDLING ORDER INFORMATION
Keep containers cool, dry, and away from sunlight.
CAT # PACKAGE DESCRIPTION
Product shelf life is 18 months. PF-1 1 – 750-mL burst pack
(2 units/case) 1 – pair of gloves
MODEL SPECIFICATION 1 – instruction sheet
The statement below may be inserted into a Coverage is 1 ft2 (0.1 m2)
customer specification to help maintain
engineering standards and ensure work integrity. PF-2 1 – 1500-mL burst pack
(2 units/case) 1 – pair of gloves
1 – roll duct tape
The approved enclosure/communications
1 – plastic sheet
equipment pad opening sealant shall be Polywater 1 – instruction sheet
PedFloor Sealant Barrier. The base sealant shall
flow and self-level to create a strong cross-linked Coverage is 2 ft2 (0.2 m2)
polymer matrix barrier to seal out water, gases,
and rodents. The base sealant shall be a closed- PF-3 1 – bottle part A
(1 unit/case) 1 – bottle part B
cell foam structure with compression strength
1 – pair of gloves
>70 psi (480 kPa) (ASTM D1621) and dielectric 1 – mixing pail
strength >60 V/mil (2360 V/mm) (ASTM D149). 1 – mixing stick
Base sealant shall block 1-foot (0.03 bar) water 1 – roll duct tape
head pressure continuously. 1 – plastic sheet
Base sealant shall be compatible with cable jacket 1 – instruction sheet
materials. Base sealant shall be chemically
Coverage is 3 ft2 (0.3 m2)
resistant to gasoline, oils, dilute acids and bases,
and most unsaturated hydrocarbons. Base sealant
shall withstand direct sunlight with no decrease in
functionality. Base sealant shall have excellent
adhesion to plastics, PVC, HDPE, metals, copper,
aluminum, wood, fiberglass, polymer concrete,
and concrete. Base sealant shall withstand
freeze/thaw cycles without loss of adhesion. Base
sealant shall not propagate cracks or crumble
when cut or drilled to allow service change-outs.
CONTACT US
+1-651-430-2270 Main | Europe, Middle East, North Africa +31 10 233 0578 | email: support@polywater.com
IMPORTANT NOTICE: The statements here are made in good faith based on tests and observations we believe to be reliable. However, the completeness and accuracy of the information is not
guaranteed. Before using, the end- user should conduct whatever evaluations are necessary to determine that the product is suitable for the intended use.
American Polywater expressly disclaims any implied warranties and conditions of merchantability and fitness for a particular purpose. American Polywater’s only obligation shall be to
replace such quantity of the product proven to be defective. Except for the replacement remedy, American Polywater shall not be liable for any loss, injury, or direct, indirect,
or consequential damages resulting from product’s use, regardless of the legal theory asserted.