THT-100-4/8T-10-F-300: Technical Characteristics
THT-100-4/8T-10-F-300: Technical Characteristics
THT-100-4/8T-10-F-300: Technical Characteristics
17/05/2021
THT-100-4/8T-10-F-300
400°C/2h and 300°C/2h tubular axial extract fans with short casings
Tubular axial extract fans with short casing for immersed operation in fire risk zones.
Fan:
- Tubular sheet steel casing.
- Variable angle rotors made of cast aluminium.
- Approved in accordance with standard EN 12101-3. With certifications no.: 0370-CPR-
0305 (F-400) and 0370-CPR-0973 (F-300).
- Airflow direction from motor to impeller.
Motor:
- Class H motors for S1 continuous operation and S2 emergency use. With ball bearings,
IP55 protection and 1 or 2 speeds, depending on model.
- IE3 efficiency motors for powers equal to or greater than 0.75kW except single-phase, 2-
speed and 8-pole.
- Three-phase 230/400V-50Hz. (up to 3kW) and 400/690 V-50 Hz. (powers higher than
3kW).
- Maximum temperature of air to be carried: S1 -20°C +40°C continuous service, also
suitable for warm climates with temperatures up to 50°C. S2 operation, 300°C/2h,
400°C/2h.
Finish:
- Anti-corrosive finish of polyester resin polymerised at 190°C, previously degreased with
phosphate-free nanotechnological treatment.
Available versions:
- THT/CL: tubular axial fans with long casings, fitted with inspection hatches.
On request:
- Airflow direction from impeller to motor.
- 100% reversible impellers.
TECHNICAL CHARACTERISTICS
ERP
MOTOR DATA
v1.21.0.0
www.sodeca.com DB v1.21.7.0 Data in this report can change without notice 1/2
TECHNICAL DATA REPORT
17/05/2021
DIMENSIONS
ØA ØB C ØD E ØJ N
1115 1070 590 1000 450 15 16x22º30´
Dimensions without explicitly defined units are shown in millimeters (mm). Dimensions depending on the motor are approximate
v1.21.0.0
www.sodeca.com DB v1.21.7.0 Data in this report can change without notice 2/2