Project : AL FRIAH PALACE

Type of Unit: Ceiling Mounted Type


Location: First Floor (F-R4)
Unit Designation: EF # 5

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 212cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.15
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


7 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Total 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

7 16 23

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.15 23 0.03

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.035 0 0.03
Project : AL FRIAH PALACE
Type of Unit: Roof Mounted Type
Location: Roof Deck
Unit Designation: REF # 1

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 6,150cfm
A.3 Initial Duct Velocity (fpm) 1300fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.056
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


69 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 2 5 10
Take-Off 1 40 40
Elbow 90º 6 40 240

Total 290

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

69 290 359

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.056 359 0.20

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 1 0.08 0.08
Supply & Return Air 1 0.20 0.2

Total 0.28

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.201 0.28 0.48


Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: Annex
Unit Designation: EF # 11

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 80cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.27
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


23 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Total 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

23 16 39

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.27 39 0.11

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.105 0 0.11
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: Ground Floor (G-R7)
Unit Designation: EF # 10

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 177cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.17
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


23 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Total 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

23 16 39

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.17 39 0.07

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.066 0 0.07
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: Ground Floor (G-R3)
Unit Designation: EF # 9

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 124cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.2
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


23 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Total 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

23 16 39

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.2 39 0.08

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.078 0 0.08
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: Ground Floor (G-R2)
Unit Designation: EF # 8

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 132cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.2
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


23 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Project : AL FRIAH PALACE 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

23 16 39

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.2 39 0.08

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.078 0 0.08
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: Ground Floor (G-R1)
Unit Designation: EF # 7

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 110cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.24
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


48 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 3 10 30

Total 36

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

48 36 84

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.24 84 0.20

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.202 0 0.20
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: First Floor (F-R5)
Unit Designation: EF # 6

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 177cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.17
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


43 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 2 10 20

Total 26

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

43 26 69

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.17 69 0.12

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.117 0 0.12
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: First Floor (F-R4)
Unit Designation: EF # 5

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 212cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.15
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


7 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Total 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

7 16 23

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.15 23 0.03

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.035 0 0.03
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: First Floor (F-R3)
Unit Designation: EF # 4

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 185cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.18
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


7 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Total 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

7 16 23

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.18 23 0.04

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.041 0 0.04
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: First Floor (F-R2)
Unit Designation: EF # 3

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 71cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.27
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


10 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 1 10 10

Total 16

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

10 16 26

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.27 26 0.07

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.070 0 0.07
Project : AL FRIAH PALACE
Type of Unit: Ceiling Mounted Type
Location: First Floor (F-R1)
Unit Designation: EF # 2

A. General Design Criteria:

A.1 Elevation (ft) 2,047ft.


A.2 Fan Capacity (cfm) 389cfm
A.3 Initial Duct Velocity (fpm) 800fpm
A.4 Duct Material Type Galvanized Iron Sheet
A.5 Friction Loss (in. w.g.) 0.11
A.6 Duct Size Method Equal Friction

B. Length of straight duct for the farthest terminal


8.2 Feet

C. Fittings Equivalent Feet of Straight Duct


Description Quantity Equivalent Total
( ft ) ( ft )
Transition 1 5 5
Take-Off 1 1 1
Elbow 90º 2 10 20

Total 26

D. Total Length
Length of Duct Fittings Eq. Total
( ft ) ( ft ) ( ft )

8.2 26 34.2

E. Duct Static Pressure :


Friction Loss Total Length Total S.P.
( in. wg) ( ft ) ( in. wg)

0.11 34.2 0.04

F. Additional Friction Loss


Description Quantity Eq. Total
( in. wg) ( in. wg)
Electric Duct Heater 0 0.13 0
Sound Attenuator 0 0.50 0
Volume Damper 0 0.08 0
Supply & Return Air 0 0.20 0

Total 0

G. Total External StaticPressure

Duct S.P. Additional F.L. Total


( in. wg) ( in. wg) ( in. wg)

0.038 0 0.04