INSTRUCTIONS IB-65030

Type PV-38M and PV-27M


Manually Operated
Ground and Test Devices
For use with PV System 38™ and PV System 27™
Metal-Clad Switchgear

Instruction Maintenance Renewal Parts

POWELL
INDUSTRIES, INC.
POWELL ELECTRICAL MANUFACTURING COMPANY
8550 MOSLEY DRIVE • HOUSTON, TEXAS 77075 • USA
PHONE (713) 944-6900 • FAX (713) 947-4453
http://www.powellelectric.com
http://www.powellservice.com
©2001 POWELL ELECTRICAL MANUFACTURING COMPANY ALL RIGHTS RESERVED 04/2004
Type PV-38M and PV-27M Ground and Test Device IB-65030

Contents
Section Page

I. INTRODUCTION ............................................................................................................. 4
A. GENERAL ............................................................................................................................................ 4
B. SCOPE ................................................................................................................................................ 4
C. PURPOSE ........................................................................................................................................... 4
D. INSTRUCTION BULLETINS AVAILABLE ELECTRONICALLY ........................................................... 4
II. SAFETY .......................................................................................................................... 5
A. GENERAL ............................................................................................................................................ 5
B. SPECIFIC ............................................................................................................................................ 5
C. SAFETY LABELS ................................................................................................................................ 5
III. EQUIPMENT DESCRIPTION .......................................................................................... 7
IV. RECEIVING, HANDLING, AND STORAGE..................................................................... 8
A. RECEIVING ......................................................................................................................................... 8
B. HANDLING .......................................................................................................................................... 8
C. STORAGE ........................................................................................................................................... 8
V. OPERATION ................................................................................................................... 9
A. GROUNDING ....................................................................................................................................... 9
B. TESTING ............................................................................................................................................. 9
VI. MAINTENANCE ............................................................................................................ 10
VII. RENEWAL PARTS ........................................................................................................ 10
A. ORDERING ........................................................................................................................................ 10

Figures
Figure Page
Figure 1. Manually Operated Ground and Test Devices: PV-38M and PV-27M ............................................ 4
Figure 2. WARNING Label Attached to the Top, Front, Left Side of Type PV-38M (and PV-27M)
G&T Devices ................................................................................................................................... 5
Figure 3. WARNING Label Attached to All Four Access Doors of Type PV-38M and PV-27M
G&T Devices ................................................................................................................................... 6
Figure 4. CAUTION Label Attached to the Two Top Access Doors of Type PV-38M and PV-27M
G&T Devices ................................................................................................................................... 6
Figure 5: CAUTION Label Attached to the Two Bottom Access Doors of Type PV-38M and PV-27M
G&T Devices. .................................................................................................................................. 6
Figure 6. PV-38M and PV-27M Ground and Test Device Front View ............................................................. 7
Figure 7. PV-38M and PV-27M Ground and Test Device Back View ............................................................. 7
Figure 8. PV-38M and PV-27M Ground and Test Device – Access doors Open and Cables Attached .......... 8

2
Type PV-38M and PV-27M Ground and Test Device IB-65030

WARNING
THIS EQUIPMENT MAY CONTAIN HIGH VOLTAGES AND CURRENTS WHICH CAN CAUSE
SERIOUS INJURY OR DEATH.

THE EQUIPMENT IS DESIGNED FOR USE, INSTALLATION, AND MAINTENANCE BY


KNOWLEDGEABLE USERS OF SUCH EQUIPMENT HAVING EXPERIENCE AND TRAINING IN
THE FIELD OF HIGH VOLTAGE ELECTRICITY. THIS DOCUMENT, AND ALL OTHER
DOCUMENTATION SHALL BE FULLY READ, UNDERSTOOD, AND ALL WARNINGS AND
CAUTIONS SHALL BE ABIDED BY. IF THERE ARE ANY DISCREPANCIES OR QUESTIONS,
THE USER SHALL CONTACT POWELL ELECTRICAL MANUFACTURING COMPANY
IMMEDIATELY AT 1-800-480-7273.

CAUTION

BEFORE ANY ADJUSTMENT, SERVICING, PARTS REPLACEMENT, OR ANY OTHER ACT IS


PERFORMED REQUIRING PHYSICAL CONTACT WITH THE ELECTRICAL WORKING
COMPONENTS OR WIRING OF THIS EQUIPMENT, THE POWER SUPPLY MUST BE
DISCONNECTED. FAILURE TO FOLLOW THIS CAUTION MAY RESULT IN INJURY OR
DEATH.

3
Type PV-38M and PV-27M Ground and Test Device IB-65030

IMPORTANT
THE INFORMATION IN THIS INSTRUCTION BULLETIN DOES NOT PURPORT TO EXPLAIN ALL
DETAILS OR VARIATIONS OF THE MANUAL GROUND AND TEST DEVICES, NOR TO PROVIDE
FOR EVERY POSSIBLE CONTINGENCY OR HAZARD TO BE MET IN CONNECTION WITH
USAGE, INSTALLATION, TESTING, OPERATION, AND MAINTENANCE OF THE EQUIPMENT.
SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE
WHICH ARE NOT COVERED SUFFICIENTLY FOR THE USER’S PURPOSES, THE MATTER
SHOULD BE REFERRED TO POWELL ELECTRICAL MANUFACTURING COMPANY,
1-800-480-7273.

I. INTRODUCTION NOTE: The information in this instruction bulletin is


intended for both PV-38M and PV-27M G&T devices.

A. GENERAL B. SCOPE
The manually operated ground and test (G&T) device The information in this instruction bulletin applies to
is a switchgear assembly accessory that can be the following manually operated G&T devices:
inserted in place of a drawout circuit breaker. The
G&T device can be used to ground the main bus and/ PV-38M –Three Poles; Three Phase, 38kV, 2000 Amp
or external circuits connected to the switchgear
PV-38M –Three Poles; Three Phase, 38kV, 1200 Amp
assembly, and test the primary circuits.
PV-27M –Three Poles: Three Phase, 27kV, 2000 Amp
This bulletin contains instructions for the installation,
operation, and maintenance of the manually operated PV-27M –Three Poles: Three Phase, 27kV, 1200 Amp
Type PV-38M and the PV-27M G&T devices. (See
Figure 1.) C. PURPOSE

The information in this document is intended to


provide instructions for users to properly operate and
maintain the manually operated G&T devices de-
scribed in Section B. SCOPE.

This instruction bulletin contains information on the


following topics:
1. Safety
2. General description of the G&T devices
3. Operating instructions
4. Maintenance
5. Renewal part ordering
The manually operated G&T device enables the user
to access the primary disconnect devices of the
switchgear cell in order to ground the primary circuits
or to conduct high-voltage tests such as, phasing out
circuits or high voltage withstand (hipot).

D. INSTRUCTION BULLETINS AVAILABLE


ELECTRONICALLY
Figure 1. Manually Operated Ground and Test Many Powell Electrical Manufacturing Company
Devices: PV-38M and PV-27M Instruction Bulletins are posted on the company Web
4
Type PV-38M and PV-27M Ground and Test Device IB-65030

site at www.powellservice.com. For information by 3. Service conditions and G&T device applications
telephone, contact Powell Apparatus Service Division shall be considered in the development of
(PASD) at 1-800-480-7273. maintenance programs. Service conditions
include variables such as the following: ambient
temperature; humidity; and any adverse environ-
II. SAFETY mental conditions such as excessive dust, ash,
corrosive atmosphere, vermin, and insect prob-
The user should study this instruction bulletin and all lems.
other associated documentation before uncrating the
G&T device. B. SPECIFIC

Each user has the responsibility to instruct and


implement thorough maintenance and safety proce- The manually operated type PV-38M and PV-27M
dures for each type of equipment used. The user G&T devices are designed for use in the PV-38 and
shall train all personnel associated with the equip- PV-27 Metal-Clad Switchgear respectively, manufac-
ment on usage, installation, operation, maintenance, tured by Powell Electrical Manufacturing Company.
and safety procedures. All safety precautions and DO NOT attempt to use this device in any other class
procedures must be observed. of electrical equipment manufactured by Powell, or
by any other manufacturer.
A. GENERAL Before using the ground and test device, the operator
should reference the equipment drawings and visu-
1. Proper use of the G&T device described in this ally examine the equipment to locate the primary
document requires use of high-voltage testing disconnects to be grounded or tested.
equipment and procedures. Only supervised and
qualified personnel who are trained in the usage, DO NOT ATTEMPT TO USE THE TYPE PV-38M
installation, operation, and maintenance of a AND PV-27M G&T DEVICES TO GROUND AN
manually operated ground and test device shall ENERGIZED CIRCUIT. ATTEMPTING TO USE
be allowed to work on this equipment. It is A G&T DEVICE ON AN ENERGIZED CIRCUIT
mandatory that the operator reads, understands, WILL CAUSE SEVERE DAMAGE TO THE
and complies with the information in this instruc- DEVICE AND SWITCHGEAR IN WHICH IT IS
tion bulletin, supplemental equipment documents, BEING USED, AND MAY RESULT IN SERIOUS
and service advisories. INJURY TO THE OPERATOR.

2. Maintenance programs must be consistent with C. SAFETY LABELS


the customer experience and the manufacturer’s
recommendations, including information avail-
able in service advisories and the instruction Danger, warning, and caution labels are attached to
bulletin(s). A well-planned and executed routine the G&T device in various locations. Personnel must
maintenance program is essential for the G&T observe all danger, warning, and caution labels while
device reliability and safety. handling or maintaining the electrical ground and test
device.

Figure 2. WARNING Label Attached to the Top, Front, Left Side of


Type PV-38M (and PV-27M) G&T Devices

WA R N I N G
DO NOT ATTEMPT TO USE THE TYPE PV-38 M GROUND AND TEST DEVICE TO
GROUND AN ENERGIZED CIRCUIT. AN ATTEMPT TO DO SO WILL RESULT IN SEVERE
DAMAGE TO THE DEVICE AND TO THE SWITCHGEAR IN WHICH IT IS BEING USED AND
MAY RESULT IN SERIOUS INJURY TO THE OPERATOR.

READ INSTRUCTION BOOK IB-65030 BEFORE OPERATING THIS DEVICE.

5
Type PV-38M and PV-27M Ground and Test Device IB-65030

Figure 3. WARNING Label Attached to All Four Access


Doors of Type PV-38M and PV-27M G&T Devices

WA R N I N G
TEST TERMINALS BEHIND THIS DOOR
MAY BE ENERGIZED WITH DANGEROUS VOLTAGES. DO NOT TOUCH TEST
TERMINALS UNTIL YOU HAVE DETERMINED THAT THEY ARE NOT ENERGIZED. TO DO
SO MAY RESULT IN SERIOUS INJURY TO THE OPERATOR.

READ INSTRUCTION BOOK IB-65030 BEFORE OPERATING THIS DEVICE.

Figure 4. CAUTION Label Attached to the Two Top


Access Doors of Type PV-38M and PV-27M G&T Devices

CAUTION
THE TEST PORTS BEHIND THIS DOOR ARE CONNECTED TO THE UPPER PRIMARY
DISCONNECT STUDS OF THE GROUND AND TEST DEVICE. WHEN RACKED INTO A
BREAKER CELL, THESE STABS WILL ENGAGE THE UPPER SET OF PRIMARY STABS
IN THE CELL. BEFORE OPENING THIS DOOR BE SURE THAT THE CIRCUIT YOU WISH
TO GROUND OR TEST IS CONNECTED TO THE UPPER PRIMARY STABS IN THE CELL.

READ INSTRUCTION BOOK IB-65030 BEFORE OPERATING THIS DEVICE.

Figure 5: CAUTION Label Attached to the Two Bottom Access Doors of


Type PV-38M and PV-27M G&T Devices.

CAUTION
THE TEST PORTS BEHIND THIS DOOR ARE CONNECTED TO THE LOWER PRIMARY
DISCONNECT STUDS OF THE GROUND AND TEST DEVICE. WHEN RACKED INTO A
BREAKER CELL, THESE STABS WILL ENGAGE THE LOWER SET OF PRIMARY STABS IN
THE CELL. BEFORE OPENING THIS DOOR BE SURE THAT THE CIRCUIT YOU WISH TO
GROUND OR TEST IS CONNECTED TO THE LOWER PRIMARY STABS IN THE CELL.

READ INSTRUCTION BOOK IB-65030 BEFORE OPERATING THIS DEVICE.

6
Type PV-38M and PV-27M Ground and Test Device IB-65030

III. EQUIPMENT DESCRIPTION and right disconnect stabs of the switchgear compart-
ment. Isolation barriers between the disconnect
stabs are also provided where required.
The Type PV-38M and PV-27M ground and test
(G&T) devices are similar to the PV-38 and the PV-27 The G&T device is equipped with a ground shoe
circuit breakers respectively. The G&T devices and which engages the ground bus in the switchgear cell.
can be inserted in place of a circuit breaker in a A ground bar extends from the ground shoe to the
metal-clad switchgear cell for grounding and testing lower front part of the G&T device (Figure 6, g).
purposes. The manual G&T device comes in a six- Three flexible grounding cables are supplied. In this
stab model. All stabs on this model can be either instruction bulletin, see Section V. OPERATION A.
1200 Amp or 2000 Amp. GROUNDING for proper use of the grounding cables.
The Type PV-38M and the PV-27M Ground and Test The G&T device is equipped with a racking guide
(G&T) Devices consist of a wheeled frame on which which engages and disengages with the racking roller
six primary disconnect stabs are mounted. (See located in the circuit breaker cell. The racking
Figure 6 and Figure 7.) The front of the device has mechanism is operated by the hand crank as de-
four lockable access doors: two (2) upper doors, and scribed in the instruction bulletin of the PV-System 38
two (2) lower doors. (See Figure 8.) Three upper Switchgear and PV System 27 switchgear. The
test stabs are mounted behind the upper access ground and test device is equipped with a rollout
doors, and three lower test stabs are located behind latch to prevent inadvertent removal from the cell.
the lower access doors. Each of the G&T device test
stabs is connected to one of the six primary discon- The PV-38M and the PV-27M Ground and Test
nect stabs in the switchgear compartment. (See Devices can be supplied with the following compat-
Figure 7.) The upper G&T device test stabs are ibility options:
connected to the upper disconnect stabs of the
switchgear compartment. The lower device test • 1200A only
stabs are connected to the lower disconnect stabs of • 2000A only
the switchgear compartment. In each group of G&T The 1200A G&T device is supplied with small, 1.90
device test stabs, the left, center, and right G&T inch diameter, primary disconnect stabs. The 2000A
device test stabs are connected to the left, center, G&T device is supplied with large, 2.75 inch diam-
b eter, primary disconnect stabs.
c
d
a
e
b
f

a g

Figure 6. PV-38M and PV-27M Ground and Test d


Device Front View e
a. Anti-Rollout Latch f
b. Warning Label (specific for PV-38M and PV 27M)
c. Racking Slot Figure 7. PV-38M and PV-27M Ground and Test
d. Nameplate Device Back View
e. Warning Label (specific for each G&T device door) a. Lifting Eyes d. Shutter Operator
f. Caution Label (specific for each G&T device door) b. Upper Primary Disconnects e. Interference Plate
g. Ground Bus c. Lower Primary Disconnects f. Wheels

7
Type PV-38M and PV-27M Ground and Test Device IB-65030

c
b
b

a a

Figure 8. PV-38M and PV-27M Ground and Test Device – Access doors Open and Cables Attached
a. Lower Access Doors c. Test Ports
b. Upper Access Doors e. Grounding Cables

IV. RECEIVING, HANDLING, AND C. STORAGE


STORAGE Since the G&T device is an accessory that is not
normally in continual use, proper storage between
A. RECEIVING uses is essential to maintain the quality and useful-
ness of the device. The following precautions must
Inspect the manually operated ground and test be taken to assure the proper storage of the device.
device when it is received. If damage is found or
1. Since dampness has an adverse effect on the
suspected, immediately file applicable claims with
insulating parts, the G&T device should be
the transportation company, and notify the nearest
carefully protected against condensation. It
representative of Powell Electrical Manufacturing
should be stored in a warm, dry room of moder-
Company.
ate temperature between 40-100 degrees F.
Ground and test devices for outdoor metal-clad
B. HANDLING
switchgear should be stored in the equipment
Lifting eyes, located on each side of the frame top only when power is available and anti-condensa-
(Figure 6, a) are provided for using a lift crane and tion heaters are operating.
harness to move the G&T device. All lifting equip- 2. The G&T device should be stored in a clean
ment including, chains, cables, hooks, and spreader location, free from corrosive gases or fumes.
bars, should be rated to at least 1000 pounds. Particular care should be taken to protect the
equipment from moisture and cement dust, as
After the G&T device is removed from its shipping
this combination has a very corrosive effect on
pallet and carton, the preferred method for moving
many parts. For long storage periods, it is
and handling the device is to roll it on its own wheels
recommended to place a dust cover over the
on a level surface. When rolling the G&T device, it
device regardless of atmospheric conditions.
should be pushed and steered by the frame. DO
NOT HANDLE OR MOVE THE G&T DEVICE BY 3. If the G&T device is stored for any length of time,
THE PRIMARY DISCONNECT STABS AS DAM- it should be inspected periodically to ensure that
AGE TO THE G&T DEVICE MAY OCCUR. rusting has not started and to ensure it is in good
mechanical condition. When the G&T device is
stored in unfavorable atmospheric conditions, it
should be cleaned and dried out before use.
8
Type PV-38M and PV-27M Ground and Test Device IB-65030

V. OPERATION The 1200A ground and test device is supplied


with small (1.90 inch) diameter primary discon-
nect stabs. The 2000A G&T device is supplied
The manually operated ground and test device may
with large (2.75 inch) diameter primary discon-
be used with both grounding and testing functions.
nect stabs.
The procedures for these two types of operations
differ; therefore, the operations are described sepa- 4. With the grounding cables disconnected and the
rately in the following sections. access doors closed, insert the ground and test
device into the breaker cell, and rack it into the
CONNECT position.
CAUTION
5. Open the access doors over the test stabs
BECAUSE OF THE CONSTRUCTION OF connected to the terminals to be grounded.
BUS SECTIONALIZING UNITS, AND OTHER Using a high-voltage voltmeter and test probe
SPECIAL TYPES OF UNITS, IT IS NOT rated for the system voltage, or another safe
POSSIBLE TO MAKE A GENERAL voltage measuring method, verify that the three
STATEMENT ABOUT WHICH SET OF terminals to be grounded are not energized.
PRIMARY DISCONNECTS IS CONNECTED 6. Rack the ground and test device to the DISCON-
TO THE SWITCHGEAR MAIN BUS AND NECT position.
WHICH IS CONNECTED TO THE
OUTGOING CONDUCTORS. BEFORE 7. Bolt the ends of the three grounding cables to the
USING THE GROUND AND TEST DEVICE, three test stabs to be grounded.
THE OPERATOR SHOULD REFERENCE 8. Bolt the three free ends of the grounding cables
THE EQUIPMENT DRAWINGS AND to the ground bus.
VISUALLY EXAMINE THE EQUIPMENT TO
LOCATE THE PRIMARY DISCONNECTS TO 9. Rack the ground and test device fully into the
BE GROUNDED OR TESTED. CONNECT position. The circuit is now grounded.
10. To remove the ground, rack the device back to
the DISCONNECT position and remove it from
A. GROUNDING the cell.
To ground a circuit, perform the following steps:
B. TESTING
1. Deenergize the circuit to be grounded. If there
are power sources to this circuit other than the The ground and test device may be used to gain
circuit breaker where the ground and test device access to switchgear connections for high voltage
is to be used, the switching devices at these testing. For testing, perform the following steps:
alternate sources should be locked or tagged 1. Remove the circuit breaker from the cell to be
open in accordance with the user’s standard tested.
safety procedures to insure that they will not be
closed during the grounding operation. 2. Verify that the diameter of the primary disconnect
stabs of the circuit breaker removed in step 1
2. Remove the circuit breaker from the switchgear match the diameter of the G&T device test stabs.
cell. This action will place the levering-in mecha- See Section V. OPERATION, A. GROUNDING,
nism in the TEST/DISCONNECT position, which step 3. (See Figure 6, b.)
allows the G&T device to be racked into the
switchgear cell. (See Figure 5, c - racking slot.) 3. With the grounding cables disconnected and the
access doors closed, insert the ground and test
3. Verify that the diameter of the primary disconnect device into the breaker cell and rack it into the
stabs of the circuit breaker removed in step 2 CONNECT position.
match the diameter of the mechanically operated
ground and test device. (See Figure 6, b).
The PV-38M and PV-27M Ground and Test
Devices can be supplied with the following two
(2) different compartment compatibility options:
1200A only and 2000A only.

9
Type PV-38M and PV-27M Ground and Test Device IB-65030

WARNING
VI. MAINTENANCE
DO NOT ATTEMPT TO INSTALL THE TYPE The ground and test device requires little routine
PV-38M AND PV-27M GROUND AND TEST maintenance. Proper storage is essential for the
DEVICES IN ANY COMPARTMENT UNLESS manually operated ground and test device when it is
IT HAS BEEN VERIFIED THAT THE not in use. For more details, see Section IV, RE-
PRIMARY DISCONNECT DIAMETERS OF CEIVING, HANDLING AND STORAGE, C. STOR-
THE GROUND AND TEST DEVICE AND THE AGE.
COMPARTMENT TO BE GROUNDED AND/
OR TESTED ARE COMPATIBLE. A The contact surfaces of the primary disconnect stabs
MISMATCH OF DIAMETERS MAY RESULT IN and the fingers of the ground shoe should be lubri-
LOSS OF GROUNDING CAPABILITY AND/OR cated with a thin film of Mobilgrease 28. Before use,
EQUIPMENT DAMAGE. particularly if the ground and test device has been in
storage for a long period of time, wipe these surfaces
with a clean, dry cloth, and apply fresh lubricant.
4. If the testing to be done involves measurement of
system voltages, such as verifying the proper
phase relationship between circuits on the two VII. RENEWAL PARTS
sides of the device, perform the following steps:
a. Open the necessary access doors. A. ORDERING

b. Using proper high voltage instrumentation Should any part require replacement due to wear or
and observing all safety rules, make the damage, order renewal parts from Powell Apparatus
required measurements. Service Division. Visit the Powell Web site at
www.powellservice.com, or call 1-800-480-7273.
5. If the testing to be done involves application of
test voltages, such as for high potential testing, The nameplate, which is located on the G&T device
perform the following steps: top of the right top door, contains information needed
for ordering parts (Figure 6, d). Provide the following
a. Insure that the circuit to be tested is information when ordering parts:
deenergized. See Section, V. OPERATION,
A. GROUNDING, step 1. • Name of the ultimate user
b. Verify that the circuit is deenergized. See • Location of the installation
Section, V. OPERATION, A. GROUNDING,
step 1.
• Type of device including rated voltage and
rated amps (included on nameplate)
c. Attach the test power leads to the appropriate
test stabs and conduct the tests.
• Serial number of the device (included on
nameplate)
6. When testing is completed, perform the following
steps: • Description of the part
a. Remove all test leads. • Photo of the device with the needed part
marked will be helpful in assuring that the
b. Close access doors. proper part is furnished.
c. To remove the G&T device from the cell,
push down on the anti-rollout latch (Figure 6,
a). The G&T device can now be racked to
the DISCONNECT position and removed
from the cell.

10
Type PV-38M and PV-27M Ground and Test Device IB-65030

Index
A G N
Access doors 7 Ground bar 7 Nameplate 10
Anti-condensation heaters 8 Ground bus 10
O
Anti-rollout latch 10 Ground shoe 7
Grounding cables 7 Operation
C
grounding 9
H
Contact Powell 3 testing 9
Corrosive effect 8 High voltages 3 Ordering parts 10
D I P
Description Instruction bulletin Powell Electrical Manufacturing
anti-rollout latch 7 available electronically 4 Telephone number 5
caution label 7 Introduction Web Site 5
ground bus 7 high-voltage tests 4 Powell Electrical Manufacturing
interference plate 7 purpose 4 Company 4
lifting eyes 7 PV-27M 4 primary disconnect stab 7
lower primary disconnects 7 PV-38M 4
R
lower test stabs 7 safety 5
nameplate 7 general 5 Racking guide 7
racking slot 7 safety labels 5 Receiving Handling and Storage
shutter operator 7 specific 5 anti-condensation heaters 8
upper primary disconnects 7 scope 4 corrosive effect 8
warning label 7 Isolation barriers 7 handling 8
wheels 7 inspect periodically 8
L
storage 8
E
Lifting eyes 8
S
Equipment Description 7 Lower test stabs 7
grounding and testing 7 Safety
M
primary disconnects 7 description 5
upper test stabs 7 Metal-clad switchgear 7 specific 5
Six-stab units 7
Storage 8

11